Page 284

Appendix Instruction Timing

A The Series 90-30, 90-20, and Micro PLCs support many different functions and function blocks. This appendix contains tables showing the memory size in bytes and the execution time in microseconds for each function. Memory size is the number of bytes required by the function in a ladder diagram application program. Two execution times are shown for each function: Execution Time

Description

Enabled

Time required to execute the function or function block when power flows into and out of the function. Typically, best-case times are when the data used by the block is contained in user RAM (word-oriented memory) and not in the discrete memory.

Disabled

Time required to execute the function when power flows into the function or function block; however, it is in an inactive state, as when a timer is held in the reset state.

Note Timers and counters are updated each time they are encountered in the logic, timers by the amount of time consumed by the last sweep and counters by one count.

Note For the 350, 351, 352, and 360 PLC CPUs, times are identical except for the MOVE instruction, which is different for the 350 CPU - refer to the note at the bottom of the table on page A-6.

GFK-0467M

A-1

Page 285

A

Table A-1. Instruction Timing, Standard Models Function Group Timers

Counters Math

Relational

Enabled

Disabled

Increment

311

313

331

340/41

311

313

331

340/41

311

313

331

340/41

Size

On-Delay Timer Off-Delay Timer Timer Up Counter Down Counter Addition (INT)

146 98 122 137 136 76

81 47 76 70 70 47

80 44 75 69 69 46

42 23 40 36 37 24

105 116 103 130 127 41

39 63 54 63 61 0

38 58 53 62 61 1

21 32 30 33 31 0

– – – – – –

– – – – – –

– – – – – –

– – – – – –

15 9 15 11 11 13

Addition (DINT)

90

60

60

34

41

1

0

0

–

–

–

–

13

Subtraction (INT)

75

46

45

25

41

0

1

0

–

–

–

–

13

Subtraction (DINT)

92

62

62

34

41

1

0

0

–

–

–

–

13

Function

Multiplication (INT)

79

49

50

28

41

0

1

0

–

–

–

–

13

Multiplication (DINT) Division (INT)

108 79

80 51

101 50

43 27

41 41

1 0

0 1

0 0

– –

– –

– –

– –

13 13

Division (DINT)

375

346

348

175

41

1

0

0

–

–

–

–

13

Modulo Division (INT)

78

51

49

27

41

0

1

0

–

–

–

–

13

Modulo Div (DINT)

134

103

107

54

41

1

0

0

–

–

–

–

13

Square Root (INT)

153

124

123

65

42

0

1

0

–

–

–

–

9

Square Root (DINT) Equal (INT)

268 66

239 35

241 36

120 19

42 41

0 1

0 1

1 0

– –

– –

– –

– –

9 9 9

Equal (DINT)

86

56

54

29

41

1

0

0

–

–

–

–

Not Equal (INT)

67

39

35

22

41

1

1

0

–

–

–

–

9

Not Equal (DINT)

81

51

51

28

41

1

0

0

–

–

–

–

9

Greater Than (INT)

64

33

35

20

41

1

1

0

–

–

–

–

9

Greater Than (DINT) Greater Than/Eq (INT)

89 64

59 36

58 34

32 19

41 41

1 1

0 1

0 0

– –

– –

– –

– –

9 9

57

Greater Than/Eq (DINT)

87

58

Less Than (INT)

66

35

Less Than (DINT)

87

57

Less Than/Equal (INT)

66

36

34

Less Than/Equal (DINT) Range (INT)

86 92

57 58

56

Range(DINT)

106

75

Range(WORD)

93

60

54 57 54

30

41

1

0

0

–

–

–

–

9

19

41

1

1

0

–

–

–

–

9

30

41

1

1

0

–

–

–

–

9

21

41

1

1

0

–

–

–

–

9

31 29

41 46

1 1

1 0

0 1

– –

– –

– –

– –

9 15

37

45

0

0

0

–

–

–

–

15

29

0

0

0

0

–

–

–

–

15

Notes: 1. Time (in microseconds) is based on Release 5.01 of Logicmaster 90-30/20 software for Models 311, 313, 340, and 341 CPUs (Release 7 for the 331). 2. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 3. Enabled time for single length units of type %R, %AI, and %AQ. 4. COMMREQ time has been measured between CPU and HSC. 5. DOIO is the time to output values to discrete output module. 6. Where there is more than one possible case, the time indicated above represents the worst possible case.

