Series 90-30/20/Micro PLC CPU Instruction Set Reference Manual: Chapter 3 - Fault Explanation and Correction, pages 65 to 73

Pages 65 to 73 of 337, from Series 90-30/20/Micro PLC CPU Instruction Set Reference Manual

The original document is the PDF (4.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the GE Fanuc IC692CPU211D / IC692MDR541C, Fanuc IC692CPU211D / IC692MDR541C, GE IC692CPU211D / IC692MDR541C and GE Fanuc IC693CPU311X

Page 65

Chapter

Fault Explanation and Correction

3 This chapter is an aid to troubleshooting the Series 90-30, 90-20, and Micro PLC systems. It explains the fault descriptions, which appear in the PLC fault table, and the fault categories, which appear in the I/O fault table. Each fault explanation in this chapter lists the fault description for the PLC fault table or the fault category for the I/O fault table. Find the fault description or fault category corresponding to the entry on the applicable fault table displayed on your programmer screen. Beneath it is a description of the cause of the fault along with instructions to correct the fault. Chapter 3 contains the following sections:

GFK-0467M

Section

Title

Description

Page

1

Fault Handling

Describes the type of faults that may occur in the Series 90-30 and how they are displayed in the fault tables. Descriptions of the PLC and I/O fault table displays are also included.

3-2

2

PLC Fault Table Explanations

Provides a fault description of each PLC fault and instructions to correct the fault.

3-7

3

I/O Fault Table Explanations

Describes the Loss of I/O Module and Addition of I/O Module fault categories.

3-16

3-1

Page 66

3

Section 1: Fault Handling Note This information on fault handling applies to systems programmed using Logicmaster 90-30/20/Micro software. Faults occur in the Series 90-30, 90-20, or Series 90 Micro PLC system when certain failures or conditions happen that affect the operation and performance of the system. These conditions, such as the loss of an I/O module or rack, may affect the ability of the PLC to control a machine or process. Or, a reported condition may only act as an alert, such as a low battery signal, which indicates that the memory backup battery needs to be changed. However, some conditions reported in the fault tables are not reports of failures. For example, if you were to add a new module to the PLC, this would be listed in the I/O fault table as “Addition of I/O Module.”

Alarm Processor A fault is the condition or failure itself. When a fault is received and processed by the CPU, it is called an alarm. The firmware in the CPU that handles these conditions is called the Alarm Processor. The user interface for the Alarm Processor is through the programming software. Any detected fault is recorded in a fault table and displayed on either the PLC fault table screen or the I/O fault table screen, as applicable.

Classes of Faults The Series 90-30, 90-20, and Micro PLCs detect several classes of faults. These include internal failures, external failures, and operational failures. Fault Class

Examples

Internal Failures

Non-responding modules. Low battery condition. Memory checksum errors.

External I/O Failures

Loss of rack or module. Addition of rack or module.

Operational Failures

Communication failures. Configuration failures. Password access failures.

Note For information specific to Micro PLC fault handling, refer to the Series 90 Micro PLC User’s Manual (GFK-1065).

3-2

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 67

3

System Reaction to Faults Hardware failures require that either the system be shut down or the failure be tolerated. I/O failures may be tolerated by the PLC system, but they may be intolerable by the application or the process being controlled. Operational failures are normally tolerated. Series 90-30, 90-20, and Micro PLC faults have two attributes: Attribute

Description

Fault Table Affected

I/O Fault Table PLC Fault Table

Fault Action

Fatal Diagnostic Informational

Fault Tables Two fault tables are maintained in the PLC for logging faults, the I/O fault table for logging faults related to the I/O system and the PLC fault table for logging all other faults. The following table lists the fault groups, their fault actions, the fault tables affected, and the “name” for system discrete %S points that are affected. Table 3-1. Fault Summary

