The text of a manual · part 2 of 3

X200 Series Inverter Quick Reference Guide, pages 10 to 18

Pages 10 to 18 of 25

The original document is the PDF (623 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 10

Restoring Factory Default Settings Action Press FUNC , needed Press

1 or

Display 2 as

FUNC

Press/hold

1 until…

Press FUNC . If setting is correct, then skip next step. To change country code, press

1

Function/Parameter b- - -

“B” Group selected b001

First “B” Group parameter b085

Country code for initialization selected

02

00 = Japan 01 = Europe 02 = United States or

2 to set;

STR to store.

Press

FUNC b085

Country code for initialization selected

Press

2 b084

Initialization function selected

Press

FUNC

00

00 = disable initialization

Press

1

01

01 = enable initialization

Press

STR b084

Initialization now enable to restore all defaults b084

First part of key sequence all the keys.

EU USA JP

Default parameter country code shown during initialization

Initialization is complete.

d001

Function code for output frequency monitor shown

Press/hold FUNC ,

2 and

STOP RESET keys. Do not release yet. When your country code appears in the display, release

Note: After initializing the inverter, use the Powerup Test on page 6 to get the motor running again.

-9-

Page 11

Parameter Tables “D” group: Monitoring Functions Func. Code

Name / Description

Units

D001 Output frequency monitor D002 Output current monitor D003 Rotation direction monitor

Forward

Hz A −

Stop

Reverse

Direction

D004 Process variable (PV), PID feedback monitor

%

Intelligent input terminal status

−

D005

ON OFF 5

4

3

2

1

Terminal Numbers

D006 Intelligent output terminal status

− ON OFF

AL

11

Terminal Numbers Scaled output frequency monitor

D007 (output frequency ∗ b086 scale factor)

Userdefined

D013 Output voltage monitor

V

D016 Cumulative operation RUN time monitor hr

D017 Cumulative power-ON time monitor hr

D018 Cooling fin temperature monitor

°C

D080 Trip counter

−

D081

Trip monitor 1 (most recent trip n)

−

D082

Trip monitor 2 (trip n-1)

−

D083

Trip monitor 3 (trip n-2)

−

D102 DC bus voltage monitor

V

D104 Electronic thermal monitor

%

- 10 -

Page 12

Trip History and Inverter Status No error Monitor Mode

Error exists?

Display data

No

Yes FUNC FUNC 2 1

2

1

2

Error code

1

2

Output frequency at trip point FUNC 1

1

2

Motor current at trip point

2

1

2

DC bus voltage at trip point 1

2

Cumulative inverter operation time at trip point 1

2

Cumulative power-ON time at trip point 1

- 11 -

Page 13

Parameter tables for user-settable functions follow these conventions: y Some parameters have 2nd motor equivalents, indicated by the x2xx parameter codes in the left-most column. y Some parameters specify an option code. Where applicable, the option codes will be in a bulleted list in the Name/Description column. y The default values apply to all models unless otherwise noted for each parameter… -FE (Europe) / -FU (U.S.) / -FR (Japan). y Some parameters cannot be edited during Run Mode, and certain Software Lock settings (b031) can prohibit all edits. If in doubt, place the inverter in Stop Mode or Consult the inverter manual for details.

“F” group: Main Profile Parameters Func. Code

F001 F002 F202 F003 F203 F004

Name / Description

Output frequency setting Acceleration (1) time setting Acceleration (1) time setting <2nd motor> Deceleration (1) time setting Deceleration (1) time setting <2nd motor> Keypad Run key routing y 00 Forward y 01 Reverse

- 12 -

Default value -FE/FU

0.0 10.0 10.0 10.0 10.0 00

Set value

Page 14

“A” group: Standard Functions Func. Code A001/ A201

A002/ A202 A003/ A203 A004/ A204 A005

A011 A012 A013 A014 A015 A016 A020/ A220 A021~ A035 A038 A039

A041/ A241 A042/ A242 A043/ A243 A044/ A244

Default -FE/-FU 01/00

Name / Description Frequency source setting y 00 Keypad potentiometer y 01 Control terminal y 02 Function F_01 setting y 03 RS485 Modbus communication y 10 Calculate function output Run command source setting y 01 Input terminal FW or RV (assignable) y 02 RUN key on the keypad y 03 RS485 Modbus communication Base frequency setting

