Appendix Interpreting Fault Tables

B The Series 90-30, Series 90-20, and Series 90 Micro PLCs maintain two fault tables, the I/O fault table for faults generated by I/O devices (including I/O controllers) and the PLC fault table for internal PLC faults. The information in this appendix will enable you to interpret the message structure format when reading these fault tables. Both tables contain similar information. The fault data in these tables only exists in the PLC, not in the folder. Therefore, if using Logicmaster, you must be connected in either the ONLINE or MONITOR mode to view faults. •

•

The PLC fault table contains: †

Fault location.

†

Fault description.

†

Date and time of fault.

The I/O fault table contains: †

Fault location.

†

Reference address.

†

Fault category.

†

Fault type.

†

Date and time of fault.

PLC Fault Table Access the PLC fault table through the programming software. For information about accessing fault tables, refer to the online help, Logicmaster 90 Series 90-30/20/Micro Programming Software User’s Manual, GFK-0466.

GFK-0467M

B-1

Page 301

B Example The following figure shows the example of a System Configuration Mismatch fault that has been zoomed to its fault detail screen.

The following diagram identifies each field in the fault entry for the System Configuration Mismatch fault displayed above: 00 3A0000 000373F2 0B03 0600 000000000000000000000000000000000000000000000000 Spare

Error Code

Task

Long/ Short

Slot Rack

Fault Group

Fault Extra Data

Fault Action

This System Configuration Mismatch fault entry is explained below. (All data is in hexadecimal.)

B-2

Field

Value

Comment

Long/Short

00

00=Short, which indicates only 8 bytes of the Fault Extra Data field are used

Rack

00

Main rack (rack 0)

Slot

03

Slot 3

Task

F2

Fault Group

0B

System Configuration Mismatch fault

Fault Action

03

FATAL fault

Error Code

06

Fault Extra Data

00

No Fault Extra Data reported in the 8 bytes

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 302

B The following paragraphs describe each field in the fault entry. Included are tables describing the range of values each field may have.

Long/Short Indicator This byte indicates whether 8 bytes or all 24 bytes of the Fault Extra Data field are used. Type

Code

Fault Extra Data

Short

00

8 bytes

Long

01

24 bytes

Spare These six bytes are pad bytes, used to make the PLC fault table entry exactly the same length as the I/O fault table entry.

Rack The rack number ranges from 0 to 7. Zero is the main rack, containing the PLC. Racks 1 through 7 are expansion racks, connected to the PLC through an expansion cable.

Slot The slot number ranges from 0 to 9. The PLC CPU always occupies slot 1 in the main rack (rack 0).

Task The task number ranges from 0 to +65,535. Sometimes the task number gives additional information for PLC engineers; typically, the task can be ignored.

GFK-0467M

Appendix B Interpreting Fault Tables

B-3

Page 303

B

PLC Fault Group Fault group is the highest classification of a fault. It identifies the general category of the fault. The fault description text displayed by Logicmaster 90-30/20/Micro software is based on the fault group and the error codes. Table B-1 lists the possible fault groups in the PLC fault table. The last non-maskable fault group, Additional PLC Fault Codes, is declared for the handling of new fault conditions in the system without the PLC having to specifically know the alarm codes. All unrecognized PLC-type alarm codes belong to this group. Table B-1. PLC Fault Groups Group Number

B-4

Decimal

Hexadecimal

Group Name

Fault Action

1 4 5 8 11 12 13 14 16 17 18 19 20 21 22 –

1 4 5 8 B C D E 10 11 12 13 14 15 16 –

Loss of, or missing, rack Loss of, or missing, option module Addition of, or extra, rack Addition of, or extra, option module System configuration mismatch System bus error PLC CPU hardware failure Non-fatal module hardware failure Option module software failure Program block checksum failure Low battery signal Constant sweep time exceeded PLC system fault table full I/O fault table full User Application fault Additional PLC fault codes

Fatal Diagnostic Diagnostic Diagnostic Fatal Diagnostic Fatal Diagnostic Diagnostic Fatal Diagnostic Diagnostic Diagnostic Diagnostic Diagnostic As specified

128 129 130

80 81 82

System bus failure No user’s program on power-up Corrupted user RAM detected

Fatal Informational Fatal

132 135 137

84 87 89

Password access failure PLC CPU software failure PLC sequence-store failure

Informational Fatal Fatal

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 304

B

Fault Action Each fault may have one of three actions associated with it. These fault actions are fixed on the Series 90-30 PLC and cannot be changed by the user. Table B-2. PLC Fault Actions Fault Action

