Manual · Hitachi
X200 Series Inverter Quick Reference Guide
Manual25 pagesPDF 623 KB
Quick reference guide for Hitachi X200 Series inverters: terminals, basic wiring, keypad, powerup test, error codes and parameters.
Covers · 1 model
The models it covers
Summary
What is in it
Hitachi's quick reference guide for X200 Series inverters (single-phase 200V class, three-phase 200V and 400V class), meant for experienced users servicing existing installations. It shows power and control circuit terminals with ratings, a basic wiring diagram, keypad operation and navigation, a step-by-step powerup test, error codes with probable causes, how to read trip conditions, restoring factory defaults, and parameter tables.
From the manual
Key facts from this manual
Each line names its page in the PDF.
Quick reference guide NT3011XB (September 2007) for the Hitachi X200 series inverters in the single-phase 200V, three-phase 200V and three-phase 400V classes. It gives the power and control terminals, keypad use, a powerup test, error codes, factory reset, parameter tables and UL wiring data. It is written for experienced users servicing existing installations.
- Motor output
- 0.2 kW (1/4 HP) to 7.5 kW (10 HP) p. 24
- Logic inputs
- Five programmable inputs [1] to [5], 27VDC max, 4.7kΩ input impedance p. 3
- Logic output
- Terminal [11]: 50mA max ON current, 27VDC max OFF voltage p. 3
- Analog inputs
- O: 0 to 9.6VDC (10VDC nominal, 10kΩ); OI: 4 to 19.6mA (20mA nominal); not both at once p. 3
- Analog output
- AM: 0 to 10VDC, 1mA max, motor speed or motor current p. 3, 19
- Alarm relay
- AL0/AL1/AL2; resistive 250VAC 2.5A or 30VDC 3A; inductive 250VAC 0.2A or 30VDC 0.7A p. 3
- Logic supply
- P24: 24VDC, 30mA max, not for network power p. 3
- Network
- RS485 Modbus at 4800, 9600 or 19200 bps p. 8, 19
- Keypad
- 4-digit 7-segment display, speed potentiometer, Run, Stop/Reset, Function, Up/Down and Store keys p. 5
- Fault codes
- E_05 overload, E_07 over voltage, E_08 EEPROM error, E_09 under voltage, E_11 CPU error, E_12 external trip, E_14 ground fault, E_21 inverter thermal trip, E_35 thermistor, E_60 communications error p. 8
- Over-current trip
- Nominally 200% of rated current p. 8
- Trip monitor
- d081 shows the error with output frequency, motor current, DC bus voltage, run hours and power-on hours at the trip p. 9
- Ambient limit
- Maximum surrounding air temperature 50°C p. 23
What this manual walks you through
- Identifying the power circuit terminals p. 2
- Control terminal names and ratings p. 3
- Basic wiring with forward and reverse run and a speed potentiometer p. 4
- Using the keypad and moving between monitor and program modes p. 5, 6
- Running a powerup test from the keypad or the logic terminals p. 7
- Reading error codes and the conditions at the trip p. 8, 9
- Restoring factory default settings p. 10
- Assigning intelligent input and output terminal functions p. 21
- Setting up analog input signal types p. 22
- UL wiring, wire sizes, terminal torque, breakers and fuses p. 23, 24, 25
Good to know
- Meant as a reference for experienced users; read the X200 Manual and its addendum before a first installation. p. 2
- The power terminal layout differs from older models such as the L100 and L200 series. p. 2
- Analog inputs O and OI cannot be used at the same time. p. 3
- The capacitors take at least 5 minutes to discharge. p. 23
- With two or more motors on one inverter, the electronic overload cannot protect them; fit a thermal relay on each motor. p. 25
Questions this manual answers
What do X200 error codes E_07 and E_09 mean?
E_07 is over voltage protection, when the DC bus voltage passes a threshold from motor regeneration. E_09 is an under voltage error. p. 8
How do I reset an X200 inverter to factory defaults?
Set b084 to 01 and store it, then hold the FUNC, 2 and STOP/RESET keys together and release them when your country code appears. p. 10
What Modbus baud rates does the X200 support?
The communication speed can be set to 4800, 9600 or 19200 bps. p. 19
What is the X200 alarm relay contact rating?
Resistive loads up to 250VAC 2.5A or 30VDC 3A, inductive loads up to 250VAC 0.2A or 30VDC 0.7A. p. 3
How do I see what caused the last X200 trip?
Open d081 and press the Function key; the Up and Down keys then show the frequency, current, DC bus voltage and hours at the trip. p. 9
The whole text · 3 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file



