Manual · GE Fanuc
Series 90-30/20/Micro PLC CPU Instruction Set Reference Manual
Manual337 pagesPDF 4.4 MB
Instruction set reference for GE Fanuc Series 90-30, 90-20 and Micro PLC CPUs: system operation, faults and programming instructions.
What this file really is
The old site listed this file as a manual for the GE Fanuc IC692CPU211D / IC692MDR541C, IC693ACC200C and 26 more models. The file is named as a user manual for the IC693CHS398 baseplate, but it is the Series 90-30/20/Micro PLC CPU instruction set reference and does not mention that part number.
Names · 4 models
The models it names
Filed with · 24 models
Also filed with these models on the old site
Summary
What is in it
GE Fanuc reference manual for the CPU instruction set of the Series 90-30, Series 90-20 and Series 90 Micro programmable logic controllers. It explains the PLC sweep, program organization, data types, power-up and power-down, clocks, passwords and the I/O system, then how to read and correct PLC and I/O faults, and describes each Logicmaster 90 instruction: relays, timers and counters, math, relational, bit, data move, table, conversion and control functions.
Its parts
- Introduction
- System Operation
- Fault Explanation and Correction
- Relay Functions
- Timers and Counters
- Math Functions
- Relational Functions
- Bit Operation Functions
- Data Move Functions
- Table Functions
- Conversion Functions
- Control Functions
From the manual
Key facts from this manual
Each line names its page in the PDF.
This is the GE Fanuc Series 90-30/20/Micro PLC CPU Instruction Set Reference Manual (GFK-0467M, May 2002). It explains how Series 90-30, Series 90-20 and Series 90 Micro PLCs run their programs, how to read and correct faults in the PLC and I/O fault tables, and the Logicmaster 90 ladder instructions. It covers the CPUs (models such as CPU311, CPU331, CPU364, CPU374 and the Series 90-20 CPU211) and lists Series 90-30 I/O modules by catalog number, pointing to GFK-0898 for their specifications and wiring.
- What it is
- Reference for system operation, fault handling and Logicmaster 90 instructions of Series 90-30, 90-20 and Micro PLCs p. 3
- Manual number
- GFK-0467M, May 2002 p. 1
- Processors
- 80188 in Series 90-30 CPUs 341 and lower and the Series 90-20; 80386EX in 35x and 36x; 586 in 37x; H8 in the Micro p. 18
- User memory
- CPU311 6 KB; CPU313 and CPU323 12 KB; CPU331 16 KB; CPU340 32 KB; CPU341 80 KB; Series 90-20 Model 211 programs up to 2 KB p. 36
- I/O capacity
- CPU311 and CPU313 (5-slot): 5 modules; CPU323 (10-slot): 10 modules; CPU331 to CPU341: 49 modules in 5 racks; CPU350 to CPU374: 79 modules in 8 racks p. 59
- Series 90-20 bases
- IC692MAA541 (120 VAC in and out), IC692MDR541 (24 VDC in, relay out, 120 VAC supply) and IC692MDR741 (240 VAC supply), each 16 in/12 out, with CPU module IC692CPU211 p. 64
- Modules listed
- Series 90-30 discrete, analog and option modules by catalog number, including IC693MDL240, IC693MDL645, IC693MDL732, IC693MDL741, IC693MDL940 and the IC693ACC300 input simulator p. 60, 61, 62
- Output defaults
- Discrete outputs are off at power-up until the first output scan p. 62
- Analog output default
- A jumper on the removable terminal block sets default to zero or hold last state p. 62
- Genius global data
- IC693BEM331 (version 5 and later) and IC693CMM302 send up to 128 bytes and receive up to 128 bytes from each of up to 30 other controllers p. 63
- Ethernet
- CPU364 (release 9.0 and later): AAUI or 10BaseT, one at a time; CPU374: two 10BaseT/100BaseTx ports p. 63
- Floating point
- 35x and 36x CPUs release 9 or later, and all CPU352 and CPU374 p. 18
- Error code
- First two hex digits of the fifth group in the fault detail p. 71
What this manual walks you through
- How the Series 90-30 I/O system is organized and how many modules each CPU supports p. 59
- Looking up Series 90-30 and 90-20 modules by catalog number and the manual for each p. 60, 61, 62, 64
- Sharing data between PLCs with Genius global data and Ethernet Global Data p. 63
- Reading the PLC fault table and the I/O fault table p. 65, 66
- Finding the hexadecimal fault code on the fault detail screen p. 70
- What fatal, diagnostic and informational faults do to the PLC p. 72
- Correcting corrupted memory, option module, configuration mismatch, checksum and low battery faults p. 71, 72, 73, 74
- Ladder logic instructions for the Series 90-30 and 90-20 (chapters 4 to 12) p. 64
Good to know
- The manual is written for Logicmaster (DOS) users; Windows-based software shows the instructions differently and has its own online help. p. 19
- CPU311, CPU313 and CPU323 do not support expansion or remote racks. p. 59
- A PCM or PCM-type module in a CPU 311, 313 or 323 system, or in an expansion or remote rack, causes an Unsupported Hardware fault (error code 18). p. 73
- Ethernet Global Data on the CPU364 and CPU374 needs a Windows-based programmer, not Logicmaster 90. p. 63
- For a failed or low battery fault, the manual says to replace the battery without removing power from the rack. p. 74
Questions this manual answers
How much user memory does a Series 90-30 CPU311 have?