01/00

50/60

Maximum frequency setting

50/60

[AT] selection y 02 Select [O] or POT by [AT] terminal input y 03 Select [OI] or POT by [AT] terminal input y 04 [O] input only y 05 [OI] input ony A005 02 03 04 AT input OFF ON OFF ON OFF ON Active [O] POT [OI] POT [O]

02

Not assigned [AT] is the same as [AT]=OFF. O-L input active range start frequency O-L input active range end frequency O-L input active range start voltage O-L input active range end voltage O-L input start frequency enable y 00 Use A011 (starting value) y 01 Use 0Hz External frequency filter time constant Multi-speed frequency setting Multi-speed frequency settings (for both motors) Jog frequency setting Jog stop mode y 00 Free-run stop, jogging disabled during motor run y 01 Controlled deceleration, jogging disabled during motor run y 02 DC braking to stop, jogging disabled during motor run Torque boost method selection y 00 Manual torque boost y 01 Automatic torque boost Manual torque boost value Manual torque boost frequency adjustment V/f characteristic curve selection y 00 V/f constant torque y 01 V/f variable torque y 06 V/f variable torque1

- 13 -

Set value

05 OFF ON [OI] 0.0 0.0 0. 100. 01 8. 0.0 0.0 1.0 00

00 1.8(A042)/ 0.0(A242) 10.0(A043)/ 0.0(A243) 00

Page 15

Func. Code A045/ A245 A051 A052 A053 A054 A055 A056 A061/ A261 A062/ A262 A063 A065 A067 A064 A066 A068 A071 A072 A073 A074 A075 A076

A077 A078 A081 A082 A085 A086 A092/ A292 A093/ A093 A094/ A294 A095/ A295 A096/

Name / Description V/f gain setting

Default -FE/-FU 100.

DC braking enable y 00 Disable y 01 Enable y 02 Freq.detection DC braking frequency setting DC braking wait time DC braking force during deceleration DC braking time for deceleration DC braking / edge or level detection for [DB] input y 00 Edge y 01 Level Frequency high limit setting

0.5 0.0 0. 0.0 01

Frequency low limit setting

0.0

Jump (center) frequency setting

0.0

Jump (hysteresis) frequency width setting

0.5

PID enable y 00 PID operation OFF y 01 PID operation ON PID proportional gain PID integral time constant PID derivative time constant PV scale conversion PV source setting y 00 [OI] terminal (current input) y 01 [O] terminal (voltage input) y 02 ModBus network y 03 Calculate function output Reverse PID action y 00 PID input = SP-PV y 01 PID input = -(SP-PV) PID output limit AVR function select y 00 AVR enabled y 01 AVR disabled y 02 AVR enabled except during decel. AVR voltage select

00

Operation mode selection y 00 Normal operation y 01 Energy-saver operation Energy saving mode tuning Acceleration (2) time setting

00

0.0

1.0 1.0 0.00 1.00 00

00 0.0 00 230,400/ 230,460 00 50.0 15.0

Deceleration (2) time setting

15.0

Select method to switch to Acc2/Dec2 profile y 00 2CH input from terminal y 01 transition frequency Acc1 to Acc2 frequency transition point

00 0.0

Dec1 to Dec2 frequency transition point

0.0

- 14 -

Set value

Page 16

Func. Code A296 A097 A098 A101 A102 A103 A104 A105 A141

A142

A143

A145 A146 A151 A152 A153 A154 A155

Name / Description Acceleration curve selection y 00 Linear y 01 S-curve Deceleration curve selection y 00 Linear y 01 S-curve [OI]-[L] input active range start frequency [OI]-[L] input active range end frequency [OI]-[L] input active range start current [OI]-[L] input active range end current [OI]-[L] input start frequency enable y 00 Use A101 (starting value) y 01 Use 0Hz Input A select for calculate function y 00 Integrated operator y 01 Keypad POT y 02 [O] input y 03 [OI] input y 04 Network variable Input A select for calculate function y 00 Integrated operator y 01 Keypad POT y 02 [O] input y 03 [OI] input y 04 Network variable Calculation symbol y 00 ADD (A + B) y 01 SUB (A - B) y 02 MUL (A * B) ADD frequency ADD direction select y 00 Plus (adds A145 value to output freq.) y 01 Minus (subtracts A145 value from output freq.) POT active range start frequency POT input active range end frequency POT input active range start POT input active range end POT input start frequency enable

