B.3 - DeviceNet™ Module Introduction
The DeviceNet™ scanner module is an interface between the PiC and a DeviceNet network. The module contains an on-board processor, a DeviceNet compliant interface, and firmware that makes it act as the master to all other nodes on the network. Prior to initial operation, a file is generated with specific configuration software in an external PC. This file must be downloaded via the RS232 configuration port to the DeviceNet module prior to initial operation. Two indicator LEDs (IN/OUT) are connected to this configuration port. Directly above the DeviceNet port are two LEDs that provide operation information; Network Status and DeviceNet Scanner Status. The DIAG LED goes on briefly while the diagnostic tests are running. Figure B3-1. DeviceNet Module DeviceNet™ DIAG IN OUT CNFG PORT
Network Status DeviceNet Port Phoenix 5-pin
Name of module Diagnostic LED Configuration Port LEDs
DeviceNet Scanner Status 1 2 3 4 5
Door
Configuration Port RS232 Port 9-pin D
B.3 -1
Page 110
DeviceNet™ Module
Connections
DeviceNet connections are illustrated in Figure B3-2. Up to 63 DeviceNet Nodes may be attached to the DeviceNet scanner module. Figure B3-2. DeviceNet Connections
PiC CSM CPU
DEVIC
To DeviceNet Trunk
DeviceNet Node
DeviceNet Node
To DeviceNet Trunk
DeviceNet Node
PC connected to RS232 port for downloading file generated with Giddings & Lewis configuration software
The DeviceNet Port
The DeviceNet port is on the front of the module near the center as shown in Figure B3-1. The pinout for the DeviceNet port is shown below: Pin #
B.3 -2
Signal Name
Standard Wire Colors
1
V- black
2
CAN_L blue
3
Shield (drain)
bare
4
CAN_H white
5
V+ red
Page 111
DeviceNet™ Module
The Configuration (RS232) Port
There is an RS232 port on the lower front of the module as shown in Figure B3-1. This is used to connect to a PC in order to download a file representing your DeviceNet network. Pin #
Signal Name
In/Out
2
Receive Data
In
3
Transmit Data
Out
5
Ground
In/Out
LEDs
The two configuration port LEDs and DeviceNet port LEDs are described below. Port
LED
Color
State
Definition
DeviceNet
Network status Green
OFF
Off-line
ON
On-line and connected to at least one node
Flashing
On-line and connected to at least one node
ON
Unrecoverable Fault (dupicate MAC ID check failed, critical bus fault, etc.)
Flashing
I/O connections in timed-out state or other Recoverable Fault
OFF
No power or else reset asserted
ON
Scanner OK and active
Flashing
Scanner OK but not active
ON
Hardware or software error
Flashing
Recoverable configuration error (invalid data downloaded)
Orange
ON
Configuration (download) mode
Red
Flickering
Data is being passed to the module
OFF
No data to the module
Flickering
Data is being passed from the module
OFF
No data from the module
RED
Scanner status Green
Red
Configuration IN
OUT
Red
B.3 -3
Page 112
DeviceNet™ Module
Theory of operation
The DeviceNet scanner module provides a memory image of the nodes (slaves) connected to a DeviceNet network. It is this memory image that is controlled by your LDO created in PiCPro. The module’s on-board processor continually transfers data between this memory image and the actual DeviceNet nodes. Communication between the DeviceNet module and the nodes can be set at 125 Kbaud, 250 Kbaud, or 500 Kbaud. The baud rate, the relationship between the memory image and specific data in each node, and other parameters are established with configuration software run in an external PC. This configuration software generates two files. One file is downloaded to the DeviceNet module through its RS232 serial port. The other file is used by PiCPro to establish the relationship between the memory image and the declared variables in the LDO. To ensure that a given location in the memory image is connected to a variable in the LDO and to the corresponding data in the DeviceNet node, the same tag name or label must be used. For example, when running the configuration software, PROX_SW1 could be used as the name for the boolean bit representing a DeviceNet proximity switch’s logic state. The name PROX_SW1 must also be used for the corresponding variable in your LDO.
NOTE The G&L DeviceNet configuration software (G&L Part No. M.1017.4267) is required to configure the DeviceNet scanner (within the DeviceNet module) for the devices on the associated network.
IMPORTANT Additional information about DeviceNet can be obtained from www.odva.org.
B.3 -4
Page 113
DeviceNet™ Module
Specification Table
Characteristics
DeviceNet Module Specifications
Function
Interfaces to a DeviceNet network with up to 63 other nodes
Part number
M. 1016.9720 (old # 502-04157-98)
DeviceNet Port
Phoenix style 5-pin male connector
Configuration Port
RS232 interface
Logic side power requirements (typical)
275 mA @ 5 V
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
B.3 -5
Page 114
DeviceNet™ Module
NOTES
B.3 -6