Chapter
8
16 Circuit DC Input/Output Blocks
Four different types of 16-Circuit DC I/O Blocks are available. There are two source blocks, which provide current to field output devices:
m 24VDC Sourceblock(IC660BBD022), for use with 2-wire and 3-wire solid state sensors and electromechanicalsensors.
m 24/48VDC Sourceblock (IC660BBD020), for use with 3-wire solid state sensors and electromechanical sensors.
There are also two sink blocks, which receive current from field output devices:
m 24VDCSinkblock (IC660BBD023), for use with 2-wire and 3-wire solid state sensors and electromechanicalsensors.
m 24/48VDCSinkblock (IC660BBD021), for use with 3-wire solid state sensors and electromechanical sensors.
Features
Genius 16 Circuit DC Input/Output blocks have 16 discrete circuits, each easily configured to be an input, tristate input, or output. Output circuits can be connected directly to input circuits without the use of other components or inversion of, logic states.
Control power is tapped off the input/output device voltages wired;to the terminals. No separate block power supply is needed:
Configurablefeaturesinclude:
Output Pulse Testcapability
Selectable Input Filter Time from 10mS to 100mS Output powerup defaults
Output Hold Last State or default
CPU Redundancy type
Bus Switching Module control
The block’s advanced diagnostics can pinpoint causes of installation and run-time errors. Each circuit has electronic circuit protection that shuts down an output if inductive surge current exceeds 15 amps for more than 10mS. The output is easily restored by command from a Hand-held Monitor or the CPU.
GEK-90486D-2
Additional diagnostics of these blocks are: m= Overtemperature Failed)\Switch Open Wire for Tristate Inputs
Overload Detection and Shutdown No-load Detection
Ds, = a44485
> Re
4OWUOyY
GENIUS $l og] 24/48 vDC rn B |=! Source In/Out = m *2)2<| GE Fanuc oBl/Eo sa/8 Qo g
1 b £ @ srjstjfeferjarjin jor) ef ey ej sis} ele lz]
-309l St fl eb Zt oul OF 6 8 £ 9 G
2A/Pt Max 154 Max Total
Compatibility
These blocks can be used with any Genius bus controller. They can also be used with a PCIM or QBIM module. They are compatible with all Genius Hand-held Monitors.
8-1
Page 3
Specifications Block Type: 16 circuit discrete input and output CatalogNumbers: 24/48 VDC 16 CircuitSourceI/O Block IC660BBD020 Terminal Assembly only IC660TSD020 ElectronicsAssemblyonly IC660EBD020 (sameas block IC660BBD022) 24VDC Source 16 Circuit Source I/O Block IC660BBD022 Terminal Assembly only IC660TBD022 ElectronicsAssemblyonly IC660EBD020 (same as block IC660BBS020) 24/48VDC 16CircuitSinkI/OBlock IC660BBD021 Terminal Assembly only IC660TSD021 ElectronicsAssembly only IC660EBD021 (sameas block IC660BBD023) 24VDC 16 Circuit Sink I/O Block IC660BBD023 Terminal Assembly only IC660TBD023
ElectronicsAssembly only
IC660EBD021 (sameas block IC660BBD021)
Size (height x width x depth): Weight:
LEDS (block):
LEDs (each circuit):
Heat Dissipation:
Block to Block Isolation:
8.83” (22.44cm) x3.50” (8.89cm) x3.94” (10.00cm) 4 lbs. (1.8 kg)
Unit OK, I/O Enabled
Individual load side indicators
68.8 Watts with 16 outputs on at 2 amps.
1500 V
Operating voltage: 18-56 VDC (24/48 V), 18-30 VDC (24 V) Ripple (maximum): 10% Required DC power: 150mA typical/300mAmaximum Power supply dropout time: 10mS Input Characteristics: For standard input, voltage relative to (DC-) Source Blocks Sink Blocks Input ON, 24 VDC supply 16-24 VDC 0-8 VDC 48 VDC supply* 32-48 VDC * 0-16 VDC* Input OFF, 24 VDC supply, 0-7 VDC 17-24 VDC 48 VDC supply* 0-14 VDC* 34-48 VDC*
Input processing time (typical) Input impedance (typical) Selectable input filter times Input diagnostics
5.6K ohms (24/48V), 1.8K ohms (24V)
1.7mS (plus selectable filter delay)
5-100mS
Open wire, Overtemperature, Failed Switch
OutputCharacteristics: Output current (steady state) Maximuminrush current Block output current
2 amps per circuit 10 amps up to 10mS 15 amps at 35C
OutputOFF leakage current 1.0mA
Maximumswitching frequency Once per second (high inrush current)
Output turn-on delay (maximum) 1mS
Output voltage drop 2.0 volts maximum at 2 amps inrush
Minimum Recommended Load 50 mA with No Load nabled
Output Diagnostics Short Circuit, Overload, No Load, Failed Switch, Overtemperature Environmental:
Operating temperature 0 to +60C (32 to +140F)
Storage temperature -40 to +100C (-40 to +212F)
Humidity 5 to 95% (non-condensing)
Vibration 5-10Hz 0.2” (5.08mm) displacement, 10-200Hz at 1G
8-2
*, for24/48VDCblocks
Genius I/O Discrete and Analog Blocks User’s Manual, September 1993
GEK-90486D-2
Page 4
DC+
Configured as an Input
DC+
Input Device
75V
1–16
Smart Switch
I/O 5.6K
Configured as an Output
Output Device
.1"F
Processor
1200!
