X200 Series Inverter Quick Reference Guide • • •
Single-phase Input 200V class Three-phase Input 200V class Three-phase Input 400V class
Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NT3011XB • Sep 2007
Page 2
!
Caution: Be sure to read the X200 Manual and the X200 Manual Addendum, and follow their Cautions and Warnings for the initial product installation. This Quick Reference Guide is intended for reference use by experienced users in servicing existing installations.
Power Circuit Terminals Inverter models X200-002SFEF/NFU, -004SFEF/NFU
SFEF
L1
/
NFU
L1
L2 L3/N
N Jumper
Jumper Jumper -
+
+1
U/T1 V/T2 W/T3
Inverter models X200-005SFEF, -007SFEF/NFU to -022SFEF/NFU, -037LFU to -075LFU, 004HFEF/HFU to –075HFEF/HFU
SFEF
L1
/
NFU,LFU
L1
L2 L3/N
HFEF,HFU
R/L1 S/L2 T/L3
N Jumper Jumper
Jumper Jumper U/T1 V/T2 W/T3
!
-
+
+1
Caution: Power terminal assignment is is different compared to old models such as L100, L200 series. Pay attention when wiring the power cable.
-1-
Page 3
Control Circuit Terminals
Alarm relay AL2 AL1 AL0 Analog output AM
Analog inputs H
O
OI
Logic outputs
Logic inputs L
5
4
3
2
1
L PCS P24 CM2 11 Jumper
Terminal Name P24
Description +24V for logic inputs
Ratings and Notes 24VDC supply, 30mA max. (Notes: Do not use for network power. Do not short to terminal L) 1, 2, 3, 4, 5 Intelligent (programmable 27VDC max. (Use P24 or an discrete logic) inputs external supply reference to terminal L), 4.7kΩ input impedance. 11 Discrete logic output 50mA max. ON current, 27VDC max. OFF voltage L (right) GND for logic inputs Sum of input 1 to 5 currents (Note: Do not ground) CM2 Common for logic 50mA max for terminal 11 outputs current AM Analog voltage output 0 to 10VDC, 1mA max. L (left) Common for analog Sum of OI, O and H currents inputs (return) OI Analog input, current 4 to 19.6mA range, 20mA nom. O Analog input, voltage 0 to 9.6VDC range, 10VDC nominal, 12VDC max., input impedance 10kΩ H +10V analog reference 10VDC nominal, 10mA max. AL0 Relay common contact Contact rating AL1 Relay contact, normally Max resistive load=250VAC, 2.5A; 30VDC 3A; closed during RUN AL2 Relay contact, normally Max inductive load=250VAC, 0.2A; 30VDC 0.7A open during RUN Minimum load=5VDC 100mA, 100VAC 10mA Note) Analog input O and OI cannot be used at the same time.
-2-
Page 4
Basic Wiring Diagram The following wiring diagram shows the power and motor connections for basic operation. The optional signal input wiring supports external Fwd and Rev Run command, and a speed potentiometer.
X200 series From 3-phase or single-phase power input source (See specifications label on inverter for details)
R
U
(L1)
(T1)
S
V
(L2)
(T2)
T
W
(N/L3)
(T3)
P24
AL1
1
AL0
Motor
Wiring for Source type models Inputs:
Forward Alarm contacts, 1C
Reverse
2
AL2
3 4 Reset
5 Short bar
Open collector output
L
11
Frequency arrival signal Load
PCS
+ -
Analog reference
H External speed reference POT.
CM2
O
L Analog common
-3-
Logic output common
Page 5
Inverter Keypad Operation Display Units (Hertz / Amperes) LEDs Parameter Display Run key Enable LED
Hz
POWER
A
ALARM
Run key
RUN
STOP RESET
RUN
Stop/Reset key
FUNC
1
2
Power LED Alarm LED Run/Stop LED Potentiometer Enable LED
PRG
Potentiometer STR
Program/Monitor LED
Function key Up/Down keys
Store key
• Run/Stop LED – ON when the inverter output is ON and the motor is developing torque (Run Mode), and OFF when the inverter output is OFF (Stop Mode). • Program/Monitor LED – This LED is ON when the inverter is ready for parameter editing (Program Mode). It is OFF when the parameter display is monitoring data (Monitor Mode). • Run Key Enable LED – is ON when the inverter is ready to respond to the Run key, OFF when the Run key is disabled. • Run Key – Press this key to run the motor (the Run Enable LED must be ON first). Parameter F004, Keypad Run Key Routing, determines whether the Run key generates a Run FWD or Run REV command. • Stop/Reset Key – Press this key to stop the motor when it is running (uses the programmed deceleration rate). This key will also reset an alarm that has tripped. • Potentiometer – Allows an operator to directly set the motor speed when the potentiometer is enabled for output frequency control. • Potentiometer Enable LED – ON when the potentiometer is enabled for value entry. • Parameter Display – A 4-digit, 7-segment display for parameters and function codes. • Display Units, Hertz/Amperes – One of these LEDs will be ON to indicate the units associated with the parameter display. • Power LED – This is ON when the power input to the inverter is ON. • Alarm LED – ON when an inverter trip is active (alarm relay contact will be closed). • Function Key – This key is used to navigate through the lists of parameters and functions for setting and monitoring parameter values. • Up/Down keys – Use these keys alternatively to move up or down the lists of parameter and functions shown in the display, and increment/decrement values. • Store key – When the unit is in Program Mode and you have edited a parameter value, press the Store key to write the new value to the EEPROM. -4-
Page 6
Keypad Navigation Map Monitor Mode PRG LED=OFF
Program Mode PRG LED=ON
Display Data
Select parameter
Edit parameter
Power down
Select Function or Group 1
2
1
2
1
2
Store as powerup default
1
FUNC
1
1
2
1
2 1
1
2
FUNC
1
2
1
2
1
2
1
2
Increment/ decrement value
2
Edit FUNC
1
2
1
2
1
2
1
2
FUNC
STR
2
2
-5-
Write data to EEPROM
Return to parameter list
Page 7
Powerup Test The Powerup Test procedure uses minimal parameter settings to run the motor. The procedure describes two alternative methods for commanding the inverter: via the inverter keypad, or via the logic terminals.