Fault Group

Fault Table

Special Discrete Fault References

Loss of or Missing I/O Module

Diagnostic

I/O io_flt any_flt io_pres

Loss of or Missing Option Module

Diagnostic

PLC sy_flt any_flt sy_pres los_sio

System Configuration Mismatch

Fatal

PLC sy_flt any_flt sy_pres cfg_mm

PLC CPU Hardware Failure

Fatal

PLC sy_flt any_flt sy_pres hrd_cpu

Program Checksum Failure

Fatal

PLC sy_flt any_flt sy_pres pb_sum

Low Battery

Diagnostic

PLC sy_flt any_flt sy_pres low_bat

PLC Fault Table Full

Diagnostic, sy_full los_iom

I/O Fault Table Full

Diagnostic, io_full

Application Fault

Diagnostic

PLC sy_flt any_flt sy_pres apl_flt

No User Program

Informational

PLC sy_flt any_flt sy_pres no_prog

Corrupted User RAM

Fatal

PLC sy_flt any_flt sy_pres bad_ram

Password Access Failure

Diagnostic

PLC sy_flt any_flt sy_pres bad_pwd

PLC Software Failure

Fatal

PLC sy_flt any_flt sy_pres sft_cpu

PLC Store Failure

Fatal

PLC sy_flt any_flt sy_pres stor_er

Diagnostic

PLC sy_flt any_flt sy_pres ov_swp

Unknown PLC Fault

Fatal

PLC sy_flt any_flt sy_pres

Unknown I/O Fault

Fatal

I/O io_flt any_flt io_pres

Constant Sweep Time Exceeded

GFK-0467M

Fault Action

Chapter 3 Fault Explanation and Correction

3-3

Page 68

3 Fault Action Faults can be fatal, diagnostic or informational. Fatal faults cause the fault to be recorded in the appropriate table, any diagnostic variables to be set, and the system to be halted. Diagnostic faults are recorded in the appropriate table, and any diagnostic variables are set. Informational faults are only recorded in the appropriate table. Possible fault actions are listed in the following table. Table 3-2. Fault Actions Fault Action

Response by CPU

Fatal

Log fault in fault table. Set fault references. Go to STOP mode.

Diagnostic

Log fault in fault table. Set fault references.

Informational

Log fault in fault table.

When a fault is detected, the CPU uses the fault action for that fault. Fault actions are not configurable in the Series 90-30 PLC, Series 90-20, or the Series 90 Micro PLC.

Fault References System fault references in the Series 90-30 are of one type - fault summary references. Fault summary references are set to indicate what fault occurred. The fault reference remains on until the PLC is cleared or until cleared by the application program. An example of a system fault bit being set and then cleared is shown in the following figure. In this example, the coil, Light_01, is turned on when system contact OV_SWP (%SA0002) closes, which indicates that an oversweep occurred. The OV_SWP contact and Light_01 coil are turned off if contact %I0359 is closed, because closing %I0359 turns on reset coil OV_SWP.

| ov_swp Light_01 | - - ] [ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ( ) - | |%I0359 ov_swp | - - ] [ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - (R) - |

System Status References The alarm processor maintains the states of the 128 system status bits in %S memory. Many of these status references indicate where a fault has occurred and what type of fault it is. Status references are assigned to %S, %SA, %SB, and %SC memory, and each reference has a nickname. For example, status bit %SA0009 has a nickname of CFG_MM, and it goes high to indicate a

3-4

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 69

3 configuration mismatch. These references are available for use in the application program as required. Refer to Chapter 2, “System Operation,” for a list of the system status references.

Additional Fault Effects Two faults described later in this chapter have additional effects associated with them. These effects are discussed in the following table. Fault PLC CPU Software Failure

Effect Description When a PLC CPU software failure is logged, the Series 90-30 or 90-20

CPU immediately transitions into a special ERROR SWEEP mode. No activity is permitted in this mode. The only method of clearing this condition is to reset the PLC by cycling power. PLC Sequence Store Failure

If, while performing a store to the PLC, communication between the PLC and the programmer is interrupted or any other failure occurs which terminates the download (store), the PLC Sequence Store Failure fault is logged. As long as this fault is present in the system, the PLC will not transition to RUN mode. To resume operation, the error must be cleared. This can be accomplished by clearing the fault on the applicable Fault Table Screen of the programming software.

PLC Fault Table Display The PLC Fault Table screen displays PLC faults such as password violations, PLC/configuration mismatches, parity errors, and communications errors. Faults are stored in the PLC, so if the programming software is in the OFFLINE mode, no faults are displayed in this fault table. If the programming software is in either the ONLINE or MONITOR mode, PLC fault data is displayed. In ONLINE mode, faults can be cleared, although this feature may be password protected. Once cleared, faults that are still present are not logged again in the table (except for the “Low Battery” fault) unless power is cycled or a new configuration is stored.

I/O Fault Table Display The I/O Fault Table screen displays I/O faults such as circuit faults, address conflicts, forced circuits, and I/O bus faults. Faults are stored in the PLC, so if the programming software is in the OFFLINE mode, no faults are displayed in this fault table. If the programming software is in either the ONLINE or MONITOR mode, I/O fault data is displayed. In ONLINE mode, faults can be cleared, although this feature may be password protected. Once cleared, faults that are still present are not logged again in the table unless power is cycled or a new configuration is stored.

GFK-0467M

Chapter 3 Fault Explanation and Correction

3-5

Page 70

3

Accessing Additional Fault Information The fault tables contain basic information regarding the fault. Additional information pertaining to each fault can be displayed through the programming software. In addition, the programming software provides a hexadecimal fault code for each fault. The last item, “Correction”, in each fault explanation in this chapter lists the action(s) to be taken to correct the fault. Note that the corrective action for some of the faults includes the statement: Display the PLC Fault Table on the Programmer. Contact GE Fanuc Field Service, giving them all the information contained in the fault entry.