A-2

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 286

A

Table A-1. Instruction Timing, Standard Models-Continued Function

Enabled

Group Bit Operation

Data Move

Table

Function Logical AND Logical OR

Disabled

Increment

311

313

331

340/41

311

313

331

340/41

311

313

331

340/41

Size

67 68

37 38

37 38

22 21

42 42

0 0

0 0

1 1

– –

– –

– –

– –

13 13 13

Logical Exclusive OR

66

38

37

20

42

0

1

1

–

–

–

–

Logical Invert, NOT

62

32

31

17

42

0

1

1

–

–

–

–

9

Shift Bit Left

139

89

90

47

74

26

23

13

11.61

11.61

12.04

6.29

15

Shift Bit Right Rotate Bit Left

135 156

87 127

85 126

45 65

75 42

26 1

24 1

13 0

11.63 11.70

11.62 11.78

12.02 12.17

6.33 6.33

15 15

Rotate Bit Right

146

116

116

62

42

1

1

0

11.74

11.74

12.13

6.27

15

Bit Position

102

72

49

38

42

1

0

0

–

–

–

–

13

Bit Clear

68

38

35

21

42

1

1

1

–

–

–

–

13

Bit Test

79

49

51

28

41

0

0

1

–

–

–

–

13

Bit Set Masked Compare (WORD)

67 217

37 154

37

42 107

0 44

0 39

0 21

– –

– –

– –

– –

13 25

Masked Compare (DWORD)

232

169

141 156

20 74 83

108

44

39

22

–

–

–

–

25

Move (INT)

68

37

39

20

43

0

0

0

1.62

1.62

5.25

1.31

13

Move (BIT)

94

62

64

35

42

0

0

0

12.61

12.64

12.59

6.33

13

Move (WORD)

67

37

40

20

41

0

0

0

1.62

1.63

5.25

1.31

13

Block Move (INT)

76

48

50

28

59

30

30

16

–

–

–

–

27

Block Move (WORD) Block Clear

76 56

48 28

49 27

29 14

59 43

29 0

28 0

15 0

– 1.35

– 1.29

– 1.40

– 0.78

27 9

Shift Register (BIT)

201

153

153

79

85

36

34

18

0.69

0.68

0.71

0.37

15

Shift Register (WORD)

103

53

52

29

73

25

23

12

1.62

1.62

2.03

1.31

15

Bit Sequencer

165

101

99

53

96

31

29

16

0.07

0.07

0.08

0.05

15

COMM_REQ Array Move

1317

1272 1489

884

41

2

0

0

–

–

–

–

13

INT

230

201

177

104

72

41

40

20

1.29

1.15

10.56

2.06

21

DINT

231

202

181

105

74

44

42

23

3.24

3.24

10.53

2.61

21

BIT

290

261

229

135

74

43

42

23

–.03

–.03

-0.01

0.79

21

BYTE WORD

228 230

198 201

176 177

104 104

74 72

42 41

42 40

23 20

0.81 1.29

0.82 1.15

8.51 10.56

1.25 2.06

21 21

Search Equal INT

197

158

123

82

78

39

37

20

1.93

1.97

2.55

1.55

19

DINT

206

166

135

87

79

38

36

21

4.33

4.34

4.55

2.44

19

BYTE

179

141

117

74

78

38

36

21

1.53

1.49

1.83

1.03

19

WORD

197

158

123

82

78

39

37

20

1.93

1.97

2.55

1.55

19

Notes: 1. Time (in microseconds) is based on Release 5.01 of Logicmaster 90-30/20 software for Models 311, 313, 340, and 341 CPUs (Release 7 for the 331). 2. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 3. Enabled time for single length units of type %R, %AI, and %AQ. 4. COMMREQ time has been measured between CPU and HSC. 5. DOIO is the time to output values to discrete output module. 6. Where there is more than one possible case, the time indicated above represents the worst possible case. 7. For instructions that have an increment value, multiply the increment by (Length –1) and add that value to the base time.

