The text of a manual · part 2 of 3
X200 Series Inverter Quick Reference Guide, pages 10 to 18
Pages 10 to 18 of 25
The original document is the PDF (623 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Hitachi X200 Series
Page 10
Restoring Factory Default Settings Action Press FUNC , needed Press
1 or
Display 2 as
FUNC
Press/hold
1 until…
Press FUNC . If setting is correct, then skip next step. To change country code, press
1
Function/Parameter b- - -
“B” Group selected b001
First “B” Group parameter b085
Country code for initialization selected
02
00 = Japan 01 = Europe 02 = United States or
2 to set;
STR to store.
Press
FUNC b085
Country code for initialization selected
Press
2 b084
Initialization function selected
Press
FUNC
00
00 = disable initialization
Press
1
01
01 = enable initialization
Press
STR b084
Initialization now enable to restore all defaults b084
First part of key sequence all the keys.
EU USA JP
Default parameter country code shown during initialization
Initialization is complete.
d001
Function code for output frequency monitor shown
Press/hold FUNC ,
2 and
STOP RESET keys. Do not release yet. When your country code appears in the display, release
Note: After initializing the inverter, use the Powerup Test on page 6 to get the motor running again.
-9-
Page 11
Parameter Tables “D” group: Monitoring Functions Func. Code
Name / Description
Units
D001 Output frequency monitor D002 Output current monitor D003 Rotation direction monitor
Forward
Hz A −
Stop
Reverse
Direction
D004 Process variable (PV), PID feedback monitor
%
Intelligent input terminal status
−
D005
ON OFF 5
4
3
2
1
Terminal Numbers
D006 Intelligent output terminal status
− ON OFF
AL
11
Terminal Numbers Scaled output frequency monitor
D007 (output frequency ∗ b086 scale factor)
Userdefined
D013 Output voltage monitor
V
D016 Cumulative operation RUN time monitor hr
D017 Cumulative power-ON time monitor hr
D018 Cooling fin temperature monitor
°C
D080 Trip counter
−
D081
Trip monitor 1 (most recent trip n)
−
D082
Trip monitor 2 (trip n-1)
−
D083
Trip monitor 3 (trip n-2)
−
D102 DC bus voltage monitor
V
D104 Electronic thermal monitor
%
- 10 -
Page 12
Trip History and Inverter Status No error Monitor Mode
Error exists?
Display data
No
Yes FUNC FUNC 2 1
2
1
2
Error code
1
2
Output frequency at trip point FUNC 1
1
2
Motor current at trip point
2
1
2
DC bus voltage at trip point 1
2
Cumulative inverter operation time at trip point 1
2
Cumulative power-ON time at trip point 1
- 11 -
Page 13
Parameter tables for user-settable functions follow these conventions: y Some parameters have 2nd motor equivalents, indicated by the x2xx parameter codes in the left-most column. y Some parameters specify an option code. Where applicable, the option codes will be in a bulleted list in the Name/Description column. y The default values apply to all models unless otherwise noted for each parameter… -FE (Europe) / -FU (U.S.) / -FR (Japan). y Some parameters cannot be edited during Run Mode, and certain Software Lock settings (b031) can prohibit all edits. If in doubt, place the inverter in Stop Mode or Consult the inverter manual for details.
