Series 90-30/20/Micro PLC CPU Instruction Set Reference Manual: Chapter 3 - Fault Explanation and Correction, pages 74 to 81
Pages 74 to 81 of 337, from Series 90-30/20/Micro PLC CPU Instruction Set Reference Manual
The original document is the PDF (4.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the GE Fanuc IC692CPU211D / IC692MDR541C, Fanuc IC692CPU211D / IC692MDR541C, GE IC692CPU211D / IC692MDR541C and GE Fanuc IC693CPU311X
Page 74
3
Option Module Software Failure The Fault Group Option Module Software Failure occurs when a non-recoverable software failure occurs on a PCM or ADC module. The fault action for this group is Fatal. Error Code:
All
Name:
COMMREQ Frequency Too High
Description:
COMMREQs are being sent to a module faster than it can process them.
Correction:
Change the PLC program to send COMMREQs to the affected module at a slower rate.
Program Block Checksum Failure The Fault Group Program Block Checksum Failure occurs when the PLC CPU detects error conditions in program blocks received by the PLC (downloaded by the programming software). It also occurs when the PLC CPU detects checksum errors during power-up verification of memory or during RUN mode background checking. The fault action for this group is Fatal. Error Code:
All
Name:
Program Block Checksum Failure
Description:
The PLC Operating Software generates this error when a program block is corrupted.
Correction:
(1)
Clear PLC memory and retry the store.
(2)
Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry.
Low Battery Signal The Fault Group Low Battery Signal occurs when the PLC CPU detects a low battery on the PLC power supply or a module, such as the PCM, reports a low battery condition. The fault action for this group is Diagnostic.
3-10
Error Code:
0
Name:
Failed Battery Signal
Description:
The CPU module (or other module having a battery) battery is dead.
Correction:
Replace the battery. Do not remove power from the rack.
Error Code:
1
Name:
Low Battery Signal
Description:
A battery on the CPU, or other module has a low signal.
Correction:
Replace the battery. Do not remove power from the rack.
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 75
3 Constant Sweep Time Exceeded The Fault Group Constant Sweep Time Exceeded occurs when the PLC CPU operates in CONSTANT SWEEP mode, and it detects that the sweep has exceeded the constant sweep timer. The fault extra data contains the actual time of the sweep in the first two bytes and the name of the program in the next eight bytes. The fault action for this group is Diagnostic. Correction:
(1)
Increase constant sweep time.
(2)
Remove logic from application program.
Application Fault The Fault Group Application Fault occurs when the PLC CPU detects a fault in the user program. The fault action for this group is Diagnostic, except when the error is a Subroutine Call Stack Exceeded, in which case it is Fatal. Error Code:
7
Name:
Subroutine Call Stack Exceeded
Description:
Subroutine calls are limited to a depth of 8. A subroutine can call another subroutine which, in turn, can call another subroutine until 8 call levels are attained.
Correction:
Modify program so that subroutine call depth does not exceed 8.
Error Code: Name: Description:
1B CommReq Not Processed Due To PLC Memory Limitations No-wait communication requests can be placed in the queue faster than they can be processed (e.g., one per sweep). In a situation like this, when the communication requests build up to the point that the PLC has less than a minimum amount of memory available, the communication request will be faulted and not processed Issue fewer communication requests or otherwise reduce the amount of mail being exchanged within the system.
Correction: Error Code: Name: Description:
Correction:
GFK-0467M
5A User Shut Down Requested The PLC operating software (function blocks) generates this informational alarm when Service Request #13 (User Shut Down) executes in the application program. None required. Information-only alarm.
Chapter 3 Fault Explanation and Correction
3-11
Page 76
3
No User Program Present The Fault Group No User Program Present occurs when the PLC CPU is instructed to transition from STOP to RUN mode or a store to the PLC and no user program exists in the PLC. The PLC CPU detects the absence of a user program on power-up. The fault action for this group is Informational. Correction:
Download an application program before attempting to go to RUN mode.