GFK-0467M

Appendix A Instruction Timing

A-3

Page 287

A

Table A-1. Instruction Timing, Standard Models-Continued Function

Enabled

Group

Function

311

313

331

Disabled 340/41

311

313

331

Increment 340/41

311

313

331

340/41

Size

Search Not Equal INT

198

159

124

83

79

39

36

21

1.93

1.93

2.48

1.52

19

DINT

201

163

132

84

79

37

35

21

6.49

6.47

6.88

3.82

19

BYTE

179

141

117

73

79

38

36

19

1.54

1.51

1.85

1.05

19

WORD

198

159

124

83

79

39

36

21

1.93

1.93

2.48

1.52

19

198 206

160 167

125 135

82 88

79 78

37 38

38 36

19 20

3.83 8.61

3.83 8.61

4.41 9.03

2.59 4.88

19 19

2.03

Search Greater Than INT DINT BYTE

181

143

118

73

79

37

36

19

3.44

3.44

3.75

WORD

198

160

125

82

79

37

38

19

3.83

3.83

4.41

2.59

19 19

Search Greater Than/Eq INT

197

160

124

83

77

38

36

20

3.86

3.83

4.45

2.52

19

DINT BYTE

205 180

167 142

136 118

87 75

80 79

39 37

36 37

21 20

8.62 3.47

8.61 3.44

9.02 3.73

4.87 2.00

19 19

WORD

197

160

124

83

77

38

36

20

3.86

3.83

4.45

2.52

19

Search Less Than INT

199

159

124

84

78

38

36

20

3.83

3.86

4.48

2.48

19

DINT

206

168

135

87

79

38

38

19

8.62

8.60

-1.36

4.88

19

BYTE WORD

181 199

143 159

119 124

75 84

80 78

38 38

37 36

20 20

3.44 3.83

3.44 3.86

3.75 4.45

2.00 2.48

19 19

Search Less Than/Equal

Conversion

INT

200

158

124

82

79

38

37

21

3.79

3.90

4.45

2.55

19

DINT

207

167

137

88

78

39

37

19

8.60

8.61

9.01

4.86

19

BYTE

180

143

119

74

78

40

37

19

3.46

3.44

3.73

2.02

19

WORD

200

158

124

82

79

38

37

21

3.79

3.90

4.45

2.55

19

Convert to INT

74

46

39

25

42

1

1

1

–

–

–

–

9

Convert to BCD–4

77

50

34

25

42

1

1

1

–

–

–

–

9

Notes: 1. Time (in microseconds) is based on Release 5.01 of Logicmaster 90-30/20 software for Models 311, 313, 340, and 341 CPUs (Release 7 for the 331). 2. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 3. Enabled time for single length units of type %R, %AI, and %AQ. 4. COMMREQ time has been measured between CPU and HSC. 5. DOIO is the time to output values to discrete output module. 6. Where there is more than one possible case, the time indicated above represents the worst possible case. 7. For instructions that have an increment value, multiply the increment by (Length –1) and add that value to the base time.

A-4

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 288

A

Table A-1. Instruction Timing, Standard Models-Continued Function

Enabled

Disabled

Increment

Group

Function

311

313

331

340/41

311

313

331

340/41

311

313

331

340/41

Size

Control

Call a Subroutine Do I/O

155 309

93 278

192 323

85 177

41 38

0 1

0 0

0 0

– –

– –

– –

– –

7 12

PID – ISA Algorithm

1870

1827

1812

929

91

56

82

30

–

–

–

–

15

PID – IND Algorithm

2047

2007

2002

1017

91

56

82

30

–

–

–

–

15

–

–

–

–

–

–

–

–

–

–

–

–

–

93 –

54 37

63 309

45 161

41 –

2 2

0 0

0 0

– –

– –

– –

– –

9 9

End Instruction Service Request #6 # 7 (Read) # 7 (Set)

–

37

309

161

–

2

0

0

–

–

–

–

9

#14

447

418

483

244

41

2

0

0

–

–

–

–

9

#15

281

243

165

139

41

2

0

0

–

–

–

–

9

#16 #18

131 –

104 56

115 300

69 180

41 –

2 2

0 0

0 0

– –

– –

– –

– –

9 9

#23

1689

1663

1591

939

43

1

0

0

–

–

–

–

9

#26//30*

1268

1354

6680

3538

42

0

0

0

–

–

–

–

9

#29 Nested MCR/ENDMCR Combined

–

–

55

41

–

–

1

0

–

–

–

–

9

135

73

68

39

75

25

21

12

–

–

–

–

8

*Service request #26/30 was measured using a high speed counter, 16-point output, in a 5-slot rack. Notes: 1. Time (in microseconds) is based on Release 5.01 of Logicmaster 90-30/20 software for Models 311, 313, 340, and 341 CPUs (Release 7 for the 331). 2. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 3. Enabled time for single length units of type %R, %AI, and %AQ. 4. COMMREQ time has been measured between CPU and HSC. 5. DOIO is the time to output values to discrete output module. 6. Where there is more than one possible case, the time indicated above represents the worst possible case. 7. For instructions that have an increment value, multiply the increment by (Length –1) and add that value to the base time.