“F” group: Main Profile Parameters Func. Code
F001 F002 F202 F003 F203 F004
Name / Description
Output frequency setting Acceleration (1) time setting Acceleration (1) time setting <2nd motor> Deceleration (1) time setting Deceleration (1) time setting <2nd motor> Keypad Run key routing y 00 Forward y 01 Reverse
- 12 -
Default value -FE/FU
0.0 10.0 10.0 10.0 10.0 00
Set value
Page 14
“A” group: Standard Functions Func. Code A001/ A201
A002/ A202 A003/ A203 A004/ A204 A005
A011 A012 A013 A014 A015 A016 A020/ A220 A021~ A035 A038 A039
A041/ A241 A042/ A242 A043/ A243 A044/ A244
Default -FE/-FU 01/00
Name / Description Frequency source setting y 00 Keypad potentiometer y 01 Control terminal y 02 Function F_01 setting y 03 RS485 Modbus communication y 10 Calculate function output Run command source setting y 01 Input terminal FW or RV (assignable) y 02 RUN key on the keypad y 03 RS485 Modbus communication Base frequency setting
01/00
50/60
Maximum frequency setting
50/60
[AT] selection y 02 Select [O] or POT by [AT] terminal input y 03 Select [OI] or POT by [AT] terminal input y 04 [O] input only y 05 [OI] input ony A005 02 03 04 AT input OFF ON OFF ON OFF ON Active [O] POT [OI] POT [O]
02
Not assigned [AT] is the same as [AT]=OFF. O-L input active range start frequency O-L input active range end frequency O-L input active range start voltage O-L input active range end voltage O-L input start frequency enable y 00 Use A011 (starting value) y 01 Use 0Hz External frequency filter time constant Multi-speed frequency setting Multi-speed frequency settings (for both motors) Jog frequency setting Jog stop mode y 00 Free-run stop, jogging disabled during motor run y 01 Controlled deceleration, jogging disabled during motor run y 02 DC braking to stop, jogging disabled during motor run Torque boost method selection y 00 Manual torque boost y 01 Automatic torque boost Manual torque boost value Manual torque boost frequency adjustment V/f characteristic curve selection y 00 V/f constant torque y 01 V/f variable torque y 06 V/f variable torque1
- 13 -
Set value
05 OFF ON [OI] 0.0 0.0 0. 100. 01 8. 0.0 0.0 1.0 00
00 1.8(A042)/ 0.0(A242) 10.0(A043)/ 0.0(A243) 00
Page 15
Func. Code A045/ A245 A051 A052 A053 A054 A055 A056 A061/ A261 A062/ A262 A063 A065 A067 A064 A066 A068 A071 A072 A073 A074 A075 A076
A077 A078 A081 A082 A085 A086 A092/ A292 A093/ A093 A094/ A294 A095/ A295 A096/
Name / Description V/f gain setting
Default -FE/-FU 100.
DC braking enable y 00 Disable y 01 Enable y 02 Freq.detection DC braking frequency setting DC braking wait time DC braking force during deceleration DC braking time for deceleration DC braking / edge or level detection for [DB] input y 00 Edge y 01 Level Frequency high limit setting
0.5 0.0 0. 0.0 01
Frequency low limit setting
0.0
Jump (center) frequency setting
0.0
Jump (hysteresis) frequency width setting
0.5
PID enable y 00 PID operation OFF y 01 PID operation ON PID proportional gain PID integral time constant PID derivative time constant PV scale conversion PV source setting y 00 [OI] terminal (current input) y 01 [O] terminal (voltage input) y 02 ModBus network y 03 Calculate function output Reverse PID action y 00 PID input = SP-PV y 01 PID input = -(SP-PV) PID output limit AVR function select y 00 AVR enabled y 01 AVR disabled y 02 AVR enabled except during decel. AVR voltage select
00
Operation mode selection y 00 Normal operation y 01 Energy-saver operation Energy saving mode tuning Acceleration (2) time setting
00
0.0
1.0 1.0 0.00 1.00 00
00 0.0 00 230,400/ 230,460 00 50.0 15.0
Deceleration (2) time setting
15.0
Select method to switch to Acc2/Dec2 profile y 00 2CH input from terminal y 01 transition frequency Acc1 to Acc2 frequency transition point
00 0.0
Dec1 to Dec2 frequency transition point
0.0
- 14 -
Set value
Page 16
Func. Code A296 A097 A098 A101 A102 A103 A104 A105 A141
A142
A143
A145 A146 A151 A152 A153 A154 A155