LED
DC–
DC–
Field Connections
Terminal Assembly
Electronics Assembly
DC+
DC+
.1"F Configured as an Output
LED
1200!
Output Device
* I/O
Configured as an Input
Input Device DC– Field Connections
*
Smart Switch
1–16
Processor
75V DC–
Terminal Assembly
Electronics Assembly
5.6K ohms for 24/48 VDC blocks. 1.8K ohms for 24 VDC blocks
GEK-90486D-2
8-3
Page 5
Inputs and Outputs
8-4
The block can be configured as an inputs-only, outputs-only, or combination block. Regardless, the block always broadcasts two bytes of data each bus scan, and accepts two bytes of data each bus scan.
If the block is configured as an inputs-only block, all circuits must be regular inputs or tristate inputs. The block will use 16 input references and NO output references.
If the block is configured as an outputs-only block, all circuits must be regular outputs; no feedback analysis will be performed. The block will use 16 output references and NO input references.
If the block is configured as a combination block circuits can be any mix of inputs and/or outputs. The block will use 16 input references and 16 output references, The actual state of each output circuit will be returned to the CPU in the corresponding input references location. The CPU can monitor the feedback state to-verify (after an appropriate delay) that the output switching device has operated properly and that the load has the proper voltage and current applied.
Appendix B shows reference usage for a Series 90, Series Six, or Series Five PLC.
Input Data Format A 16 Circuit DC I/O Block broadcasts 2 bytes.of input data each bus scan.
Byte # Description 0 Inputs 1 - 8 (input 1 in bit 0) 1 Inputs 9, 16 (input 9 in bit 0)
Output Data Format
The block receives 2 bytes of output data from the bus controller each bus scan.
Byte # Description 0 Outputs 1 - 8 (output 1 in bit 0) 1 Outputs 9 - 16 (output 9 in bit 0)
Hand-held Monitor I/O Display
The Hand-held Monitor displays the I/O types (line 3) and current states (line 4) of all circuits on the Monitor Block screen.
REF 1 - 160; 1234567890123456 IIIIIIIIIIIIIIIO,
1101010010010101
Individual circuits are displayed on the Monitor/Control Reference screen (which also shows a circuit’s fault and force status).
Genius I/O Discrete and Analog Blocks User’s Manual, September 1993 GEK-90486D-2
Page 6
Diagnostics
GEK-90486D-2
The block always performs its standard diagnostic checks, plus two optional output diagnostics. The block reports all faults to the Hand-held Monitor, and takes appropriate corrective action.
Individual circuits can be configured not to send diagnostic messages to the CPU ifa fault occurs. If the CPU requests diagnostic information from the block using Read Diagnostics datagrams, the block returns current diagnostics for all circuits, including any with CPU fault reporting disabled.
Overtemperature Diagnostic
Each circuit has a built-in thermal sensor. If the block’s internal temperature exceeds 100C, the block sends an OVERTEMPERATURE message and turns off the circuit to protect its internal electronics. This diagnostic is always performed for both inputs and outputs.
Short Circuit Diagnostic
Automatic output diagnostic. Output circuits are protected by a short circuit level sensor at the switching device. If the instantaneous current on an output exceeds 10 amps at turn-on, the block turns the output off within microseconds. The block will try to restart the load; if two attempts are unsuccessful, the output circuit is forced off and the block sends a SHORT CIRCUIT message. To restore normal operation to output the cause of the current surge must be removed, then the diagnostic must be cleared from the HHM or the CPU.
This diagnostic detects shorts across the load only. Also, systems with floating power supplies do not detect shorts of [/O points to ground because there is no return current path. Systems with power supplies grounded on the negative side detect grounded output points. either as Failed Switch (sink blocks) of Short Circuit (source blocks).
Partial (high resistance) shorts may not draw enough current during a Pulse Test to be detected by. the Pulse Test.
