The text of a manual · part 5 of 13
Micro 84 Programmable Controller User's Manual, pages 41 to 50
Pages 41 to 50 of 124
The original document is the PDF (6.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Gould Micro 84 Controller, Modicon Micro 84 Controller, AEG Micro 84 Controller and Schneider Micro 84 Controller
Page 41
Place cursor in upper node location and press the following keys in sequence: 010 jl lT1.01
4020
I]
Logic Element Entry Rules The following rules and restrictions apply when entering logic element information. 1.
Logic coils cannot be entered directly over existing double-node logic elements (error code 92). A coil can be entered over a single-node logic element (the overwritten logic element is deleted and replaced by the coil).
2.
A double-node logic element cannot be entered over a coil. In both cases above, the logic element to be replaced must first be erased by entering a horizontal open.
J
6.3.4.11 d
3.
A double-node logic element can be entered over another double-node logic element or any logic element in the upper node position. To replace a logic element, the lower node must be a horizontal open. A double-node logic element cannot be entered where obliteration of one-half of another double-node logic element would occur (error code 92).
4.
A double-node logic element cannot be entered where the lower node extends below the bottom rung of a network (error code 93).
5.
A contact can be entered over a double-node logic element (either the upper or lower node). The other node is replaced by a horizontal open.
6.
No vertical connectors can be entered in the bottom rung or in the seventh column.
7.
Out of range or inappropriate reference numbers or preset values cause an error code (94) to appear.
6.
A logic coil with a given reference number can occur only once in the user’s logic. An attempt to write one results in error code 93. A logic coil reference number can be assigned to one or more contacts. The logic coil can then not only be used as a discrete signal to an output device, but also as a control for other user logic (for example, the latch in a seal circuit).
9.
No data can be entered if the Memory Protect Switch is ON.
10.
Any logic coil, whether disabled or enabled ON or OFF, is set to OFF when it is deleted by being replaced by another logic element.
SHIFT/ENTER VALUE The SHIFT/ENTER VALUE function allows the user to insert a value into a register or to change the contents of a register. To use this function, first make sure the appropriate register reference number appears in the REF display. Using the numeric keypad, enter the desired value (O-999) for the contents of the register.
6-13
Page 42
The new register contents appear in the DATA display. Enter the contents into the register by pressing the SHIFT and ENTER keys sequentially. 4
To enter or change the contents of register 4021, position the cursor in the proper location, and press the following keys: 4021
I
FIEF nnnn
II
/I where nnnn is the value of the register contents being entered. 6.3.4.12
DISABLE (SHIFT/FORCE) The DISABLE (SHIFT/FORCE) function allows the user to disable a coil or an input. To disable a coil, the cursor must be positioned on top of the coil. To disable an input, the REF display must contain the reference number of the input logic element. When the SHIFT and FORCE keys are pressed, the input is either enabled or disabled, depending upon its previous state. If the new status is disabled, a “d” appears to the left of the status in the DATA display (dOFF or dON). If a coil is disabled, the Node display reflects the current power status. To re-enable the logic element, press the SHIFT and FORCE keys a second time.
6.3.4.13
FORCE-SHIFT/DISABLE The FORCE key is used to toggle the power status of a previously disabled coil or input. When the FORCE key is pressed and the REF display contains a disabled input (10Xx), or the cursor is on a disabled coil (OOXX),the DATA display shows the power status of the element.
6.4
MEMORY PROTECT KEYLOCK SWITCH A keylock switch is located on the front of the P370 Programmer. This hardware feature is designed to prevent accidental or unauthorized changes from being made to the user portion of memory using the programmer. It does not inhibit the normal operation of the controller but does prevent any changes from being made to the user program in the controller. All other programmer functions are available (i.e., element status can be checked, register contents can be monitored, etc.). When the key is vertical, it can be removed and controller memory is protected. When the key is inserted and is in the horizontal position, controller memory is unprotected and changes to the user program can be made from the P370 Programmer. (User memory can be changed at any time using the Program Pack (see Section 8).)
6.5
PROGRAMMER OPERATIONS Tables 6-2 through 6-4 provide a quick reference for each of the four programming panel operating modes and: 1.
The liquid crystal displays active during each mode.
2.
The function keys operational during each mode.
3.
The function keys used for panel mode entry.
6-14
Page 43
Table 6-2. LCD Displays
During Panel Modes
PANEL MODE T
DISPLAY AREA
EXAMINE
ENTER
SUPERVISORY
ERROR
NETWORK
Displays current network number
Displays current network number.
SUP4:Displays current network number. Others: Blank
Contains network number in which error occurred.
REFERENCE
Displays Reference Number or Preset Value
Blank or displays preset data just entered.
SUPX = Supervisory Code
Blank
DATA
If Reference field contains OOXX, 10Xx, or 2RXX, displays H or h if in Hold mode, d if Disabled, ON or OFF for state if register ref displays 000-999.
Blank or displays data just entered.