Corrupted User Program on Power-Up The Fault Group Corrupted User Program on Power-Up occurs when the PLC CPU detects corrupted user RAM. The PLC CPU will remain in STOP mode until a valid user program and configuration file are downloaded. The fault action for this group is Fatal. Error Code:
1
Name:
Corrupted User RAM on Power-Up
Description:
The PLC operating software (operating software) generates this error when it detects corrupted user RAM on power-up.
Correction:
(1)
Reload the configuration file, user program, and references (if any).
(2)
Replace the battery on the PLC CPU.
(3)
Replace the expansion memory board on the PLC CPU.
(4)
Replace the PLC CPU.
Error Code:
2
Name:
Illegal Boolean OpCode Detected
Description:
The PLC operating software (operating software) generates this error when it detects a bad instruction in the user program.
Correction:
(1)
Restore the user program and references (if any).
(2)
Replace the expansion memory board on the PLC CPU.
(3)
Replace the PLC CPU.
Password Access Failure The Fault Group Password Access Failure occurs when the PLC CPU receives a request to change to a new privilege level and the password included with the request is not valid for that level. The fault action for this group is Informational. Correction:
3-12
Retry the request with the correct password.
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 77
3 PLC CPU System Software Failure Faults in the Fault Group PLC CPU System Software Failure are generated by the operating firmware of the Series 90-30, 90-20 or Micro PLC CPU. They can occur at many different points of system operation. When a Fatal fault occurs, the PLC CPU immediately transitions into a special ERROR SWEEP mode. No activity is permitted when the PLC is in this mode. The only way to clear this condition is to cycle power on the PLC. The fault action for this group is Fatal. Error Code: Name: Description:
Correction: Error Code: Name: Description:
Correction: Error Code: Name: Description:
Correction:
Error Code: Name: Description:
Correction: Error Code: Name: Description:
Correction:
GFK-0467M
1 through B User Memory Could Not Be Allocated The PLC operating software (memory manager) generates these errors when software requests the memory manager to allocate or de-allocate a block or blocks of memory from user RAM that are not legal. These errors should not occur in released products; they are normally encountered only during the firmware development process at the factory. Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry. D System Memory Unavailable The PLC operating software (I/O Scanner) generates this error when its request for a block of system memory is denied by the memory manager because no memory is available from the system memory heap. It is Informational if the error occurs during the execution of a DO I/O function block. It is Fatal if it occurs during power-up initialization or autoconfiguration. Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry. E System Memory Could Not Be Freed The PLC operating software (I/O Scanner) generates this error when it requests the memory manager to de-allocate a block of system memory and the de-allocation fails. This error can only occur during the execution of a DO I/O function block. (1) Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry. (2) Perform the corrections for corrupted memory. 10 Invalid Scan Request of the I/O Scanner The PLC operating software (I/O Scanner) generates this error when the operating system or DO I/O function block scan requests neither a full nor a partial scan of the I/O. This should not occur in a production system. Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry. 13 PLC Operating Software Error The PLC operating software generates this error when certain PLC operating software problems occur. This error should not occur in released products; they are normally encountered only during the firmware development process at the factory. (1) Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry. (2) Perform the corrections for corrupted memory.
