Series 90-30/20/Micro PLC CPU Instruction Set Reference Manual: Appendix A - Instruction Timing, pages 292 to 299
Pages 292 to 299 of 337, from Series 90-30/20/Micro PLC CPU Instruction Set Reference Manual
The original document is the PDF (4.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the GE Fanuc IC692CPU211D / IC692MDR541C, Fanuc IC692CPU211D / IC692MDR541C, GE IC692CPU211D / IC692MDR541C and GE Fanuc IC693CPU311X
Page 292
A
Table A-2. Instruction Timing, 35x-36x Models-Continued Function Group
Function
Enabled
Disabled
Increment
Enabled
Disabled
Increment
350/351/36x
350/351/36x
350/351/36x
352
352
352
Size
37 41
0 1
1.52 2.27
37 41
0 1
1.52 2.27
19 22
Search Less Than INT DINT BYTE
37
0
1.41
37
0
1.41
19
WORD
37
0
1.52
37
0
1.52
19
Search Less Than/Equal
Conversion
Control
INT
38
0
1.48
38
0
1.48
19
DINT
40
1
2.30
40
1
2.30
22
BYTE WORD
37 38
0 0
1.24 1.48
37 38
0 0
1.24 1.48
19 19
Convert to INT
19
1
–
19
1
–
10
Convert to BCD-4
21
1
–
21
1
–
10
Convert to REAL
27
0
–
21
0
–
8
Convert to WORD
28
1
–
30
1
–
11
Truncate to INT
32
0
–
32
0
–
11
Truncate to DINT
63
0
–
31
0
–
11
Call a Subroutine
72
1
–
73
1
–
7
Do I/O PID – ISA Algorithm*
114 162
1 34
– –
115 162
1 34
– –
13 16
PID – IND Algorithm*
146
34
–
146
34
–
16
End Instruction
–
–
–
–
–
–
–
Service Request #6
22
1
–
22
1
–
10
#7 (Read)
75
1
–
75
1
–
10
#7 (Set) #14
75 121
1 1
– –
75 121
1 1
– –
10 10
#15
46
1
–
46
1
–
10
#16
36
1
–
36
1
–
10
#18
261
1
–
261
1
–
10
#23
426
0
–
426
0
–
10
#26//30** #29
2260 20
1 0
– –
2260 20
1 0
– –
10 10
1
1
–
1
1
–
4
See Table A-3
26.50
#43 Nested MCR/ENDMCR Combined Sequential Event Recorder (SER)
See Table A-3
*The PID times shown above are based on the 6.5 release of the 351 CPU. **Service request #26/30 was measured using a high speed counter, 16-point output, in a 5-slot rack. Notes: 1. Time (in microseconds) is based on Release 7 of Logicmaster 90-30/20/Micro software for 350 and 360 Series CPUs. 2. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 3. Enabled time for single length units of type %R, %AI, and %AQ. 4. COMMREQ time has been measured between CPU and HSC. 5. DOIO is the time to output values to discrete output module. 6. Where there is more than one possible case, the time indicated above represents the worst possible case. 7. For instructions that have an increment value, multiply the increment by (Length –1) and add that value to the base time.
GFK-0467M
Appendix A Instruction Timing
A-9
Page 293
A
Table A-3. SER Function Block Timing Configuration
Example
No power flow (disabled), Contiguous 8 channels 16 channels 24 channels 32 channels 8 + 8 contiguous channels 8 + 8 + 8 contiguous channels 8 + 8 + 8 + 8 contiguous channels Noncontiguous 8 channels 16 channels 24 channels 32 channels Reset with 8 channels with 16 channels with 24 channels with 32 channels Notes:
A-10
%I1 - 8 %I1 - 16 %I1 - 24 %I1 - 32 %I1 - 8 and %Q1 - 8 %I1 - 8, %Q1 - 8 and %M1 - 8 %I1 - 8, %Q1 - 8 and %M1 - 8 and %T1 - 8
Time (µsec) 26.50 79.94 80.58 81.56 81.73 111.03 143.38 175.79
%I1, %M10, %Q3, etc. 299.64 552.83 806.35 1059.85, - - - 162.63 267.51 372.73 477.95
When a slot with an Input module is specified add an additional 46 µsecs to each of the Contiguous and Noncontiguous timings. When the trigger occurs, add an additional 29 usec if using BCD format or 148 usec if using Posix format. Times shown for reset are for the maximum buffer size of 1024 samples. (Reset clears all samples in the sample buffer.)