Name / Description Acceleration curve selection y 00 Linear y 01 S-curve Deceleration curve selection y 00 Linear y 01 S-curve [OI]-[L] input active range start frequency [OI]-[L] input active range end frequency [OI]-[L] input active range start current [OI]-[L] input active range end current [OI]-[L] input start frequency enable y 00 Use A101 (starting value) y 01 Use 0Hz Input A select for calculate function y 00 Integrated operator y 01 Keypad POT y 02 [O] input y 03 [OI] input y 04 Network variable Input A select for calculate function y 00 Integrated operator y 01 Keypad POT y 02 [O] input y 03 [OI] input y 04 Network variable Calculation symbol y 00 ADD (A + B) y 01 SUB (A - B) y 02 MUL (A * B) ADD frequency ADD direction select y 00 Plus (adds A145 value to output freq.) y 01 Minus (subtracts A145 value from output freq.) POT active range start frequency POT input active range end frequency POT input active range start POT input active range end POT input start frequency enable
- 15 -
Default -FE/-FU 00 00 0.0 0.0 0. 100. 01 01
02
00
0.0 00 0.0 0.0 0. 100. 01
Set value
Page 17
“B” group: Fine-tuning Functions Func. Code B001
B002 B003 B004 B005 B011
B012/ B212 B013/ B213 B021/ B221 B022/ B222 B023/ B223 B028/ B228 B029 B030 B031
B050 B051 B052 B053 B054 B055 B056 B080 B082
Name / Description Selection of automatic restart mode y 00 Alarm output after trip, automatic restart disable y 01 Restart at 0Hz y 02 Resume operation after frequency pull-in y 03 Resume previous freq. after freq. pull-in, then decelerate to stop and display trip info Allowable under-voltage power failure time Retry wait time before motor restart Instantaneous power failure / under-voltage trip alarm enable y 00 Disable y 01 Enable Number of restarts on power failure / under-voltage trip event y 00 Restarts 16 times y 01 Always restart Start freq to be used in case of freq pull-in restart y 00 Freq at previous shutoff y 01 Start from max. Hz y 02 Start from set freq Level of electronic thermal setting Electronic thermal characteristics y 00 Reduced torque y 01 Const. torque Overload restriction operation mode y 00 Disabled y 01 Enabled for accel and constant speed y 02 Enabled for constant speed only Overload restriction level setting Deceleration rate at overload restriction Source of restriction selection y 00 set value of B022 y 01 [O] input Deceleration rate of freq pull-in restart setting Current level of freq pill-in restart setting Software lock mode selection y 00 Low-level access, [SFT] blocks edits y 01 Low-level access, [SFT] blocks edits (except F001 and Multi-speed parameters) y 02 No access to edits y 03 No access to edits (except F001 and Multi-speed parameters) y 10 High level access Selection of the non stop operation y 00 Disable y 01 Enable(stop) y 02 Enable(restart) Non stop operation start voltage setting OV-LAD Stop level of non stop operation setting Deceleration time of non stop operation setting Frequency width of quick deceleration setting DC bus AVR P-gain DC bus AVR I-time [AM] analog signal gain Start frequency adjustment - 16 -
Default -FE/FU 00
1.0 1.0 00 00 00
INV Rated current 01 01
INV Rated current x 1.5 1.0/30.0 00 0.5 INV Rated current 01
00 0.0 0.0 1.0 0.0 0.2 0.2 100. 0.5
Set value
Page 18
Func. Code B083 B084
B085 B086 B087 B088 B089
B091 B092
B130 B131 B133 B134 B140 B150 B151
Name / Description Carrier frequency setting Initialization mode (parameter or trip history) y 00 Trip history clear y 01 Parameter initialization y 02 Trip history clear and parameter initialization Country code for initialization y 00 Japan version y 01 Europe version y 02 US version Frequency scaling conversion factor STOP key enable y 00 Enable y 01 Disable Restart mode after FRS y 00 Restart from 0Hz y 01 Restart with frequency pull-in Data select for digital operator OPE-J y 01 Output frequency (d001) y 02 Output current (d002) y 03 Motor direction (d003) y 04 PID PV feedback (d004) y 05 Input status for input terminals (d005) y 06 Output status for output terminals (d006) y 07 Scaled output frequency (d007) Stop mode selection y 00 DEC (decelerates and stop) y 01 FRS (free-run to stop) Cooling fan control y 00 Fan is always ON y 01 Fan is ON during run, OFF during stop (5 minutes delay from ON to OFF) y 02 Fan is temperature controlled Over-voltage LADSTOP enable y 00 Disable y 01 Enable Over-voltage LADSTOP level DC bus AVR selection y 00 Disable y 01 Enable Threshold voltage of DC bus AVR setting Over-current trip suppression y 00 Disable y 01 Enable Automatic carrier control y 00 Disable y 01 Enable Selection of RDY function
- 17 -
Default -FE/FU 3.0 00
01/02 1.0 00 00 01
00 00
00 380,760 00 380,760 00 00 00
Set value