Chapter 3 Fault Explanation and Correction
3-13
Page 78
3
Error Code: Name: Description:
Correction:
Error Code: Name: Description:
Correction: Error Code: Name: Description:
Correction:
Error Code: Name: Description:
Correction:
Error Code: Name: Description:
Correction:
Error Code: Name: Description: Correction:
3-14
14, 27 Corrupted PLC Program Memory The PLC operating software generates these errors when certain PLC operating software problems occur. These errors should not occur in released products; they are normally encountered only during the firmware development process at the factory. (1) Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry. (2) Perform the corrections for corrupted memory. 27 through 4E PLC Operating Software Error The PLC operating software generates these errors when certain PLC operating software problems occur. These errors should not occur in released products; they are normally encountered only during the firmware development process at the factory. Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry. 4F Communications Failed The PLC operating software (service request processor) generates this error when it attempts to comply with a request that requires backplane communications and receives a rejected response. (1) Check the bus for abnormal activity. (2) Replace the intelligent option module to which the request was directed. 50, 51, 53 System Memory Errors The PLC operating software generates these errors when its request for a block of system memory is denied by the memory manager because no memory is available or contains errors. (1) Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry. (2) Perform the corrections for corrupted memory. 52 Backplane Communications Failed The PLC operating software (service request processor) generates this error when it attempts to comply with a request that requires backplane communications and receives a rejected mail response. (1) Check the bus for abnormal activity. (2) Replace the intelligent option module to which the request was directed. (3) Check parallel programmer cable for proper attachment. All Others PLC CPU Internal System Error An internal system error has occurred that should not occur in a production system. Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry.
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 79
3 Communications Failure During Store The Fault Group Communications Failure During Store occurs during the store of program blocks and other data to the PLC. If communications with the programming device performing the store is interrupted or any other failure occurs which terminates the load, this fault is logged. As long as this fault is present in the system, the controller will not transition to RUN mode. This fault is not automatically cleared on power-up; the user must specifically order the condition to be cleared. The fault action for this group is Fatal. For additional information on this fault, please see the “Additional Fault Effects” section earlier in this chapter. Correction:
GFK-0467M
Clear the fault and retry the download of the program or configuration file.
Chapter 3 Fault Explanation and Correction
3-15
Page 80
3
Section 3: I/O Fault Table Explanations The I/O fault table reports data about faults in three classifications: •
Fault category.
•
Fault type.
•
Fault description.
The faults described on the following page have a fault category, but do not have a fault type or fault group. Each fault explanation contains a fault description and instructions to correct the fault. Many fault descriptions have multiple causes. In these cases, the error code, displayed with the additional fault information obtained by pressing CTRL-F, is used to distinguish different fault conditions sharing the same fault description. (For more information about using CTRL-F, refer to Appendix B, “Interpreting Fault Tables,” in this manual.) The Fault Category is the first two hexadecimal digits in the fifth group of numbers, as shown in the following example.
02
1F0100
00030101FF7F
0302
0200 84000000000003 | |_____ Fault Category (first two hex digits in fifth group)
The following table enables you to quickly find a particular I/O fault explanation in this section. Each entry is listed as it appears on the programmer screen.
Loss of I/O Module The Fault Category Loss of I/O Module applies to Model 30 discrete and analog I/O modules. There are no fault types or fault descriptions associated with this category. The fault action is Diagnostic.
3-16
Description:
The PLC operating software generates this error when it detects that a Model 30 I/O module is no longer responding to commands from the PLC CPU, or when the configuration file indicates an I/O module is to occupy a slot and no module exists in the slot.
Correction:
(1)
Replace the module.
(2)
Correct the configuration file.
(3)
Display the PLC fault table on the programmer. Contact GE Fanuc PLC Field Service, giving them all the information contained in the fault entry.
Series 90™-30/20/Micro PLC CPU Instruction Set Reference Manual – May 2002
GFK-0467M
Page 81
3
Addition of I/O Module The Fault Category Addition of I/O Module applies to Model 30 discrete and analog I/O modules. There are no fault types or fault descriptions associated with this category. The fault action is Diagnostic.
GFK-0467M
Description:
The PLC operating software generates this error when an I/O module which had been faulted returns to operation.
Correction:
(1)
No action necessary if the module was removed or replaced, or the remote rack was power cycled.
(2)
Update the configuration file or remove the module.
Description:
The PLC operating software generates this error when it detects a Model 30 I/O module in a slot which the configuration file indicates should be empty.
Correction:
(1)
Remove the module if it is there by mistake.
(2)
Update and restore the configuration file to include the extra module if it is supposed to be there.
Chapter 3 Fault Explanation and Correction
3-17