1. Blank until command initiated, -Reads CONF (after first ENTER) then Reads DONE (after second ENTER)
Exy = Error Code
Power Flow and Cursor
Normal Cursor
Normal
SUP4: Real-time power flow and cursor move, ment Others: Blank
Blank
Element
1. If monitoring node at cursor position, the node graphic is displayed. 2. No display if monitoring a reference not associated with cursor.
Blank or displays logic element just entered.
Blank
Blank
COMM OK
Normal
Function:
ON for good communication,
SHIFT
Normal
Function:
ON if Shift key is depressed
ENTER
Blank
ON
Blank
Blank
EXAMINE
ON
Blank
Blank
Blank
Normal Function Function Others: Blank
SUP4: Normal Function
Normal
Element LED
Type
Status
Normal
Power Flow
Function
Function
6-15 off for bad communication
Page 44
Table 6-3. Key Usage/Panel Mode
SHIFT ALL MODE RESET | RESET | CLEAR | SUPV ENTER | NUMERICS | CURSOR | HOLD | OTHERS
Examine Mode Xx 4 » 4 > 4 Xx Xx x Xx X
Enter Mode Xx X X Xx X 4
6-16
Supervisory Mode User Error Panel/Controller/
Communication Errors x x«< KK <x~ <x x
Table 6-4. Panel Mode Entry
FROM TO:
EXAMINE
SUPERVISORY
ENTER
HOLD STATE
Enter
Supervisory
Error
Hold State
Examine
Press ENTER, RESET, or SHIFT/ RESET
Press SUPV, 0 and ENTER, or RESET, or SHIFT/ RESET
Press RESET or SHIFT/RESET
Press any key except logic element numeric, or CLEAR
N/A
N/A
N/A
Press SUPV
Press SUPV
Press SUPV Key
N/A
N/A
N/A
Press any logic element, numeric, or CLEAR
Press any logic element, numeric, or CLEAR
N/A
N/A
N/A
N/A
Press HOLD
Page 45
PROGRAMMING
SECTION 7 THE MICRO 84
The basic element used in programming the MICRO 84 Programmable Controller is the contact. A contact can be either normally open or normally closed. Associated with each contact is a logic element (indicating whether the contact is normally open or normally closed) and a reference number. The reference number ties the logic element to a specific connection on the l/O input module. The input used to control the status of a contact is called a discrete input (i.e., it turns the contact either to the non-normal condition or returns it to the normal condition). Another type of input that can be used is numeric data. This information is stored in an input register. Each register also has an associated reference number. A coil is another logic element and its state (energized or de-energized) is determined by the various inputs that control it. A coil is an output used to control a specific piece of user equipment or as input to another network. Each coil is associated with a specific reference number. 7.1
NETWORKS In the MICRO 84, each program element occupies one or two “nodes”. The nodes are arranged so that seven elements can be entered horizontally (a rung on the ladder). Up to four rungs can be combined to form a network. A network then, is the ladder diagram program. The number of logic elements that can be contained in a MICRO 84 depends upon the complexity of the networks and the memory size of the controller. Figure 7-1 illustrates a typical multi-node network.
J
7.2
SOLVING NETWORK LOGIC The MICRO 84 function is to “solve” the ladder logic networks. To do this, it “scans” the various elements of a network, checking the state of each input element (are contacts open or closed, etc.) and setting the status of the output coils accordingly. In performing its scan of a network, the MICRO 84 checks the status of the leftmost COLUMN of elements first and then proceeds COLUMN by COLUMN to the right until the network is “solved”. An element in Row 3, Column 4 is scanned (and solved) before an element in Row 1, Column 6. The output of the first element can be used as input to the second element. Figure 7-2 illustrates the sequence the controller uses in solving a network. TIMER
0004
0060
COUNTER ooo5
0060
COUNTER
0006
0024 I
TI.0
0005
4015
-f-1_
Figure
0006 4014
7-l. Typical Multi-Node
7-1
4013
Network
Page 46
I
2
3
4
5
6
7
Figure 7-2. Network Solving Sequence
Because the MICRO 84 solves a network in a particular fixed sequence, it is possible to arrange the logic elements in such a way that the status of a coil can be used as discrete input to a contact in a column further to the right than the coil (see Figure 7-3). The status of a coil also can be used as discrete input to another network.
TIMER 0003
0002
0030
TIMER r-l 0030
0002 I I__
TI.0 4011
I
1
Figure 7-3. Coil Used as Discrete Input
7.3
NETWORK POWER FLOW Within a network, power flow is from left to right, bottom to top, or top to bottom. When displayed on the LCD programming panel, power flow is indicated for all contacts by illuminating those contacts that are passing power from left to right.
7.4
LADDER LOGIC PROGRAMMING PAD A Ladder Logic Programming Pad has been designed and is available for use in planning and documenting ladder logic programs. Figure 7-4 shows the format of the pad.
