Field Wiring

Allfield wiring to this block are standard screw, clamp-type terminals which can be operated with a flat or phillips-head screwdriver. Each terminal accepts one AWG #12 or two AWG #14 wires. The

° °

° oo minimum recommended wire size is AWG #22. The | 112) SERIAL 1 terminals can accommodate spade or ring terminals up 2 2) SERIAL 2 to 0.27 inch (6.85 mm) in width with a minimum p 3 |O|] SHIELD IN opening for a #6 screw, and up to 0.20 inch (5.1 mm) 41Q]| SHIELD ouT depth from the screw center to the back barrier. Co oof

Connect a DC power source to the DC+ terminal (5) and the return to the DC- terminal (22). Depending on the layout and current loads, positive and negative connections can be bussed and made by individual wires back to the block or power source.

| ae de

© ae

Connections for a DC Sink Block

|

Any circuit can be an input or output. Connect one _ 4 terminal of the device to the block (terminals 6-21). FIELD | a | Connect outputs to DC+ and inputs to DC-. rors | OE | DEVICES | 16 eo | . . po | DC Sink Block, Power Disconnects Loe no 7 | Since block power is the same as circuit power, it is oe 1918 | important to wire block power disconnects so that 20| block power and input power will be removed at the 21 OH same time. | 22[)|| oc 1 rete DC SINK DC SINK L_DEVICES__| BLOCK

Sink Block, Wiring for Tristate Inputs

De + If any input is configured as a Tristate Input, install a resistor across the dry contacts of the

Oo Io9- - ¢ DC a44473 use the Open Wire diagnostic.

YES NO °. = | : | | - IN

Caution : | |

If circuit power is not removed at the same & time as block power, the block may power up when multiple inputs are activated, even though one leg of power has been removed from the block.

For a 24/48 VDC block, the resistor should be 5.1K ohms, 1/2 Watt or larger. For a 24 VDC block, the resistor should be 1.6K ohms.

Genius I/O Discrete and Analog Blocks User’s Manual, September 1993 input device. This added resistance is required to

GEK-90486D-2

Page 10 read from a scan by OCR; it may hold reading errors

GEK-90486D-2

Connections for a DC Source Block

Any circuit can be an input or output. Connect one terminal of the device to the block (terminals 6-21). Connect outputs to DC- and inputs to DC+.

For a DC source block, connect outputs to the negative side of the power supply and inputs to the positive side. No logic inversion is needed.

a41552

° ° rome} fe}

SERIAL 1

SERIAL 2 wh || =>

QOS

SHIELD IN

SHIELD OUT pct

| | Selalsiolala l |

FIELD INPUT DEVICES l alae lI eae

Ole)

Nh = a

DC SOURCE

DC Source Block, Power Disconnects

Since block power is the same as circuit power, it is important to wire block power disconnects so that block power and input power will be removed at the same time. Locate the power disconnect as shown at right above.

a44472 DC SOURCE BLOCK

Bren De + | =

T

DC, Caution

If circuit power is notremoved at the same time as block power, the block may power up whenmultiple inputs are activated, even though one leg of power has, been removed from the block.

Source Block, Wiring for Tristate Inputs

Ifany input is configured as a Tristate Input, install a resistor across the dry contacts of the input device. This added resistance is required to use the Open Wire diagnostic.

O a44473 | + | |

For a 24/48 VDC block, the resistor should be 5.1K ohms, 1/2 Watt or larger. For a 24 VDC block, the resistor should be 1.6K ohms.

Wiring for a Bus Switching Module

If the block will be a BSM Controller, attach the BSM like a load to circuit 1. Connect either BSM pigtail wire to terminal 6. For a DC Sink block, connect the other BSM wire to DC+. Fora DC Source block, connect the other BSM wire to DC-.

Chapter 8 16 Circuit DC Input/Output Blocks 8-9

Page 11 read from a scan by OCR; it may hold reading errors

Block Configuration

8-10

The configurable features of a 16 Circuit DC Input/Output Block are listed below. For many, the factory setting may not need to be changed.

Feature Circuit or | Selections Factory Setting Block

Device Number* Block null 0 to 31 (anumber must be selected) Reference Address* Block none Depends on host CPU type BlockI/OType* Block input input, output, combination Baud Rate* Block 153.6 std 153.6 std, 153.6.ext,76.8, 38.4 Kbd Pulse Test for Outputs Block enabled enabled, disabled Input Filter Time Block 20mSec 10-100mSec in 10mS steps CircuitI/ OType Circuit input input, output, tristate input Report Faults Circuit yes yes, no Hold Last State Circuit no yes, no Output Default State Circuit off on, off Detect No Load Circuit yes yes, no Overload Shutdown Circuit yes yes, no BSM Present Block no yes, no BSM Controller Block no yes, no Output Default Time Block 3 bus scans (for bus redundancy) 2.5 or 10 sec Redundancy Mode Block none none, hot standby, duplex, GMR Duplex Default Block off on, off

Features marked with an asterisk in the table are configured from the Program Block ID screen of the Hand-held Monitor, as explained in chapter 3.

