For the Hitachi X200 Series

Page 1

X200 Series Inverter Quick Reference Guide • • •

Single-phase Input 200V class Three-phase Input 200V class Three-phase Input 400V class

Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NT3011XB • Sep 2007

Page 2

!

Caution: Be sure to read the X200 Manual and the X200 Manual Addendum, and follow their Cautions and Warnings for the initial product installation. This Quick Reference Guide is intended for reference use by experienced users in servicing existing installations.

Power Circuit Terminals Inverter models X200-002SFEF/NFU, -004SFEF/NFU

SFEF

L1

/

NFU

L1

L2 L3/N

N Jumper

Jumper Jumper -

+

+1

U/T1 V/T2 W/T3

Inverter models X200-005SFEF, -007SFEF/NFU to -022SFEF/NFU, -037LFU to -075LFU, 004HFEF/HFU to –075HFEF/HFU

SFEF

L1

/

NFU,LFU

L1

L2 L3/N

HFEF,HFU

R/L1 S/L2 T/L3

N Jumper Jumper

Jumper Jumper U/T1 V/T2 W/T3

!

-

+

+1

Caution: Power terminal assignment is is different compared to old models such as L100, L200 series. Pay attention when wiring the power cable.

-1-

Page 3

Control Circuit Terminals

Alarm relay AL2 AL1 AL0 Analog output AM

Analog inputs H

O

OI

Logic outputs

Logic inputs L

5

4

3

2

1

L PCS P24 CM2 11 Jumper

Terminal Name P24

Description +24V for logic inputs

Ratings and Notes 24VDC supply, 30mA max. (Notes: Do not use for network power. Do not short to terminal L) 1, 2, 3, 4, 5 Intelligent (programmable 27VDC max. (Use P24 or an discrete logic) inputs external supply reference to terminal L), 4.7kΩ input impedance. 11 Discrete logic output 50mA max. ON current, 27VDC max. OFF voltage L (right) GND for logic inputs Sum of input 1 to 5 currents (Note: Do not ground) CM2 Common for logic 50mA max for terminal 11 outputs current AM Analog voltage output 0 to 10VDC, 1mA max. L (left) Common for analog Sum of OI, O and H currents inputs (return) OI Analog input, current 4 to 19.6mA range, 20mA nom. O Analog input, voltage 0 to 9.6VDC range, 10VDC nominal, 12VDC max., input impedance 10kΩ H +10V analog reference 10VDC nominal, 10mA max. AL0 Relay common contact Contact rating AL1 Relay contact, normally Max resistive load=250VAC, 2.5A; 30VDC 3A; closed during RUN AL2 Relay contact, normally Max inductive load=250VAC, 0.2A; 30VDC 0.7A open during RUN Minimum load=5VDC 100mA, 100VAC 10mA Note) Analog input O and OI cannot be used at the same time.

-2-

Page 4

Basic Wiring Diagram The following wiring diagram shows the power and motor connections for basic operation. The optional signal input wiring supports external Fwd and Rev Run command, and a speed potentiometer.

X200 series From 3-phase or single-phase power input source (See specifications label on inverter for details)

R

U

(L1)

(T1)

S

V

(L2)

(T2)

T

W

(N/L3)

(T3)

P24

AL1

1

AL0

Motor

Wiring for Source type models Inputs:

Forward Alarm contacts, 1C

Reverse

2

AL2

3 4 Reset

5 Short bar

Open collector output

L

11

Frequency arrival signal Load

PCS

+ -

Analog reference

H External speed reference POT.

CM2

O

L Analog common

-3-

Logic output common

Page 5

Inverter Keypad Operation Display Units (Hertz / Amperes) LEDs Parameter Display Run key Enable LED

Hz

POWER

A

ALARM

Run key

RUN

STOP RESET

RUN

Stop/Reset key

FUNC

1

2

Power LED Alarm LED Run/Stop LED Potentiometer Enable LED

PRG

Potentiometer STR

Program/Monitor LED

Function key Up/Down keys

Store key

• Run/Stop LED – ON when the inverter output is ON and the motor is developing torque (Run Mode), and OFF when the inverter output is OFF (Stop Mode). • Program/Monitor LED – This LED is ON when the inverter is ready for parameter editing (Program Mode). It is OFF when the parameter display is monitoring data (Monitor Mode). • Run Key Enable LED – is ON when the inverter is ready to respond to the Run key, OFF when the Run key is disabled. • Run Key – Press this key to run the motor (the Run Enable LED must be ON first). Parameter F004, Keypad Run Key Routing, determines whether the Run key generates a Run FWD or Run REV command. • Stop/Reset Key – Press this key to stop the motor when it is running (uses the programmed deceleration rate). This key will also reset an alarm that has tripped. • Potentiometer – Allows an operator to directly set the motor speed when the potentiometer is enabled for output frequency control. • Potentiometer Enable LED – ON when the potentiometer is enabled for value entry. • Parameter Display – A 4-digit, 7-segment display for parameters and function codes. • Display Units, Hertz/Amperes – One of these LEDs will be ON to indicate the units associated with the parameter display. • Power LED – This is ON when the power input to the inverter is ON. • Alarm LED – ON when an inverter trip is active (alarm relay contact will be closed). • Function Key – This key is used to navigate through the lists of parameters and functions for setting and monitoring parameter values. • Up/Down keys – Use these keys alternatively to move up or down the lists of parameter and functions shown in the display, and increment/decrement values. • Store key – When the unit is in Program Mode and you have edited a parameter value, press the Store key to write the new value to the EEPROM. -4-

