The text of a manual · part 7 of 39
Series 90-30/20/Micro PLC CPU Instruction Set Reference Manual, pages 58 to 64
Pages 58 to 64 of 337
The original document is the PDF (4.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the GE Fanuc IC692CPU211D / IC692MDR541C, Fanuc IC692CPU211D / IC692MDR541C, GE IC692CPU211D / IC692MDR541C and GE Fanuc IC693CPU311X
Page 58
2
Privilege Level Change Requests A programmer requests a privilege level change by supplying the new privilege level and the password for that level. A privilege level change is denied if the password sent by the programmer does not agree with the password stored in the PLC’s password access table for the requested level. The current privilege level is maintained and no change will occur. If you attempt to access or modify information in the PLC using the Hand-Held Programmer without the proper privilege level, the Hand-Held Programmer will respond with an error message that the access is denied.
Locking/Unlocking Subroutines Subroutine blocks can be locked and unlocked using the block-locking feature of programming software. Two types of locks are available: Type of Lock
Description
View
Once locked, you cannot zoom into that subroutine.
Edit
Once locked, the information in the subroutine cannot be edited.
A previously view locked or edit locked subroutine may be unlocked in the block declaration editor unless it is permanently view locked or permanently edit locked. A search or search and replace function may be performed on a view locked subroutine. If the target of the search is found in a view locked subroutine, one of the following messages is displayed instead of logic: Found in locked block <block_name>
(Continue/Quit)
or Cannot write to locked block <block_name>
(Continue/Quit)
You may continue or abort the search. Folders that contain locked subroutines may be cleared or deleted. If a folder contains locked subroutines, these blocks remain locked when the programming software Copy, Backup, and Restore folder functions are used.
Permanently Locking a Subroutine In addition to VIEW LOCK and EDIT LOCK, there are two types of permanent locks. If a PERMANENT VIEW LOCK is set, all zooms into a subroutine are denied. If a PERMANENT EDIT LOCK is set, all attempts to edit the block are denied.
Caution The permanent locks differ from the regular VIEW LOCK and EDIT LOCK in that once set, they cannot be removed. Once a PERMANENT EDIT LOCK is set, it can only be changed to a PERMANENT VIEW LOCK. A PERMANENT VIEW LOCK cannot be changed to any other type of lock.
GFK-0467M
Chapter 2 System Operation
2-39
Page 59
2
Section 6: Series 90-30, 90-20, and Micro I/O System The PLC I/O system provides the interface between the Series 90-30 PLC and user-supplied devices and equipment. Series 90-30 I/O modules plug directly into slots in Series 90-30 baseplates. The number of Series I/O modules supported depends upon the CPU model: •
CPU models 350 - 374 support up to 79 I/O modules. These CPUs support up to eight racks, which includes the CPU rack plus a total of seven expansion and/or remote racks. • CPU models 331, 340, and 341, support up to 49 I/O modules. These CPUs support up to five racks, which includes the CPU rack plus a total of four expansion and/or remote racks. • CPU models 311 and 313 (5-slot baseplates) support up to 5 Series 90-30 I/O modules. CPU model 323 (10-slot baseplate) supports up to 10 Series 90-30 I/O modules. These three CPUs do not support expansion or remote racks. The I/O structure for the Series 90-30 PLC is shown in the following figure. PLC I/O System APPLICATION RAM % AI % AQ %R
CACHE MEMORY a43072
%I %T %G %S %Q
I/O SCANNER
I/O CONFIGURATION DATA
%M
16 BITS
1 BIT
SERIES 90-30 BACKPLANE
MODEL 30 DISCRETE INPUT MODULE
MODEL 30 DISCRETE OUTPUT MODULE
MODEL 30 ANALOG I/O MODULE
SERIES 90-30 GENIUS MODULES (GCM and GBC)
GENIUS BUS SERIES FIVE GBC
SERIES SIX GBC
SERIES 90-70 GBC
GLOBAL GENIUS
SERIES FIVE CPU
SERIES SIX CPU
SERIES 90-70 CPU
SERIES 90-30 CPU
Figure 2-7. Series 90-30 I/O Structure
Note The drawing shown above is specific to the 90-30 I/O structure. Intelligent and option modules are not part of the I/O scan; they use the System Communication Window. For information about the 90-20 I/O structure, refer to the Series 90™20 Programmable Controller User’s Manual (GFK-0551). For information about the Micro PLC I/O structure, refer to the Series 90™ Micro PLC User’s Manual (GFK-1065).
2-40
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 60
2
Series 90-30 I/O Modules Series 90-30 I/O modules are available as five types, discrete input, discrete output, analog input, analog output, and option modules. The following table lists the Series 90-30 I/O modules by catalog number, number of I/O points, and a brief description of each module.