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 294
A
Table A-4. Instruction Timing, 37x Models Function
Enabled Disabled Increment
Group
Function
Timers
37x
On-Delay Timer Timer
4 2
37x
37x
Size
5
– –
15 15
–
15
– –
13 13
2 2 2 2
Off-Delay Timer
3
Counters
Up Counter Down Counter
2 1
Math
Addition (INT)
1
0
–
13
Addition (DINT)
2
0
–
19
Addition (REAL)
5
0
–
17
Subtraction (INT) Subtraction (DINT)
1 2
0 0
– –
13 19
Subtraction (REAL)
5
0
–
17
Multiplication (INT)
5
0
–
13
Multiplication (DINT)
5
0
–
19
Trigonometric
Multiplication (REAL)
5
0
–
17
Division (INT) Division (DINT),
5 5
0 0
– –
13 19
Division (REAL)
5
0
–
17
Modulo Division (INT)
5
0
–
13
Modulo Div (DINT)
5
0
–
19
Square Root (INT) Square Root (DINT)
5 10
0 0
– –
10 13
Square Root (REAL)
5
0
–
11
SIN (REAL)
10
0
–
11
COS (REAL) TAN (REAL)
10 10
0 0
– –
11 11
ASIN (REAL)
10
0
–
11
ACOS (REAL)
10
0
–
11 11
ATAN (REAL)
5
0
–
Logarithmic
LOG (REAL)
5
0
–
11
Exponential
LN (REAL) EXP
5 10
0 0
– –
11 11
EXPT
10
0
–
17
Radian Conversion
Convert RAD to DEG
5
0
–
Convert DEG to RAD
5
0
11 11
Notes: 1. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 2. Enabled time for single length units of type %R, %AI, and %AQ. 3. COMMREQ time has been measured between CPU and HSC. 4. DOIO is the time to output values to discrete output module. 5. Where there is more than one possible case, the time indicated above represents the worst possible case.
GFK-0467M
Appendix A Instruction Timing
A-11
Page 295
A
Table A-4. Instruction Timing, 37x Models- Continued Function
Enabled Disabled Increment
Group Relational
Function
Size
37x
37x
37x
Equal (INT)
1
0
–
10
Equal (DINT)
2
0
–
16
Equal (REAL) Not Equal (INT)
5 1
0 0
– –
14 10
Not Equal (DINT)
1
0
–
16
Not Equal (REAL)
5
0
–
14
Greater Than (INT)
1
0
–
10
Greater Than (DINT) Greater Than (REAL)
1 5
0 0
– –
16 14
Greater Than/Equal (INT)
1
0
–
10
Greater Than/Equal (DINT)
1
0
–
10
Greater Than/Equal (REAL)
5
0
–
14
Less Than (INT)
1
0
–
10
Less Than (DINT) Less Than (REAL)
1 5
0 0
– –
16 14
Less Than/Equal (INT)
1
0
–
10
Less Than/Equal (DINT)
3
0
–
16
Less Than/Equal (REAL) Range (INT) Range (DINT)
5
0
2
0 0 0
14 13 22
Range (WORD)
2 1
– – – –
13
Bit
Logical AND
2
0
–
13
Operation
Logical OR
2
0
–
13
Logical Exclusive OR
1
0
–
13
Logical Invert, NOT Shift Bit Left
1 5
0 0
– 1
10 16
Shift Bit Right
5
0
1
16
Rotate Bit Left
5
0
1
16
Rotate Bit Right
5
0
1
16
Bit Position
5
0
–
13
Bit Clear Bit Test
5 5
0 0
– –
13 13
Bit Set Mask Compare (WORD)
5
0
9
0
– –
13 25
Mask Compare (DWORD)
10
0
–
25
Notes: 1. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 2. Enabled time for single length units of type %R, %AI, and %AQ. 3. COMMREQ time has been measured between CPU and HSC. 4. DOIO is the time to output values to discrete output module. 5. Where there is more than one possible case, the time indicated above represents the worst possible case.