Action Taken by CPU

Informational Diagnostic

Code

Log fault in fault table Log fault in fault table Set fault references Log fault in fault table Set fault references Go to STOP mode

Fatal

1 2 3

Error Code The error code further describes the fault. Each fault group has its own set of error codes. Table B3 shows error codes for the PLC Software Error Group (Group 87H). Table B-3. Alarm Error Codes for PLC CPU Software Faults Decimal

Hexadecimal

20

14

Corrupted PLC Program Memory

39

27

Corrupted PLC Program Memory

82

52

Backplane Communications Failed

90

5A

User Shut Down Requested

All others

Name

PLC CPU Internal System Error

Table B-4 shows the error codes for all the other fault groups.

GFK-0467M

Appendix B Interpreting Fault Tables

B-5

Page 305

B

Table B-4. Alarm Error Codes for PLC Faults Decimal

Hexadecimal

Name

PLC Error Codes for Loss of Option Module Group (4) 44 45 255 79

2C 2D FF 4F

Option Module Soft Reset Failed Option Module Soft Reset Failed Option Module Communication Failed Loss of Daughterboard

Error Codes for Reset of, Addition of, or Extra Option Module Group (8) 2 04 05

1 2 3 5 11 13 401 8 10 23 58

2 Module Restart Complete 4 Addition of Daughterboard 5 Reset of Daughterboard All others Reset of, Addition of, or Extra Option Module Error Codes for Option Module Software Failure Group (10 hex) 1 2

Unsupported Board Type COMREQ – mailbox full on outgoing message that starts the COMREQ 3 COMREQ – mailbox full on response 5 Backplane Communications with PLC; Lost Request B Resource (alloc, tbl ovrflw, etc.) error D User program error 191 Module Software Corrupted; Requesting Reload Error Codes for System Configuration Mismatch Group (B hex) 8 Analog Expansion Mismatch A Unsupported Feature 17 Program exceeds memory limits 3A Mismatch of Daughterboard Error Codes for System Bus Error Group (C hex) All others

System Bus Error

3

Error Codes for Program Block Checksum Group (11 hex) 3 Program or program block checksum failure

0 1

0 1

2 5 6 7

Error Codes for User Application Fault Group (16 hex) 2 PLC Watchdog Timer Timed Out 5 COMREQ – WAIT mode not available for this command 6 COMREQ – Bad Task ID 7 Application Stack Overflow

1

1

1 2 3 4

Error Codes for Low Battery Signal Failed battery on PLC CPU or other module Low battery on PLC CPU or other module

Error Codes for System Bus Failure Group (80 hex) Operating system

Error Codes for Corrupted User RAM on Powerup Group (82 hex) 1 Corrupted User RAM on Power-up 2 Illegal Boolean Opcode Detected 3 PLC_ISCP_PC_OVERFLOW 4 PRG_SYNTAX_ERR Error Codes for PLC CPU Hardware Faults (D hex) All codes

B-6

PLC CPU Hardware Failure

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 306

B Fault Extra Data This field contains details of the fault entry. The following example shows what data may be present: Example - Corrupted User RAM Group Four of the error codes in the System Configuration Mismatch group supply fault extra data: Table B-5. PLC Fault Data – Illegal Boolean Opcode Detected Fault Extra Data

Model Number Mismatch

[0]

ISCP Fault Register Contents

[1]

Bad OPCODE

[2,3]

ISCP Program Counter

[4,5]

Function Number

For a RAM failure in the PLC CPU (one of the faults reported as a PLC CPU hardware failure), the address of the failure is stored in the first four bytes of the field.

PLC Fault Time Stamp PLC CPU Hardware Failure (RAM Failure) The six-byte time stamp is the value of the system clock when the fault was recorded by the PLC CPU. (Values are coded in BCD format.) Table B-6. PLC Fault Time Stamp Byte Number 1 2 3 4 5 6

GFK-0467M

Appendix B Interpreting Fault Tables

Description Seconds Minutes Hours Day of the month Month Year

B-7

Page 307

B

I/O Fault Table The following figure shows the example of a Loss of I/O Module fault that has been zoomed to its fault detail screen.