Note Contact your local GE Fanuc distributor for availability of the modules listed. Refer to the “Pub Number” column for publications that contain the specifications and wiring information of each Series 90-30 I/O module. Figure 2-8. Series 90-30 I/O Modules
GFK-0467M
Catalog Number
Points
IC693MDL230 IC693MDL231 IC693MDL240 IC693MDL241 IC693MDL630 IC693MDL632 IC693MDL633 IC693MDL634 IC693MDL640 IC693MDL641 IC693MDL643 IC693MDL644 IC693MDL645 IC693MDL646 IC693MDL652 IC693MDL653 IC693MDL654 IC693MDL655 IC693ACC300
8 8 16 16 8 8 8 8 16 16 16 16 16 16 32 32 32 32 8/16
Chapter 2 System Operation
Description Discrete Modules - Input 120 VAC Isolated 240 VAC Isolated 120 VAC 24 VAC/DC Positive/Negative Logic 24 VDC Positive Logic 125 VDC Positive/Negative Logic 24 VDC Negative Logic 24 VDC Positive/Negative Logic 24 VDC Positive Logic 24 VDC Negative Logic 24 VDC Positive Logic, FAST 24 VDC Negative Logic, FAST 24 VDC Positive/Negative Logic 24 VDC Positive/Negative Logic, FAST 24 VDC Position/Negative Logic 24 VDC Positive/Negative Logic, FAST 5/12 VDC (TTL) Positive/Negative Logic 24 VDC Positive/Negative Logic Input Simulator
Pub Number GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898
2-41
Page 61
2
Table 2-8. Series 90-30 I/O Modules - Continued Catalog Number
2-42
Points
Description
Pub Number
IC693MDL310 IC693MDL330 IC693MDL340 IC693MDL390 IC693MDL730 IC693MDL731 IC693MDL732 IC693MDL733 IC693MDL734 IC693MDL740 IC693MDL741 IC693MDL742 IC693MDL750 IC693MDL751 IC693MDL752 IC693MDL753 IC693MDL760 IC693MDL930 IC693MDL931 IC693MDL940
12 8 16 5 8 8 8 8 6 16 16 16
Discrete Modules - Output 120 VAC, 0.5A 120/240 VAC, 2A 120 VAC, 0.5A 120/240 VAC Isolated, 2A 12/24 VDC Positive Logic, 2A 12/24 VDC Negative Logic, 2A 12/24 VDC Positive Logic, 0.5A 12/24 VDC Negative Logic, 0.5A 125 VDC Positive/Negative Logic, 2A 12/24 VDC Positive Logic, 0.5A 12/24 VDC Negative Logic, 0.5A 12/24 VDC Positive Logic, 1A
GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898
32 32 32 32 16 8 8 16
12/24 VDC Negative Logic 12/24 VDC Positive Logic, 0.3A 5/24 VDC (TTL) Negative Logic, 0.5A 12/24 VDC Positive/Negative Logic, 0.5A 11 Pneumatic and five 24VDC Positive Logic, 0.5 A Relay, N.O., 4A Isolated Relay, BC, Isolated Relay, N.O., 2A
GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-1881 GFK-0898 GFK-0898 GFK-0898
IC693MDR390 IC693MAR590
8/8 8/8
Input/Output Modules 24 VDC Input, Relay Output 120 VAC Input, Relay Output
GFK-0898 GFK-0898
IC693ALG220 IC693ALG221 IC693ALG222 IC693ALG223 IC693ALG390 IC693ALG391 IC693ALG392 IC693ALG442
4 ch 4 ch 16 16 2 ch 2 ch 8 ch 4/2
Analog Modules Analog Input, Voltage Analog Input, Current Analog Input, Voltage Analog Input, Current Analog Output, Voltage Analog Output, Current Analog Output, Current/Voltage Analog, Current/Voltage Combination Input/Output
GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898 GFK-0898
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 62
2
Table 2-8. Series 90-30 I/O Modules - Continued Catalog Number Description
Pub Number
Option Modules IC693APU300
High Speed Counter
GFK-0293
IC693APU301 IC693APU301
Motion Mate APM Module, 1-Axis–Follower Mode Motion Mate APM Module, 1-Axis–Standard Mode
GFK-0781 GFK-0840
IC693APU302 IC693APU302 IC693MCS001/002*
Motion Mate APM Module, 2-Axis–Follower Mode Motion Mate APM Module, 2-Axis–Standard Mode Power Mate J Motion Control System (1 and 2 Axis)
GFK-0781 GFK-0840 GFK-1256
IC693DSM302 IC693DSM314
Motion Mate Digital Servo Module Motion Mate Digital Servo Module
GFK-1464 GFK-1742
IC693APU305 IC693CMM321
I/O Processor Module Ethernet Communications Module
GFK-1028 GFK-1541
IC693ADC311
Alphanumeric Display Coprocessor
GFK-0521
IC693BEM331
Genius Bus Controller
GFK-1034
IC693BEM320
I/O Link Interface Module (slave)
GFK-0631
IC693BEM321
I/O Link Interface Module (master)
GFK-0823
IC693CMM311
Communications Coprocessor Module
GFK-0582
IC693CMM301
Genius Communications Module
GFK-0412
IC693CMM302
Enhanced Genius Communications Module
GFK-0695
IC693PBM200
Profibus Master Module
GFK-2121
IC693PBS201
Profibus Slave Module
GFK-2193
IC693PCM300
PCM, 160K Bytes (35Kbytes User MegaBasic Program)
GFK-0255
IC693PCM301
PCM, 192K Bytes (47Kbytes User MegaBasic Program)
GFK-0255
IC693PCM311
PCM, 640K Bytes (190Kbytes User MegaBasic Program)
GFK-0255
IC693PTM100/101
Power Transducer Module (PTM)
GFK-1734
IC693TCM302/303
Temperature Control Module (TCM), eight-channel
GFK-1466
*
Obsolete. Listed for reference only.