Page 6

Keypad Navigation Map Monitor Mode PRG LED=OFF

Program Mode PRG LED=ON

Display Data

Select parameter

Edit parameter

Power down

Select Function or Group 1

2

1

2

1

2

Store as powerup default

1

FUNC

1

1

2

1

2 1

1

2

FUNC

1

2

1

2

1

2

1

2

Increment/ decrement value

2

Edit FUNC

1

2

1

2

1

2

1

2

FUNC

STR

2

2

-5-

Write data to EEPROM

Return to parameter list

Page 7

Powerup Test The Powerup Test procedure uses minimal parameter settings to run the motor. The procedure describes two alternative methods for commanding the inverter: via the inverter keypad, or via the logic terminals.

y Check power input and motor output wiring (see page 3 diagram). y If using logic terminals for testing, verify correct wiring on [PCS], [FW], [H], [O] and [L] (bottom row) per the diagram on page 3. y Reverse [RV] input wiring (defaults to terminal [2]) is optional. Step 1 2 3 4

Description Set speed command source setting Set Run FW command source Set Run REV command source Set motor base freq.

5

Set motor poles

6

Set keypad display to monitor freq.

7

Perform safety check

8

Run Forward command

9

Increase speed

10

Decrease speed

11

Stop motor

12

Run Reverse command (optional)

13

Stop motor

Via Keypad

Via Logic Terminals

A001=00 (Keypad pot) A002=02 (Run key)

A001=01 [H-O-L] input A002=01 [FW] input C002=01 (default) − [RV] input A003=60 H004 = 4 (default), change only if your motor is different Access d001, press Func key, display will show 0.0 Disconnect load from motor Turn keypad pot. To MIN Ensure voltage on [O] − position [L] terminals = 0V Turn ON the [FW] Press Run key terminal Rotate keypad pot. CW Increase voltage at [O] direction Rotate keypad pot. CCW Decrease voltage at [O] direction Turn OFF the [FW] Press stop key terminal Turn ON the [RV] − terminal Turn OFF the [RV] − terminal

-6-

Page 8

Error Codes The X200 series inverters will trip on over-current, over-voltage, and under-voltage to protect the inverter. The motor output turns OFF, allowing the motor to free-run to a stop. Press the Stop/Reset key to reset the inverter and clear the error.

Basic Error Codes Error Code

Name

Probable Cause(s)

E_02

Over current event while at constant speed Over current event during deceleration

E_03

Over current event during acceleration

E_04

Over current event for other conditions

E_05

Overload protection

E_07

Over voltage protection

E_08

EEPROM error

E_09

Under voltage error y Inverter output was short-circuited y Motor shaft is locked y Load is too heavy y A dual voltage motor is wired incorrectly Note: The X200 will over-current trip at nominally 200% of the rated current. y DC braking power (A_54) set too high y Current transformer / noise error y Motor overload is detected by the electronic thermal function y DC bus voltage exceeds a threshold, due to regeneration energy from the motor y Built-in EEPROM memory experienced noise, high temperature, etc. y DC bus voltage decreased enough to cause a control circuit fault y Instantaneous power failure occurred

E_11

CPU error y Built-in CPU had internal error

E_12

External trip y [EXT] input signal detected

E_13

USP (Unattended Start Protection)

E_14

Ground fault

E_15

Input over-voltage

E_21

Inverter thermal trip

E_30

Driver error

Refer to E_01~E_04

E_35

Thermistor y Thermistor input, [5] and [L] is over the temperature threshold

E_37

Emergency stop y Emergency stop signal has given

E_60

Communications error

---

Under-voltage (brownout) with output shutoff

E_01 y When (USP) was enabled, an error occurred when power was applied while a Run signal was present y A ground fault was detected between the inverter output and the motor. This feature protects the inverter, and does not protect humans. y Input voltage was higher than the specified value, 100 sec. after powerup y Inverter internal temperature is above the threshold y Communication error on RS485 MODBUS communication y Low input voltage caused the inverter to turn OFF the motor output and try to restart. If unsuccessful, a trip occurs.

-7-

Page 9

Error Trip Conditions Use function code d081 to access the error trip conditions for the current error as shown in the table below. Use the Up and Down arrow keys to scroll through the trip condition parameters. Step

Display

1. Access d081 d081

2. Press Function Key

If no error:

___ If error exists:

E_xx 3. Press Up/Dn key (if error exists)

(error code) Output frequency at trip point:

48.50 Motor current at trip point:

10.3 1

DC bus voltage at trip point:

189.5 2

Cumulative Run hours at trip point:

15 Cumulative power-ON hours at trip point:

18

-8-