- 15 -

Default -FE/-FU 00 00 0.0 0.0 0. 100. 01 01

02

00

0.0 00 0.0 0.0 0. 100. 01

Set value

Page 17

“B” group: Fine-tuning Functions Func. Code B001

B002 B003 B004 B005 B011

B012/ B212 B013/ B213 B021/ B221 B022/ B222 B023/ B223 B028/ B228 B029 B030 B031

B050 B051 B052 B053 B054 B055 B056 B080 B082

Name / Description Selection of automatic restart mode y 00 Alarm output after trip, automatic restart disable y 01 Restart at 0Hz y 02 Resume operation after frequency pull-in y 03 Resume previous freq. after freq. pull-in, then decelerate to stop and display trip info Allowable under-voltage power failure time Retry wait time before motor restart Instantaneous power failure / under-voltage trip alarm enable y 00 Disable y 01 Enable Number of restarts on power failure / under-voltage trip event y 00 Restarts 16 times y 01 Always restart Start freq to be used in case of freq pull-in restart y 00 Freq at previous shutoff y 01 Start from max. Hz y 02 Start from set freq Level of electronic thermal setting Electronic thermal characteristics y 00 Reduced torque y 01 Const. torque Overload restriction operation mode y 00 Disabled y 01 Enabled for accel and constant speed y 02 Enabled for constant speed only Overload restriction level setting Deceleration rate at overload restriction Source of restriction selection y 00 set value of B022 y 01 [O] input Deceleration rate of freq pull-in restart setting Current level of freq pill-in restart setting Software lock mode selection y 00 Low-level access, [SFT] blocks edits y 01 Low-level access, [SFT] blocks edits (except F001 and Multi-speed parameters) y 02 No access to edits y 03 No access to edits (except F001 and Multi-speed parameters) y 10 High level access Selection of the non stop operation y 00 Disable y 01 Enable(stop) y 02 Enable(restart) Non stop operation start voltage setting OV-LAD Stop level of non stop operation setting Deceleration time of non stop operation setting Frequency width of quick deceleration setting DC bus AVR P-gain DC bus AVR I-time [AM] analog signal gain Start frequency adjustment - 16 -

Default -FE/FU 00

1.0 1.0 00 00 00

INV Rated current 01 01

INV Rated current x 1.5 1.0/30.0 00 0.5 INV Rated current 01

00 0.0 0.0 1.0 0.0 0.2 0.2 100. 0.5

Set value

Page 18

Func. Code B083 B084

B085 B086 B087 B088 B089

B091 B092

B130 B131 B133 B134 B140 B150 B151

Name / Description Carrier frequency setting Initialization mode (parameter or trip history) y 00 Trip history clear y 01 Parameter initialization y 02 Trip history clear and parameter initialization Country code for initialization y 00 Japan version y 01 Europe version y 02 US version Frequency scaling conversion factor STOP key enable y 00 Enable y 01 Disable Restart mode after FRS y 00 Restart from 0Hz y 01 Restart with frequency pull-in Data select for digital operator OPE-J y 01 Output frequency (d001) y 02 Output current (d002) y 03 Motor direction (d003) y 04 PID PV feedback (d004) y 05 Input status for input terminals (d005) y 06 Output status for output terminals (d006) y 07 Scaled output frequency (d007) Stop mode selection y 00 DEC (decelerates and stop) y 01 FRS (free-run to stop) Cooling fan control y 00 Fan is always ON y 01 Fan is ON during run, OFF during stop (5 minutes delay from ON to OFF) y 02 Fan is temperature controlled Over-voltage LADSTOP enable y 00 Disable y 01 Enable Over-voltage LADSTOP level DC bus AVR selection y 00 Disable y 01 Enable Threshold voltage of DC bus AVR setting Over-current trip suppression y 00 Disable y 01 Enable Automatic carrier control y 00 Disable y 01 Enable Selection of RDY function

- 17 -

Default -FE/FU 3.0 00

01/02 1.0 00 00 01

00 00

00 380,760 00 380,760 00 00 00

Set value