The rest of the features can be configured either using a Hand-held Monitor, or by sending a Write Configuration datagram to the block from the host.

Before configuration begins, the feature of each 16 Circuit DC Input/Output Block should be decided upon, then recorded on copies of the Configuration Worksheet printed on the next page.

Genius I/O Discrete and Analog Blocks User’s Manual, September 1993

GEK-90486D-2

Page 12

Block

Location

Block Features: Configuration Protected (Y/N) Block Number (0–31)

Block Type (Input/Output/Combination)

Reference Address through

Baud Rate (153.6 Kb Std/153.6 Kb Ext/76.8 Kb/38.4 Kb) Pulse Test (Enabled/Disabled)

Input Filter Time (5–100) mS

Redundancy Features: Redundancy Mode (None/Standby/Duplex, GMR)

Duplex Default (on/off)

BSM Present (Y/N)

Outputs Default (2.5/10 sec)

BSM Controller (Y/N)

Circuit Features: Ckt #

Reference Number

I/O Type (I/O/IT*)

Report Faults (yes/no)

(output) Hold Last State (yes/no)

(output) Default State (ON/OFF)

(output) Report No Load (yes/no)

(output) Overload Shutdown (yes/no)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 * IT (Tristate Input) must have 5.1K ! resistor across dry contacts of input device

GEK-90486D-2

8-11

Page 13 read from a scan by OCR; it may hold reading errors

Pulse Test Pulse Testing verifies the ability of a block’s outputs to change state. A new block is configured to enable Pulse Testing. Pulse Testing should remain enabled if the block has loads that hold one state for long periods of time, unless any load(s) are sensitive to pulses or interruptions of up to 16mS. It should be disabled if the block’s loads will normally change state as the program executes. These will report faults during normal operation, and do not need to be pulsed. Hand-held Monitor Configuration Steps 1. To change the current selection, press F2 (tgl).. Press F3 (enter). PULSE TEST : ; . REF 2. Press F4 (next) to advance to the next configuration display. ENABLED tgl entr nxt

8-12

Pulse Testing Outputs

Outputs can be pulse-tested from a Hand-held Monitor or by sending a command from the CPU. Pulse Testing checks the continuity of each output circuit including the switch device, power source, wiring, interposing devices (fuses, circuit breakers, terminals), and output device. It works whether or not there is minimum current to check for a No-Load condition. Pulse testing will not activate mechanical devicesjsuchhas motor starters, relays, or solenoid valves.

Pulse Testing should.momentarily cause outputs that are OFF to turn ON and outputs that are ON to go OFE Progressively longer pulses are applied until the desired circuit function is sensed. If the pulse width reaches the maximum of 16mS without detecting valid operation, one of these fault conditions is reported:

Failed Switch: Ifthe output does not change state when pulsed.

Short Circuit: Ifthe load on an output that was OFF exceeds 10 amps when pulsed ON.

No Load: If the load on an output that was OFF draws less than 50 mA when pulsed ON.

If the output was OFE no current flow when the output is pulsed indicates an open circuit or failed switch. Similarly, continued current flow when ON outputs are pulsed OFF indicates a shorted switch (both malfunctions are reported to the CPU).

Genius I/O Discrete and Analog Blocks User’s Manual, September 1993 GEK-90486D-2

Page 14 read from a scan by OCR; it may hold reading errors

Pulse Test Description

Pulse Testing switches a load to the opposite state then back again. This should occur so quickly that there is no effect on the mechanics or contact outputs of the load device.

Specific Pulse Test operation depends on whether or not No Load detection is enabled.

A. If No Load detection is enabled, the block looks for presence or absence of load current, using the normal No Load threshold. This verifies load continuity.

B. If No Load detection is NOT enabled, Pulse Testing tests only that the block output is switching voltage.

Pulse Testing begins with narrow pulses. If the appropriate condition described above is found on the first try, the test is complete. If the condition is not found, the test is repeated with successively longer pulses (2.5mS increments) until successful. The maximum Pulse Test time is 16 mS. If this time is reached and the result is still not successful, a fault message is generated.

The normal pulse width seen by the load is typically shorter than the maximum 16msS.