A-12
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 296
A
Table A-4. Instruction Timing, 37x Models- Continued Function Group
Disabled
Increment
Function
Data Move
Table
Enabled 37x
37x
37x
Size
Move (INT) Move (BIT)
2 5
0 0
1 1
10 13
Move (WORD)
2
0
1
10
Move (REAL)
5
0
1
13
Block Move (INT)
2
0
–
28
Block Move (WORD) Block Move (REAL)
3 11
0 1
– –
28 13
Block Clear
1
0
1
11
Shift Register (BIT)
10
0
1
16
Shift Register (WORD)
15
0
1
16
Bit Sequencer COMM_REQ
14 200
10 200
1 –
16 13
Array Move INT
10
0
1
22
DINT
15
0
1
22
BIT
10
0
1
22
BYTE
10
0
1
22
WORD
10
0
1
22
5 5
0 0
1 2
19 22
Search Equal INT DINT BYTE
5
0
1
19
WORD
5
0
1
19
Search Not Equal INT
5
0
1
19
DINT
10
0
2
22
BYTE WORD
5 5
0 0
2 2
19 19
Search Greater Than INT
5
0
1
19
DINT
5
0
2
22
BYTE
10
0
1
19
WORD
5
0
1
19
Search Greater Than/Equal INT
5
0
1
19
DINT BYTE
5 5
0 0
2 1
22 19
WORD
5
0
1
19
Notes: 1. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 2. Enabled time for single length units of type %R, %AI, and %AQ. 3. COMMREQ time has been measured between CPU and HSC. 4. DOIO is the time to output values to discrete output module. 5. Where there is more than one possible case, the time indicated above represents the worst possible case. 6. For instructions that have an increment value, multiply the increment by (Length –1) and add that value to the base time.
GFK-0467M
Appendix A Instruction Timing
A-13
Page 297
A
Table A-4. Instruction Timing, 37x Models- Continued Function Group
Function
Enabled
Disabled
Increment
37x
37x
37x
Size
5 10
0 0
1 2
19 22
Search Less Than INT DINT BYTE
5
0
1
19
WORD
5
0
1
19
Search Less Than/Equal
Conversion
Control
INT
5
0
1
19
DINT
5
0
2
22
BYTE WORD
5 5
0 0
1 1
19 19
Convert to INT
5
0
–
10
Convert to BCD-4
5
0
–
10
Convert to REAL
5
0
–
8
Convert to WORD
5
0
–
11
Truncate to INT
5
0
–
11
Truncate to DINT
5
0
–
11
Call a Subroutine
15
0
–
7
Do I/O PID – ISA Algorithm
5 14
0 10
– –
13 16
PID – IND Algorithm
14
10
–
16
End Instruction
–
–
–
–
Service Request #6
5
0
–
10
#7 (Read)
10
0
–
10
#7 (Set) #14
5 15
0 0
– –
10 10
#15
5
0
–
10
#16
10
0
–
10
#18
255
0
–
10
#23
25
0
–
10
#26//30** #29
155 5
0 0
– –
10 10
Nested MCR/ENDMCR Combined
1
0
–
4
Sequential Event
60
0
=
199
0
=
Recorder (SER) 8 Channels Sequential Event Recorder (SER) 16 Channels **Service request #26/30 was measured using a high speed counter, 16-point output, in a 5-slot rack. Notes: 1. For table functions, increment is in units of length specified.; for bit operation functions, microseconds/bit.; for data move functions, microseconds/number of bits or words. 2 Enabled time for single length units of type %R, %AI, and %AQ. 3. COMMREQ time has been measured between CPU and HSC. 4. DOIO is the time to output values to discrete output module. 5. Where there is more than one possible case, the time indicated above represents the worst possible case. 6. For instructions that have an increment value, multiply the increment by (Length –1) and add that value to the base time.
A-14
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 298
A
CPU Boolean Execution Times This table lists execution times of coils and contacts for the Series 90-30 CPU modules. Table A-5. Boolean Execution Times CPU Model
Execution Time per 1,000 Boolean Contacts/Coils
Models 37x
0.15 milliseconds
Models 35x and 36x
0.22 milliseconds
Models 340/341
0.3 milliseconds
Model 331
0.4 milliseconds
Models 313/323
0.6 milliseconds
Model 311
18.0 milliseconds
Instruction Sizes for CPUs 350 - 374 Memory Size in the following table refers to the number of bytes of user memory required by a given instruction in a ladder diagram application program. Table A-6. Instruction Sizes for CPUs 350 – 374
GFK-0467M
Function
Memory Size
Pop stack and AND to top
1
Pop stack and OR to top
1
Duplicate top of stack
1
Pop stack
1
Initial stack
1
Label
5
Jump
5
All other instructions
3
Function blocks – see Table A-2 various
Appendix A Instruction Timing
A-15
Page 299
A
A-16
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M