Failed Switch Diagnostic
The blockautomatically monitors all circuits for several types of faults, which may be reported as Failed Switch diagnostics.
For an output, Failed Switch is reported if the circuit’s switch state is not the same as its commanded state. The block sends a FAILED SWITCH message identifying the failed circuit. The logic state of the circuit is set to OFF
When an output fault occurs, the actual condition of the output switch is not known. If the output switch has failed shorted (or closed), current flow is not interrupted when the block forces the output state OFF Action external to the block must be taken to remedy the problem. The FAILED SWITCH message can alert personnel or cause program logic to be activated, possibly shutting off power to the block, I/O section, or process.
Several additional switch faults independent of the output state are detected and reported as Failed Switch faults on both input and output-configured circuits. Examples include loss of communications with the block’s internal microprocessor and some internal power supply faults.
Chapter 8 16 Circuit DC Input/Output Blocks 8-5
Page 7
Open Wire Diagnostic
The block automatically performs this diagnostic on any circuit configured as a tristate input. It will detect an electrical (not mechanical) malfunction in a circuit. In addition to being configured as a tristate input, the circuit must have a non-inductive resistor placed as close as practical to the actual dry contacts (such as across the field device terminals). For the 24/48 VDC blocks (IC660BBD020 and 021), a 5.1K ohm external resistor should be used. For the 24 VDC blocks (IC660BBD022 and 023), a 1.6K ohm external resistor should be used.
DC Source Block Tristate Input Thresholds
Normal Thresholds Tri-state Thresholds 941553 Dc* DC* Os L aa ! = oN =, ON wwery-ay S oo CHEV
OFF eer, - - - - - 50%, - - - - - 50% IN, - - - - - - - - - - 30%, ______ 30% OFF OPEN WIRE =
_ a | DC- DC= Ls
DC Sink Block Tristate Input Thresholds
Normal Thresholds Tri-state Thresholds a41567 DC* DCt ° + OFF OPEN WIRE = 70%, - _____ - - 70% |
50% 50% | IN OFF |, - - - - - ____ - 7V | ON, - ___ - - - - 4V = | ON ah Dc- a” DC- O-
With,the switch closed (ON state), the circuit senses the low source impedance. With the switch open (OFF state), the circuit senses the added resistance. If a wire is broken, cut or removed, impedance becomes very high. The block will transmit 0 as the state of the input, and send an OPEN WIRE message.
Since faulty input circuit monitoring requires specific current flows, devices as photo-sensors, electronic high-speed counters, instrumentation, fiber optic sensors, and similar electronic devices cannot be monitored for Open Wire conditions. Such devices should be set up as standard, not tristate, inputs.
GE offers compatible input devices including a 5.1K ohm monitoring resistor with its line of General Purpose Control sensor devices.
Genius I/O Discrete and Analog Blocks User’s Manual, September 1993 GEK-90486D-2
Page 8
No Load Diagnostic
The optional No Load diagnostic can be enabled or disabled for individual outputs.
For a new block, outputs are configured to report No-Load conditions. In this configuration, energizing the output activates a no-load current level. If the load does not continuously draw 50mA from the output circuit, the block sends a NO LOAD message. Because this diagnostic monitors both current and voltage, a No Load condition may cause an HHM monitoring the block to display 0 for the circuit although there is voltage at the output and the circuit LED is on.
This diagnostic should be not be used for circuits on which very small loads (small relays, transformers, or indicating lamps) will draw less than 50 mA.
Overload Diagnostic Like No-Load detection, this diagnostic is optional for individual outputs on the block.
In addition to the protection provided by the block’s built-in Short Circuit detection, Overload Shutdown provides further protection for output loads, field wiring, and switching devices. If a load exceeds 2.8 amps DC continuously for 10mS, the block will turn the output off and send an OVERLOAD message if Overload Shutdown is enabled.
For a load that requires more than 2 amps DC, the output can be configured not to shut off at this level or send the OVERLOAD message. These restrictions apply:
1. Maximum load current: 5 amps DC
2. Maximum duty cycleslimit duty cycle so that: (load current) x (% ON) is less than 1.0 amp.
3. Maximum ON time: I minute 4. Maximum total current of all outputs ON at the same time is less than 16 amps.
For example, a maximum 5 amp load can be pulsed at a 20% duty cycle, or up to 1 minute ON.and 9 minutes OFE Higher repetition rates can be used if the duty cycle is maintained. The duty cycle derating to an average of 1 amp output current and the ON time limit are needed to avoid overheating due to increased power dissipation in the block at these high currents. Exceeding these limits may cause an overtemperature fault.
GEK-90486D-2 Chapter 8 16 Circuit DC Input/Output Blocks 8-7