GFK-0467M

Appendix A Instruction Timing

A-5

Page 289

A

Table A-2. Instruction Timing, 35x-36x Models Function Group

Function

Timers

Enabled

Disabled

Increment

350/351/36x

350/351/36x

350/351/36x

352

6

– –

4 2

–

3

– –

2

On-Delay Timer Timer

4 3

Enabled Disabled Increment 352

352

Size

5

– –

15 15

–

15

– –

13 13 13

Off-Delay Timer

3

Counters

Up Counter Down Counter

1 3

3 3 3 3

1

2 2 2 2

Math

Addition (INT)

2

0

–

1

0

–

Addition (DINT)

2

0

–

2

0

–

19

Addition (REAL)

52

0

–

33

0

–

17

Subtraction (INT) Subtraction (DINT)

2 2

0 0

– –

1 2

0 0

– –

13 19

Subtraction (REAL)

53

0

–

34

0

–

17

Multiplication (INT)

21

0

–

21

0

–

13

Multiplication (DINT)

24

0

–

24

0

–

19

Trigonometric

Multiplication (REAL)

68

1

–

38

1

–

17

Division (INT) Division (DINT),

22 25

0 0

– –

22 25

0 0

– –

13 19

Division (REAL)

82

2

–

36

2

–

17

Modulo Division (INT)

21

0

–

21

0

–

13

Modulo Div (DINT)

25

0

–

25

0

–

19

Square Root (INT) Square Root (DINT)

42 70

1 0

– –

41 70

1 0

– –

10 13

Square Root (REAL)

137

0

–

35

0

–

11

SIN (REAL)

360

0

–

32

0

–

11

COS (REAL) TAN (REAL)

319 510

0 1

– –

29 32

0 1

– –

11 11

ASIN (REAL)

440

0

–

45

0

–

11

ACOS (REAL)

683

0

–

63

0

–

11 11

ATAN (REAL)

264

1

–

33

1

–

Logarithmic

LOG (REAL)

469

0

–

32

0

–

11

Exponential

LN (REAL) EXP

437 639

0 0

– –

32 42

0 0

– –

11 11

EXPT

89

1

–

54

1

–

17

Radian Conversion

Convert RAD to DEG

65

1

–

32

1

–

11

Convert DEG to RAD

59

0

32

0

11

Notes: 1. Time (in microseconds) is based on Release 7 of Logicmaster 90-30/20/Micro software for Model 351 and 352 CPUs. 2. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 3. Enabled time for single length units of type %R, %AI, and %AQ. 4. COMMREQ time has been measured between CPU and HSC. 5. DOIO is the time to output values to discrete output module. 6. Where there is more than one possible case, the time indicated above represents the worst possible case.

A-6

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 290

A

Table A-2. Instruction Timing, 35x-36x Models-Continued Function

Disabled

Increment

Enabled Disabled Increment

350/351/36x

350/351/36x

350/351/36x

352

352

352

Size

Equal (INT)

1

0

–

1

0

–

10

Equal (DINT)

2

0

–

2

0

–

16

Equal (REAL) Not Equal (INT)

57 1

0 0

– –

28 1

0 0

– –

14 10

Not Equal (DINT)

1

0

–

1

0

–

16

Not Equal (REAL)

62

0

–

31

0

–

14

Greater Than (INT)

1

0

–

1

0

–

10

Greater Than (DINT) Greater Than (REAL)

1 57

0 0

– –

1 32

0 0

– –

16 14

Greater Than/Equal (INT)

1

0

–

1

0

–

10

Greater Than/Equal (DINT)

1

0

–

1

0

–

10

Greater Than/Equal (REAL)

57

1

–

31

1

–

14

Less Than (INT)

1

0

–

1

0

–

10

Less Than (DINT) Less Than (REAL)

1 58

0 1

– –

1 36

0 1

– –

16 14

Group Relational

Enabled Function

Less Than/Equal (INT)

1

0

–

1

0

–

10

Less Than/Equal (DINT)

