B.1 - I/O Driver Module Introduction

A PiC900 system may include expansion racks containing I/O modules. The I/O driver module must be installed in each expansion rack. A PiC900 CPU module with a daughter board or a PiC9XX CPU module with communication capability must be installed in the master rack. The I/O driver module must always be in the second slot from the left in each expansion rack. Refer to Appendix N2 for information on I/O expansion connections. The DIAG LED turns on briefly while the diagnostic tests are running. Figure B1-1. The I/O DRIVER Module I/O Driver

DIAG CONFIG DATA IN DATA OUT

Name of module Diagnostic LED

3 I/O driver LEDs

6-pin I/O driver twisted pair connector

In

Out (located behind IN)

Fiber Optic connectors

B.1 -1

Page 96

I/O Driver Module

Connections

The pinout for the 6-pin I/O driver connector is shown in Figure B1-2. This connector is used for local I/O expansion using twisted pair wire. The top two connections are for the I/O expansion twisted pair out. The next two are for the I/O expansion twisted pair in. The fifth connection is a shield used with twisted pair wire. The sixth connection is not used. Remote I/O expansion uses fiber optic cable connected to the fiber optic connectors shown in Figure B1-1. NOTE: It is possible to combine local and remote expansion racks in the same system. Use twisted pair wiring to connect racks that are up to 40 feet apart and use fiber optic cable to connect racks that are up to 2000 feet apart. EMC NOTE To ensure EMC compliance, use fiber optic cables only. In some applications using only local expansion racks, it may be possible to comply to EMC standards when using shielded twisted pair wires. Verification would have to be done on a system by system basis. Figure B1-2. Pinout for the I/O driver twisted pair connector

I/O expansion twisted pair out I/O expansion twisted pair in

+ + -

Shield Not used

CAUTION The system is polarity dependent. Always connect the positive (+) output of one module to the positive (+) input of the next and the negative (-) to the negative (-), etc. Always connect the positive (+) input of one module to the positive (+) output of the next and the negative (-) to the negative (-), etc.

B.1 -2

Page 97

I/O Driver Module

LEDs

There are three LEDs on the I/O driver module in addition to the DIAG LED. They are located directly under the DIAG LED as shown in Figure B1-3. Figure B1-3. I/O Driver LEDs Diagnostic This rack configured I/O driver LEDs

I/O expansion line activity in I/O expansion line activity out AA823-0791

NOTE: The diagnostic LED on the CPU module flashes certain error codes connected with I/O expansion. These codes are listed in Appendix M. This rack configured

I/O expansion line activity out

On

Communication established with this expansion rack connected in an I/O expansion loop.

Off

Communication not established

Dull glow Indicates the line transmitting out is active. Off

I/O expansion line activity in

No activity out

Dull glow Indicates the line receiving in is active. Off

No activity in

B.1 -3

Page 98

I/O Driver Module

Specification Table

Characteristics

I/O driver module specifications

Function

Allows additional racks of I/O modules to be connected to a PiC900 master rack

Part number

502-03657-03

PiC9XX CPU module with communication capabilities in the master rack Logic side power requirements (typical)

510 mA @ +5V

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

B.1 -4