Page 99

B.2 - Serial Communications Module (2, 4 channel) Introduction

The serial communications module provides two or four channels to be used for asynchronous serial communication with external devices such as computers, operator interface devices, etc. For each channel, RS232 electrical interface is provided for data and control lines; RS422/485 electrical interface is provided for data lines. The DIAG LED goes on briefly while the diagnostic tests are running. Figure B2-1. Serial Communications Module (2, 4 ch)

COMMUNICATIONS

Name of module Diagnostic LED

DIAG

1 3 5 7 9 11 13

Screw terminal connector

15 17 19 21 23 25 27 29 31 33 35 37 39

Door

AA890-3391

B.2 -1

Page 100

Serial Communications Module (2, 4 channel)

Connections

A screw terminal connection is provided for each input and output as shown in Figure B2-2. RS232 or RS422/485 interface is available on all four channels. This table defines the inputs and outputs available for each channel on the module using an RS232 interface. Label

Definition

Input/Output

RDx_232

Receive data

Input

TDx_232

Transmit data

Output

CTSx_232

Clear to send (handshaking)

Input

RTSx_232

Request to send (handshaking)

Output

DTRx

Data terminal ready (pullup to 12V) Output

This table defines the inputs and outputs available for each channel on the module using an RS422/485 interface. Label

Definition

Input/Output

RDx_DIF+

Receive data

Input

RDx_DIFTDx_DIF+ TDx_DIF-

B.2 -2

Input Transmit data

Output Output

Page 101

Serial Communications Module (2, 4 channel)

Figure B2-2. Screw Terminal Connection Assignments

SCREW TERMINALS CONNECTION

CONNECTION RD1_232

CTS1 _232

1

RTS1_232

3

TD1_DIF+

5

TD1_232

RD1 _DIF+

RS232 or RS422/485

Channel 1 (Pins 1 to 8)

RD1 _DIFTD1_DIF-

7 COMMON

DTR_A

9

CTS2 _232

11

Available for all channels SHIELD

(Pins 9 to 11)

RD2_232 RTS2_232

TD2_DIF+

TD2_DIF-

13 TD2_232

RS232 or RS422/485

RD2 _DIF+

(Pins 12 to 19)

15

Channel 2

17 RD2 _DIF-

CTS3_232

19

RTS3_232

21

RD3_232

TD3_DIF+

TD3_DIF-

TD3_232

RS232 or RS422/485

RD3_DIF+

(Pins 20 to 27)

Channel 3

23 25 RD3_DIF-

DTR_B

27 COMMON

SHIELD

29

Available for all channels (Pins 28 to 30)

RD4_232 CTS4_232

31 TD4_232

RTS4_232

33 RD4_DIF+

TD4_DIF+

35

TD4_DIF-

37

(Future Use)

39

RS232 or RS422/485

Channel 4 (Pins 31 to 38)

RD4_DIF-

(Future Use)

AA891-3391

B.2 -3

Page 102

Serial Communications Module (2, 4 channel)

Figure B2-3 illustrates how to connect an RS232 device to channel 1. Maximum cable length for RS232 devices is 50 feet. Figure B2-3. Connections for an RS232 Device (Ch 1)

External RS232 Communication Device

Connections RD1_232

Screw Terminals

1

CTS1_232 TD1_232

3

RTS1_232

5

7 Common 9 DTR_A

AA892-4491

B.2 -4

Page 103

Serial Communications Module (2, 4 channel)

Figure B2-4 illustrates how to connect an RS422/485 device to channel 1. NOTE: RS422 refers to an earlier standard that applied only to single drop connections. RS485 refers to multidrop connections. See Figure B2-5. Since the interface is used for both RS422 and RS485, terminating resistors are required for proper operation. Figure B2-4. Connections for an RS422/485 Device (Ch 1) Screw Terminals

1

100 ohm terminating resistors

3 External RS422/485 Communication Device

Connections RD1_DIF+

5

TD1_DIF+ RD1_DIF-

7

TD1_DIF-

9

11

Note: Shield pins 11 and 30 are connected internally to SPG.

30

B.2 -5

Page 104

Serial Communications Module (2, 4 channel)

With RS485, multidrop connections are possible as shown in Figure B2-5. The serial communications module acts as the master, sending control sequences to activate/deactivate external devices such as hand-held terminals, touch control screens, etc. Up to 32 devices can be connected per channel. Maximum cable length is 4000 feet. A terminating resistor (100 Ω) is installed on each end of the system as shown. Figure B2-5. Multidrop Connections

Serial Communications Module Screw Terminals

1

100 ohm terminating resistors

3 RD1_DIF+

5

TD1_DIF+ RD1_DIF-

7

TD1_DIF-

9

11 Note: Shield pins 11 and 30 are connected internally to SPG.

30 100 ohm terminating resistors

B.2 -6

External communication devices-Hand-held pendants (Up to 32 devices can be connected)

Page 105

Serial Communications Module (2, 4 channel)

Theory of operation

Serial communication is accomplished through the use of one or two DUARTs (Dual Universal Asynchronous Receiver/Transmitter). External serial devices are connected to a given channel of a DUART through either an RS232 interface or an RS422/485 interface. There is a dedicated processor with FIFO buffers on the module which services the DUARTs. This saves the main CPU from the time-consuming task of directly polling each DUART. The processor supports data transfers with rates up to 19.2 Kbaud for each channel. At rates above 9600 baud, hardware handshaking should be used. The FIFO buffers provide the main means of data transfer between the main CPU and the DUARTs. Up to 1 K of input data and 1 K of output data may be buffered at a given time for each channel. Communication is handled through PiCPro software.

B.2 -7

Page 106

Serial Communications Module (2, 4 channel)

Specification Table

Characteristics

Communications Module Specifications

Function

Provides 2 or 4 asynchronous serial communication channels to be used with serial interface devices

Part number

2 channel- 502-03676-23 4 channel- 502-03676-03

Dedicated processor

80C186, 8 MHz, 32K x 16 EPROM, 8K x 16 RAM

Ports 1, 2, 3, and 4

RS232 or RS422/485 electrical interface Supports RTS/CTS hardware handshaking Baud rates to 19.2 Kbps

Logic side power requirements (typical)

420 mA @ +5V 450 mA @ +5V 5 mA @ +15V 5 mA @ -15V

(2 ch) (4 ch)

50 mA per terminated RS422/485 channel @ +5V 5 mA per active RS232 channel @ +15V 6 mA per active RS232 channel @ -15V Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

B.2 -8

Page 107

Serial Communications Module (2, 4 channel)

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

B.2 -9

Page 108

Serial Communications Module (2, 4 channel)

B.2 -10