3

0

–

3

0

–

16

Less Than/Equal (REAL) Range (INT) Range (DINT)

37

0

0

1

2

1

1 0

1 0

14 13 22

–

2 1

– – –

Range (WORD)

2 1

– – –

37

2

–

13

Bit

Logical AND

2

0

–

2

0

–

13

Operation

Logical OR

2

0

–

2

0

–

13

Logical Exclusive OR

1

0

–

1

0

–

13

Logical Invert, NOT Shift Bit Left

1 31

0 1

– 1.37

1 31

0 1

– 1.37

10 16

Shift Bit Right

28

0

3.03

28

0

3.03

16

Rotate Bit Left

25

0

3.12

25

0

3.12

16

Rotate Bit Right

25

0

4.14

25

0

4.14

16

Bit Position

20

1

–

20

1

–

13

Bit Clear Bit Test

20 20

0 0

– –

20 20

0 0

– –

13 13

Bit Set Mask Compare (WORD)

19

1

1

0

– –

19

52

52

0

– –

13 25

Mask Compare (DWORD)

50

0

–

49

0

–

25

Notes: 1. Time (in microseconds) is based on Release 7 of Logicmaster 90-30/20/Micro software for Model 351 and 352 CPUs. 2. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 3. Enabled time for single length units of type %R, %AI, and %AQ. 4. COMMREQ time has been measured between CPU and HSC. 5. DOIO is the time to output values to discrete output module. 6. Where there is more than one possible case, the time indicated above represents the worst possible case. 7. For instructions that have an increment value, multiply the increment by (Length –1) and add that value to the base time.

GFK-0467M

Appendix A Instruction Timing

A-7

Page 291

A

Table A-2. Instruction Timing, 35x-36x Models-Continued Function

Enabled

Disabled

Increment

Enabled

Disabled

Increment

350/351/36X

350/351/36X

350/351/36X

352

352

352

Size

2 28

0 0

0.41 4.98

2 28

0 0

0.41 4.98

10 13

Move (WORD)

2

0

0.41

2

0

0.41

10

Move (REAL)

24

1

0.82

24

1

0.82

13

Block Move (INT)

2

0

–

2

0

–

28

Block Move (WORD) Block Move (REAL)

4 41

4 0

– –

3 41

0 0

– –

28 13

Block Clear

1

0

0.24

1

0

0.24

11

Shift Register (BIT)

49

0

0.23

46

0

0.23

16

Shift Register (WORD)

27

0

0.41

27

0

0.41

16

Bit Sequencer

38

22

0.02

38

22

0.02

16

COMM_REQ

765

0

–

765

0

–

13

Group

Function

Data Move

Table

Move (INT) Move (BIT)

Array Move INT

54

0

0.97

54

0

0.97

22

DINT

54

0

0.81

54

0

0.81

22

BIT

69

0

0.36

69

0

0.36

22

BYTE

54

1

0.64

54

1

0.64

22

WORD

54

0

0.97

54

0

0.97

22

Search Equal INT

37

0

0.62

37

0

0.62

19

DINT BYTE

41 35

1 0

1.38 0.46

41 35

1 0

1.38 0.46

22 19

WORD

37

0

0.62

37

0

0.62

19

Search Not Equal INT

37

0

0.62

37

0

0.62

19

DINT

38

0

2.14

38

0

2.14

22

BYTE

37

0

0.47

37

0

0.47

19

WORD

37

0

0.62

37

0

0.62

19

Search Greater Than INT

37

0

1.52

37

0

1.52

19

DINT

39

0

2.26

39

0

2.26

22

BYTE

36

1

1.24

36

1

1.24

19

WORD

37

0

1.52

37

0

1.52

19

Search Greater Than/Equal INT

37

0

1.48

37

0

1.48

19

DINT BYTE

39 37

0 1

2.33 1.34

39 37

0 1

2.33 1.34

22 19

WORD

37

0

1.48

37

0

1.48

19

Notes: 1. Time (in microseconds) is based on Release 7 of Logicmaster 90-30/20/Micro software for 350 and 360 Series CPUs. 2. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 3. Enabled time for single length units of type %R, %AI, and %AQ. 4. COMMREQ time has been measured between CPU and HSC. 5. DOIO is the time to output values to discrete output module. 6. Where there is more than one possible case, the time indicated above represents the worst possible case. 7. For instructions that have an increment value, multiply the increment by (Length –1) and add that value to the base time.

A-8

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M