I/O Data Formats Discrete inputs and discrete outputs are stored as bits in bit cache (status table) memory. Analog input and analog output data are stored as words and are memory resident in a portion of application RAM memory allocated for that purpose.
Default Conditions for Series 90-30 Output Modules At power-up, Series 90-30 discrete output modules default to outputs off. They will retain this default condition until the first output scan from the PLC. Analog output modules can be configured with a jumper located on the module’s removable terminal block to either default to zero or retain their last state. Also, analog output modules may be powered from an external power source so that, even if the PLC has no power, the analog output modules will continue to operate in their selected default state.
GFK-0467M
Chapter 2 System Operation
2-43
Page 63
2
Diagnostic Data Diagnostic bits are available in %S memory that will indicate the loss of an I/O module or a mismatch in I/O configuration. Diagnostic information is not available for individual I/O points. More information on fault handling can be in Chapter 3, “Fault Explanations and Correction.”
Global Data Genius Global Data The Series 90-30 PLC supports very fast sharing of data between multiple CPUs using Genius global data. The Genius Bus Controller, IC693BEM331 in CPU, version 5 and later, and the Enhanced Genius Communications Module, IC693CMM302, can broadcast up to 128 bytes of data to other PLCs or computers. They can receive up to 128 bytes from each of the up to 30 other Genius controllers on the network. Data can be broadcast from or received into any memory type, not just %G global bits. The original Genius Communications Module, IC693CMM301, is limited to fixed %G addresses and can only exchange 32 bits per serial bus address from SBA 16 to 23. For new installations, we recommend this module not be used; instead, use the newer enhanced GCM, which has considerably more capability. Global data can be shared between Series Five, Series Six, and Series 90 PLCs connected to the same Genius I/O bus.
Ethernet Communications The Model 364 CPU (release 9.0 and later) supports connection to an Ethernet network through either (but not both) of two built-in Ethernet ports. AAUI and 10BaseT ports are provided. The Model 374 CPU supports connection to an Ethernet network through two built-in 10BaseT/100BaseTx auto-negotiating full-duplex Ethernet ports. Both the CPU364 and CPU374 support Ethernet Global Data (EGD), which is similar to Genius Global Data in that it allows one device (the producer) to transfer data to one or more other devices (the consumers) on the network. EGD is not supported by Logicmaster 90 software (requires a Windows-based programmer for Series 90 PLCs.)
2-44
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 64
2
Series 90-20 I/O Modules The following I/O modules are available for the Series 90-20 PLC. Each module is listed by catalog number, number of I/O points, and a brief description. The I/O is integrated into a baseplate along with the power supply. For the specifications and wiring information of each module, refer to chapter 5 in the Series 90-20 Programmable Controller User’s Manual, GFK-0551. Catalog Number
Description
I/O Points
IC692MAA541
I/O and Power Supply Base Module, 120 VAC In/120 VAC Out/120 VAC Power Supply
16 In/12 Out
IC692MDR541
I/O and Power Supply Base Module 24 VDC In/Relay Out/120 VAC Power Supply
16 In/12 Out
IC692MDR741
I/O and Power Supply Base Module 24V DC In/Relay Out/240 VAC Power Supply
16 In/12 Out
IC692CPU211
CPU Module, Model CPU 211
Not Applicable
Configuration and Programming Configuration is the process of assigning logical addresses, as well as other characteristics, to the hardware modules in the system. It can be done either before or after programming, using the configuration software or Hand-Held Programmer; however, it is recommended that configuration be done first. Refer to the User’s Manual for your programming software for details on how to create, transfer, edit, and print programs. Chapters 4 through 12 describe the programming instructions that can be used to create ladder logic programs for the Series 90-30 and Series 90-20 programmable controllers. .
GFK-0467M
Chapter 2 System Operation
2-45