7-2
Page 47
i Program
Name
Writer Date
1
2
3
5
4
6
7
Comnwntn
A
6 --
----
----
----
----
----
----
-- c --
----
----
----
----
----
----
--
D --
----
----
----
----
----
----
--
2
3
4
Program
Name
Writer Nhvbrk
Date 1
5
Number 6
7
Commants
A
B c--
D
Figure
7.5
7-4. Ladder Logic Programming
Pad
REFERENCE NUMBERS In the programming of the MICRO 84 Programmable Controller, four digit reference numbers are used in building the program logic. These reference numbers are divided into three broad categories: discrete, register, and sequencer. Discrete references are used for items that can be either ON or OFF, such as contacts, pushbuttons, motor starters, relay coils, limit switches, solenoid valves, etc. Register references are used to store numeric values such as counters, timers, analog values, etc.; all registers can store numbers that are three decimal numbers long (O-999). These numbers are stored in binary-coded decimal @CD) format. Sequencers operate like stepping drum rotary switches with a single reference contact at each position of the stepping switch. Sequencer operations are controlled by numeric values placed in specific registers (see “Sequencers” (Drum Programmers) later in this section).
7-3
Page 48
Any specific reference number can be used as many times as required throughout the logic except for a coil. A coil can be used as an output only once but can be used as many times as desired as an internal contact. Reference
7.6 numbers are defined as follows: Reference Number M84-002
Type
M84-001
Coils and discrete outputs (lights, solenoids) or internal contact
0001-0032
0001-0064
Input registers (numeric data)
3001-3004
3001-3004
Sequencers
21 Xx-28Xx XX-Step (01-16)
Same
Usable as sequencer registers
4001-4008
4001-4008
Discrete inputs (contacts, pushbuttons)
1001-1032
1001-1064
Internal registers (numeric data)
4001-4020
4001-4032
Output registers
4010, 4012, 4014, 4016
4010, 4012, 4014, 4016, 4018, 4020, 4022, 4024
PROGRAMMING FUNCTIONS The MICRO 84 Programmable Controller provides the capability to program or simulate the operation of relay contacts, timers, sequencers, counters, and arithmetic functions. All programming is done on the basic format of up to seven elements in each horizontal row or rung. A network can be a single rung, two rungs, or up to four rungs. Relay type elements occupy a single node position within a network and non-relay type elements (counters, timers and arithmetic operations) occupy two vertically oriented node positions within a network. Data is entered directly into the memory of the controller (it is not stored in the programming panel). If AC line power is interrupted prior to completion of the programming, whatever data has been entered is retained. No additional operations are required; whatever data the user enters is the data stored for use by the controller. Network elements can be added, deleted, or changed at any time using the programming panel. The logic changes do not interrupt the controller’s operation. In addition, the effect of any coil (input or output) on system operation can be tested by simulating inputs and outputs using the MICRO 84’s disable feature.
7-4
Page 49
7.6.1
7.6.1 .l
Basic Programming Elements The basic programming elements are the contacts, coils, and connectors shown below: Normally Open Contact
--it-
The normally open contact is the basic logic element point used in ladder logic diagrams. The logic element is controlled by a discrete input (reference number 10Xx) or by a coil (reference number 00Xx).
7.6.1.2
Normally Closed Contact
The normally closed contact is controlled the same way as a normally open contact.
7.6.1.3
Coil
J
The coil (reference number 00Xx) is the discrete output from ladder logic. A coil is used either to provide the control signal for an external discrete device (solenoid, motor starter, indicator lamp, etc.) and/or as the input for an internal contact. A coil can be programmed only once as a discrete output. Once programmed, it can be referred to as many times as desired as an internal contact. More than one coil (unlatched or latched) can appear on a single rung. Each coil on a rung is treated as if it were connected to the right rail of the network. Therefore, is programmed in the MICRO 84 as:
7-5
Page 50
7.6.1.4
Latched Coil
The latched coil retains its state when power is removed (or fails). Normally, coils are reset to OFF upon power-up. A latched coil will not be altered and thus will retain the ON or OFF condition it had when power was removed.
7.6.1.5
Horizontal Connector -
0
0
The horizontal connection is a short between two nodes on a ladder logic rung. The shifted horizontal connector is a horizontal open.
7.6.1.6
Vertical Connector
The vertical connector is a short between two rungs in a ladder logic network. The shifted vertical connector is a vertical open.
7.6.2
Timers Two timer rates are provided in the MICRO 84: one second and one tenth of a second. These internal timers can be used to create as many logic program timers as are necessary. The timer content is not lost due to a power failure. The one second timer (Tl.O)-is used to measure times between 1 second and 999 seconds. The one tenth of a second timer (TO.l) is used to measure times between 0.1 second and 99.9 seconds. The format of the timer element is shown below:
1
TIMER INPUT I CONTROL
INPUT 2
_
IN
ENABLE RESET
PRESET nnn ,3OOX,4OXXI
OUTPUT I
ACCUM.TIME 4oxx
OUTPUT 2
7-6
PRESET = ACCUM.TIME
PRESET 3 ACCUM.TIME