y Check power input and motor output wiring (see page 3 diagram). y If using logic terminals for testing, verify correct wiring on [PCS], [FW], [H], [O] and [L] (bottom row) per the diagram on page 3. y Reverse [RV] input wiring (defaults to terminal [2]) is optional. Step 1 2 3 4
Description Set speed command source setting Set Run FW command source Set Run REV command source Set motor base freq.
5
Set motor poles
6
Set keypad display to monitor freq.
7
Perform safety check
8
Run Forward command
9
Increase speed
10
Decrease speed
11
Stop motor
12
Run Reverse command (optional)
13
Stop motor
Via Keypad
Via Logic Terminals
A001=00 (Keypad pot) A002=02 (Run key)
A001=01 [H-O-L] input A002=01 [FW] input C002=01 (default) − [RV] input A003=60 H004 = 4 (default), change only if your motor is different Access d001, press Func key, display will show 0.0 Disconnect load from motor Turn keypad pot. To MIN Ensure voltage on [O] − position [L] terminals = 0V Turn ON the [FW] Press Run key terminal Rotate keypad pot. CW Increase voltage at [O] direction Rotate keypad pot. CCW Decrease voltage at [O] direction Turn OFF the [FW] Press stop key terminal Turn ON the [RV] − terminal Turn OFF the [RV] − terminal
-6-
Page 8
Error Codes The X200 series inverters will trip on over-current, over-voltage, and under-voltage to protect the inverter. The motor output turns OFF, allowing the motor to free-run to a stop. Press the Stop/Reset key to reset the inverter and clear the error.
Basic Error Codes Error Code
Name
Probable Cause(s)
E_02
Over current event while at constant speed Over current event during deceleration
E_03
Over current event during acceleration
E_04
Over current event for other conditions
E_05
Overload protection
E_07
Over voltage protection
E_08
EEPROM error
E_09
Under voltage error y Inverter output was short-circuited y Motor shaft is locked y Load is too heavy y A dual voltage motor is wired incorrectly Note: The X200 will over-current trip at nominally 200% of the rated current. y DC braking power (A_54) set too high y Current transformer / noise error y Motor overload is detected by the electronic thermal function y DC bus voltage exceeds a threshold, due to regeneration energy from the motor y Built-in EEPROM memory experienced noise, high temperature, etc. y DC bus voltage decreased enough to cause a control circuit fault y Instantaneous power failure occurred
E_11
CPU error y Built-in CPU had internal error
E_12
External trip y [EXT] input signal detected
E_13
USP (Unattended Start Protection)
E_14
Ground fault
E_15
Input over-voltage
E_21
Inverter thermal trip
E_30
Driver error
Refer to E_01~E_04
E_35
Thermistor y Thermistor input, [5] and [L] is over the temperature threshold
E_37
Emergency stop y Emergency stop signal has given
E_60
Communications error
---
Under-voltage (brownout) with output shutoff
E_01 y When (USP) was enabled, an error occurred when power was applied while a Run signal was present y A ground fault was detected between the inverter output and the motor. This feature protects the inverter, and does not protect humans. y Input voltage was higher than the specified value, 100 sec. after powerup y Inverter internal temperature is above the threshold y Communication error on RS485 MODBUS communication y Low input voltage caused the inverter to turn OFF the motor output and try to restart. If unsuccessful, a trip occurs.
-7-
Page 9
Error Trip Conditions Use function code d081 to access the error trip conditions for the current error as shown in the table below. Use the Up and Down arrow keys to scroll through the trip condition parameters. Step
Display
1. Access d081 d081
2. Press Function Key
If no error:
___ If error exists:
E_xx 3. Press Up/Dn key (if error exists)
(error code) Output frequency at trip point:
48.50 Motor current at trip point:
10.3 1
DC bus voltage at trip point:
189.5 2
Cumulative Run hours at trip point:
15 Cumulative power-ON hours at trip point:
18
-8-