6 Kbytes. The CPU313 and CPU323 have 12, the CPU331 16 and the CPU340 32. p. 36
How many I/O modules can a CPU311 or CPU313 run?
Up to 5 Series 90-30 I/O modules on its 5-slot baseplate, with no expansion or remote racks; the 10-slot CPU323 runs up to 10. p. 59
What does a Low Battery Signal fault mean on a Series 90-30?
Error code 0 means the battery on the CPU or another module is dead and error code 1 means it is low; the fix is to replace the battery with the rack still powered. p. 74
Which Series 90-30 CPUs have Ethernet?
The CPU364 (release 9.0 and later), through either its AAUI or 10BaseT port, and the CPU374, through two 10BaseT/100BaseTx ports. p. 63
What do Series 90-30 discrete outputs do at power-up?
They default to off and stay off until the PLC's first output scan. p. 62
Contents
Chapters and sections
Each line opens the PDF at its page.
- Front1
- Chapter 1 - Introduction18
- Chapter 2 - System Operation20
- Chapter 3 - Fault Explanation and Correction65
- Chapter 4 - Relay Functions82
- Using Contacts82
- Using Coils83
- Normally Open Contact, | |84
- Normally Closed Contact, |/|84
- Coil, ( )84
- Negated Coil, (/)85
- Retentive Coil, (M)85
- Negated Retentive Coil, (/M)85
- Positive Transition Coil, (()85
- Negative Transition Coil, (()86
- SET Coil, (S) 86
- RESET Coil, (R)86
- Retentive SET Coil, (SM)87
- Retentive RESET Coil, (RM)87
- Links88
- Continuation Coils ( - - - <+>) and Contacts (<+> - - - )89
- Chapter 5 - Timers and Counter90
- Chapter 6 - Math Functions106
64 more lines, from page 114 on
- SQRT (INT, DINT, REAL)114
- Chapter 7 - Relational Functions122
- Chapter 8 - Bit Operation Functions128
- Chapter 9 - Data Move Functions150
- Chapter 10 - Table Functions167
- Chapter 11 - Conversion Functions177
- Chapter 12 - Control Functions189
- Appendix A - Instruction Timing284
- Appendix B - Intrepreting Fault Tables300
- Appendix C - Instruction Mnemonics312
- Appendix D - Key Functions315
- Appendix E - Using Floating-Point Numbers319
- Appendix F - Programming Software Comparison327
- Index329
The whole text · 39 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Front, pages 1 to 91-9
- Front, pages 10 to 1710-17
- Pages 18 to 2718-27
- Pages 28 to 3728-37
- Pages 38 to 4738-47
- Pages 48 to 5748-57
- Pages 58 to 6458-64
- Chapter 3 - Fault Explanation and Correction, pages 65 to 7365-73
- Chapter 3 - Fault Explanation and Correction, pages 74 to 8174-81
- Chapter 4 - Relay Functions82-89
- Chapter 5 - Timers and Counter, pages 90 to 9790-97
- Chapter 5 - Timers and Counter, pages 98 to 10598-105
- Chapter 6 - Math Functions, pages 106 to 113106-113
- Chapter 6 - Math Functions, pages 114 to 121114-121
- Chapter 7 - Relational Functions122-127
- Chapter 8 - Bit Operation Functions, pages 128 to 135128-135
- Chapter 8 - Bit Operation Functions, pages 136 to 143136-143
- Chapter 8 - Bit Operation Functions, pages 144 to 149144-149
- Chapter 9 - Data Move Functions, pages 150 to 158150-158
- Chapter 9 - Data Move Functions, pages 159 to 166159-166
- Chapter 10 - Table Functions167-176
- Chapter 11 - Conversion Functions177-188
- Chapter 12 - Control Functions, pages 189 to 198189-198
- Chapter 12 - Control Functions, pages 199 to 208199-208
- Chapter 12 - Control Functions, pages 209 to 218209-218
- Chapter 12 - Control Functions, pages 219 to 228219-228
- Chapter 12 - Control Functions, pages 229 to 238229-238
- Chapter 12 - Control Functions, pages 239 to 248239-248
- Chapter 12 - Control Functions, pages 249 to 258249-258
- Chapter 12 - Control Functions, pages 259 to 268259-268
- Chapter 12 - Control Functions, pages 269 to 278269-278
- Chapter 12 - Control Functions, pages 279 to 283279-283
- Appendix A - Instruction Timing, pages 284 to 291284-291
- Appendix A - Instruction Timing, pages 292 to 299292-299
- Appendix B - Intrepreting Fault Tables300-311
- Appendix C - Instruction Mnemonics312-314
- Appendix D - Key Functions315-318
- Appendix E - Using Floating-Point Numbers319-326
- Pages 327 to 337327-337
The file