A. With No Load detection enabled, the pulses requlred may be longer due to the rise time of the load current and the load inductance.

Power devices such as contactors and actuators will typically encounter maximum width pulses. Such devices draw moderate.currents and are not affected by pulsing.

Low-power signal relays may have low current draw, high-inductance coils, and fast operation. Such devices may have to be.examined closely.

B. With No Load detection NOT enabled, a successful Pulse Test normally occurs in 4mS to 6mS. The time may be slightly longer if there are capacitive loads.

Suitable Loads for Pulse Testing Aresistive and/or inductive load is suitable for Pulse Testing if any of the following is true: A. If No Load detectiomis enabled:

1. The minimum pickup current of the load is less than the No Load threshold of theblock. The maximum threshold of the block is 50mA, but typlcal values are 20mA\to 35mA.

When testing on-off-on operation, typical devices with rated currents of 75mA and up are suitable.

When testing off-on-off operation, certain devices may require the addition of a flyback diode directly across the load coil to increase the dropout time.

2. The minimum pickup delay is greater than 16mS, and the dropout delay is greater than 5mS. Devices that have slow or delayed operation may be unsuitable because they will ride through the maximum width pulses.

3. The rise time of current in the load, at normal voltage, allows the peak current to reach the threshold in less time than the device delay, as well as less than the 16mS maximum pulse width. The load current must reach 50mA before the contacts switch. If necessary, the load current can be increased by adding a resistor load across the coil, and the device end of the wiring. This will permit testing of wiring continuity, but it may not detect an open coil.

B. IfNo Load detection is NOT enabled, the minimum pickup or dropout delay is greater than 5mS.

GEK-90486D-2 Chapter 8 16 Circuit DC Input/Output Blocks 8-13

Page 15 read from a scan by OCR; it may hold reading errors

Input Filter Time

An input filter time of 5mS to 100mS can be selected for the block. The default filter time is 20mS.

The block continuously samples an input for the length of the filter time period. If the input remains either on or off for the length of the Filter Time, the block recognizes its state. For example:

a42504

\@ OFF p< ON STATE + - - 20ms - - _> | SIGNAL Sampled Inputs Sampled Inputs Sampled Inputs ON for 5mS ON for 30mS OFF for 3mS not recognized recognized by block not recognized

IF FILTER TIME = 20mS

An input filter helps reject spurious noise. spikes and multiple inputs generated by the bounce of mechanical devices. In controlled, noise-free environments, signals generated by clean, solid state electronics may be unnecessarily slowed by a filter, delaying system response. In such an environment, no additional filter time is needed.

In noisy environments, useva longer filter time to prevent noise from possibly causing erratic or unsafe system operations.

For a block with tristate inputs, the minimum recommended Input Filter Time is 50mS.

Hand-held Monitor:Configuration Steps

1. The screen displays the currently-selected filter time. If this INPUT FILTR TIME time should be changed, press F2 (tgl) to display the other filter REF times. To save a new selection, press F3 (entr).

FILTER= 20mS tgl entr nxt

NS

Press F4 (next) to advance to the next configuration display.

8-14 Genius I/O Discrete and Analog Blocks User’s Manual, September 1993 GEK-90486D-2

Page 16 read from a scan by OCR; it may hold reading errors

I/O Circuit Type

Anearlier configuration step selected the Block I/O type (on the Program Block ID screen). That step determined whether the block would be assigned all input references, all output references, or both. The default configuration for each circuit on the block is input. On the screen shown below, the I/O type of each circuit can be changed.

If the Block I/O Type selection was Input, each circuit can be either an regular input (I) or a tristate input (It). Select Tristate Input for any input circuit that should report the Open Wire diagnostic.

If the Block I/O Type is Output, each circuit must be an output (O).

If the Block I/O Type is Combination, each circuit can be configured as an input,(I), an output (O), or a tristate input (I7). Select Tristate Input for any input circuit that should report the Open Wire diagnostic.

Hand-held Monitor Configuration Steps

1. The screen displays the current I/O type of each circuit on the

I/O CIRCUIT CFG block. On this screen, REF [=the circuit ieonftmar Was 2 input IITIIIIIIIIIIIII = the circuit is configured.as an input.

> tgl entr nxt O = the circuit.is.configured as an output ly = the circuit is configured as a tristate input

2. Toselect a circuit, press F1 (>). To change a selection, press F2 (tgl).

3. »To save the new selection, press F3 (entr).

4, Press‘F4 (next) to advance to the next configuration display.

GEK-90486D-2 Chapter 8 16 Circuit DC Input/Output Blocks 8-15