This second statement means that you must tell Field Service both the information readable directly from the fault table and the hexadecimal fault code. Field Service personnel will then give you further instructions for the appropriate action to be taken. The following figure of a Logicmaster fault detail screen shows the additional fault information and hexadecimal fault code discussed above. (The fault code is the first two hexadecimal digits in the fifth group of number from the left.) To reach this screen, select a Fault Table fault (Loss of I/O Module) by using the keyboard cursor control arrow keys, and then “zoom” using the F10 key. To return to the Fault Table screen, press either the Escape key or the Shift and F10 key combination. Hexadecimal Fault Code

3-6

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 71

3

Section 2: PLC Fault Table Explanations Each fault explanation contains a fault description and instructions to correct the fault. Many fault descriptions have multiple causes. In these cases, the error code, displayed with the additional fault information, is used to distinguish different fault conditions sharing the same fault description. The error code is the first two hexadecimal digits in the fifth group (from the left) of numbers, as shown in the following example. 01

000000

01030100

0902

0200 000000000000 | |_____ Error Code (first two hex digits in fifth group)

Some faults can occur because random access memory on the PLC CPU board has failed. These same faults may also occur because the system has been powered off and the battery voltage is (or was) too low to maintain memory. To avoid excessive duplication of instructions when corrupted memory may be a cause of the error, the correction simply states: Perform the corrections for Corrupted Memory.

This means: 1.

If the system has been powered off, replace the battery. Battery voltage may be insufficient to maintain memory contents.

2.

Replace the PLC CPU board. The integrated circuits on the PLC CPU board may be failing.

The following table enables you to quickly find a particular PLC fault explanation in this section. Each entry is listed as it appears on the programmer screen. Fault Description Loss of, or Missing, Option Module Reset of, Addition of, or Extra, Option Module System Configuration Mismatch Option Module Software Failure Program Block Checksum Failure Low Battery Signal Constant Sweep Time Exceeded Application Fault No User Program Present Corrupted User Program on Power-Up Password Access Failure PLC CPU System Software Failure Communications Failure During Store

GFK-0467M

Chapter 3 Fault Explanation and Correction

Page 3-8 3-8 3-9 3-10 3-10 3-10 3-11 3-11 3-12 3-12 3-12 3-13 3-15

3-7

Page 72

3

Fault Actions • • •

Fatal faults cause the PLC to enter a form of STOP mode at the end of the sweep in which the error occurred. Diagnostic faults are logged and corresponding fault contacts are set; the PLC stays in RUN mode. Informational faults are simply logged in the PLC fault table; the PLC stays in RUN mode.

Loss of, or Missing, Option Module The Fault Group Loss of, or Missing Option Module occurs when an option module fails to respond. The failure may occur at power-up if the module is missing or during operation if the module fails to respond. The fault action for this group is Diagnostic. Error Code:

1, 42

Name:

Option Module Soft Reset Failed

Description:

PLC CPU unable to re-establish communications with option module after soft reset (such as pressing a Reset button) is tried.

Correction:

(1)

Repeat soft reset procedure recommended for this module.

(2)

Replace the option module.

(3)

Power off the system. Verify that the module is seated properly in the rack and that all cables are properly connected and seated.

(4)

Test or replace the cables.

Error Code:

All Others

Name:

Module Failure During Configuration

Description:

The PLC operating software generates this error when a module fails during power-up or configuration store.

Correction:

(1)

Power off the system. Replace the module located in that rack and slot.

Reset of, Addition of, or Extra, Option Module The Fault Group Reset of, Addition of, or Extra Option Module occurs when an option module (PCM, ADC, etc.) comes online, is reset, or a module is found in the rack, but none is specified in the configuration. The fault action for this group is Diagnostic. Correction:

3-8

(1)

Update the configuration file to include the module.

(2)

Remove the module from the system.

Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002

GFK-0467M

Page 73

3

System Configuration Mismatch The Fault Group Configuration Mismatch occurs when the module occupying a slot is different from that specified in the configuration file. The fault action is Fatal.

GFK-0467M

Error Code:

1

Name:

System Configuration Mismatch

Description:

The PLC operating software generates this fault when the module occupying a slot is not of the same type that the configuration file indicates should be in that slot, or when the configured rack type does not match the actual rack present.

Correction:

Identify the mismatch and reconfigure the module or rack.

Error Code:

6

Name:

System Configuration Mismatch

Description:

This is the same as error code 1 in that this fault occurs when the module occupying a slot is not of the same type that the configuration file indicates should be in that slot, or when the configured rack type does not match the actual rack present.

Correction:

Identify the mismatch and reconfigure the module or rack.

Error Code:

18

Name:

Unsupported Hardware

Description:

A PCM or PCM-type module is present in a CPU 311, 313, or 323 system, or in an expansion or remote rack.

Correction:

Physically correct the situation by removing the PCM or PCM-type module or install a CPU that does support the module. NOTE: These modules must reside only in a CPU rack and only with a CPU that supports them.

Error Code:

26

Name:

Module busy–config not yet accept by module

Description:

The module cannot accept new configuration at this time because it is busy with a different process.

Correction:

Allow the module to complete the current operation and re-store the configuration.

Error Code:

51

Name:

END Function Executed from Sequential Function Chart (SFC) Action

Description:

The placement of an END function in SFC logic or in logic called by SFC will produce this fault.

Correction:

Remove the END function from the SFC logic or logic being called by the SFC logic.

Chapter 3 Fault Explanation and Correction