The following diagram identifies the hexadecimal information displayed in each field in the example fault entry (System Configuration Mismatch) shown in the figure above. Reference Address Block Fault Fault Fault Action Type Specific Data

Slot

02 461100 00047F7FFF7F 0302 0E 00 00 0700000000000000000000000000000000000000000000

Rack

B-8

Fault Group

I/O Bus

Long/ Short

Point

Fault Description

Fault Category

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 308

B The following paragraphs describe each field in the I/O fault table. Included are tables describing the range of values each field may have.

Long/Short Indicator This byte indicates whether the particular fault uses 5 bytes or ass 21 bytes of the Fault Specific Data field. Table B-7. I/O Fault Table Format Indicator Byte Type

Code

Fault Specific Data

Short

02

5 bytes

Long

03

21 bytes

Reference Address Reference address is a three-byte address containing the I/O memory type and location (or offset) in that memory which corresponds to the point experiencing the fault. Or, when a Genius block fault or integral analog module fault occurs, the reference address refers to the first point on the block where the fault occurred. Table B-8. I/O Reference Address Byte

Description

Range

0

Memory Type

0 – FF

1–2

Offset

0 – 7FF

The memory type byte is one of the following values. Table B-9. I/O Reference Address Memory Type Name

Value (Hexadecimal)

Analog input

0A

Analog output

0C

Analog grouped

0D

Discrete input

10 or 46

Discrete output

12 or 48

Discrete grouped

1F

I/O Fault Address The I/O fault address is a six-byte address containing rack, slot, bus, block, and point address of the I/O point that generated the fault. The point address is a word; all other addresses are one byte each. All five values may not be present in a fault. When an I/O fault address does not contain all five addresses, a 7F hex appears in the address to indicate where the significance stops. For example, if 7F appears in the bus byte, the fault is a module fault. Only rack and slot values are significant.

GFK-0467M

Appendix B Interpreting Fault Tables

B-9

Page 309

B Rack The rack number ranges from 0 to 7. Zero is the main rack, i.e., the one containing the CPU. Racks 1 through 7 are expansion racks.

Slot The slot number ranges from 0 to 9. The PLC CPU always occupies slot 1 in the main rack (rack 0).

Point Point ranges from 1 to 1024 (decimal). It tells which point on the block has the fault when the fault is a point-type fault.

I/O Fault Group Fault group is the highest classification of a fault. It identifies the general category of the fault. The fault description text displayed by Logicmaster 90-30/20/Micro software is based on the fault group and the error codes. Table B-10 lists the possible fault groups in the I/O fault table. Group numbers less than 80 (Hex) are maskable faults. The last non-maskable fault group, Additional I/O Fault Codes, is declared for the handling of new fault conditions in the system without the PLC having to specifically know the alarm codes. All unrecognized I/O-type alarm codes belong to this group. Table B-10. I/O Fault Groups Group Number

B-10

Group Name

Fault Action

3

Loss of, or missing, I/O module

Diagnostic

7

Addition of, or extra, I/O module

Diagnostic

9

IOC or I/O bus fault

Diagnostic

A

I/O module fault

Diagnostic

–

Additional I/O fault codes

As specified

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 310

B I/O Fault Action The fault action specifies what action the PLC CPU should take when a fault occurs. Table B-11 lists possible fault actions. Table B-11. I/O Fault Actions Fault Action

Action Taken by CPU

Code

Informational

Log fault in fault table

1

Diagnostic

Log fault in fault table Set fault references

2

Fatal

Log fault in fault table Set fault references Go to STOP mode

3

I/O Fault Specific Data An I/O fault table entry may contain up to 5 bytes of I/O fault specific data.

Symbolic Fault Specific Data Table B-12 lists data that is required for block circuit configuration. Table B-12. I/O Fault Specific Data Decimal Number

Hex Code

Description

Circuit Configuration 1 2 3

Circuit is an input – tristate Circuit is an input Circuit is an output

Fault Actions for Specific Faults Forced/unforced circuit faults are reported as informational faults. All others are diagnostic or fatal. The model number mismatch, I/O type mismatch and non-existent I/O module faults are reported in the PLC fault table under the System Configuration Mismatch group. They are not reported in the I/O fault table.

GFK-0467M

Appendix B Interpreting Fault Tables

B-11

Page 311

B

I/O Fault Time Stamp The six-byte time stamp is the value of the system clock when the fault was recorded by the PLC CPU. Values are coded in BCD format. Table B-13. I/O Fault Time Stamp

B-12

Byte Number

Description

1 2 3 4 5 6

Seconds Minutes Hours Day of the month Month Year

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002