For the Giddings & Lewis 502-03550-02

Page 109

B.3 - DeviceNet™ Module Introduction

The DeviceNet™ scanner module is an interface between the PiC and a DeviceNet network. The module contains an on-board processor, a DeviceNet compliant interface, and firmware that makes it act as the master to all other nodes on the network. Prior to initial operation, a file is generated with specific configuration software in an external PC. This file must be downloaded via the RS232 configuration port to the DeviceNet module prior to initial operation. Two indicator LEDs (IN/OUT) are connected to this configuration port. Directly above the DeviceNet port are two LEDs that provide operation information; Network Status and DeviceNet Scanner Status. The DIAG LED goes on briefly while the diagnostic tests are running. Figure B3-1. DeviceNet Module DeviceNet™ DIAG IN OUT CNFG PORT

Network Status DeviceNet Port Phoenix 5-pin

Name of module Diagnostic LED Configuration Port LEDs

DeviceNet Scanner Status 1 2 3 4 5

Door

Configuration Port RS232 Port 9-pin D

B.3 -1

Page 110

DeviceNet™ Module

Connections

DeviceNet connections are illustrated in Figure B3-2. Up to 63 DeviceNet Nodes may be attached to the DeviceNet scanner module. Figure B3-2. DeviceNet Connections

PiC CSM CPU

DEVIC

To DeviceNet Trunk

DeviceNet Node

DeviceNet Node

To DeviceNet Trunk

DeviceNet Node

PC connected to RS232 port for downloading file generated with Giddings & Lewis configuration software

The DeviceNet Port

The DeviceNet port is on the front of the module near the center as shown in Figure B3-1. The pinout for the DeviceNet port is shown below: Pin #

B.3 -2

Signal Name

Standard Wire Colors

1

V- black

2

CAN_L blue

3

Shield (drain)

bare

4

CAN_H white

5

V+ red

Page 111

DeviceNet™ Module

The Configuration (RS232) Port

There is an RS232 port on the lower front of the module as shown in Figure B3-1. This is used to connect to a PC in order to download a file representing your DeviceNet network. Pin #

Signal Name

In/Out

2

Receive Data

In

3

Transmit Data

Out

5

Ground

In/Out

LEDs

The two configuration port LEDs and DeviceNet port LEDs are described below. Port

LED

Color

State

Definition

DeviceNet

Network status Green

OFF

Off-line

ON

On-line and connected to at least one node

Flashing

On-line and connected to at least one node

ON

Unrecoverable Fault (dupicate MAC ID check failed, critical bus fault, etc.)

Flashing

I/O connections in timed-out state or other Recoverable Fault

OFF

No power or else reset asserted

ON

Scanner OK and active

Flashing

Scanner OK but not active

ON

Hardware or software error

Flashing

Recoverable configuration error (invalid data downloaded)

Orange

ON

Configuration (download) mode

Red

Flickering

Data is being passed to the module

OFF

No data to the module

Flickering

Data is being passed from the module

OFF

No data from the module

RED

Scanner status Green

Red

Configuration IN

OUT

Red

B.3 -3

Page 112

DeviceNet™ Module

Theory of operation

The DeviceNet scanner module provides a memory image of the nodes (slaves) connected to a DeviceNet network. It is this memory image that is controlled by your LDO created in PiCPro. The module’s on-board processor continually transfers data between this memory image and the actual DeviceNet nodes. Communication between the DeviceNet module and the nodes can be set at 125 Kbaud, 250 Kbaud, or 500 Kbaud. The baud rate, the relationship between the memory image and specific data in each node, and other parameters are established with configuration software run in an external PC. This configuration software generates two files. One file is downloaded to the DeviceNet module through its RS232 serial port. The other file is used by PiCPro to establish the relationship between the memory image and the declared variables in the LDO. To ensure that a given location in the memory image is connected to a variable in the LDO and to the corresponding data in the DeviceNet node, the same tag name or label must be used. For example, when running the configuration software, PROX_SW1 could be used as the name for the boolean bit representing a DeviceNet proximity switch’s logic state. The name PROX_SW1 must also be used for the corresponding variable in your LDO.

NOTE The G&L DeviceNet configuration software (G&L Part No. M.1017.4267) is required to configure the DeviceNet scanner (within the DeviceNet module) for the devices on the associated network.

IMPORTANT Additional information about DeviceNet can be obtained from www.odva.org.

B.3 -4

Page 113

DeviceNet™ Module

Specification Table

Characteristics

DeviceNet Module Specifications

Function

Interfaces to a DeviceNet network with up to 63 other nodes

Part number

M. 1016.9720 (old # 502-04157-98)

DeviceNet Port

Phoenix style 5-pin male connector

Configuration Port

RS232 interface

Logic side power requirements (typical)

275 mA @ 5 V

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

B.3 -5

Page 114

DeviceNet™ Module

NOTES

B.3 -6