The text of a manual · part 3 of 3
X200 Series Inverter Quick Reference Guide, pages 19 to 25
Pages 19 to 25 of 25
The original document is the PDF (623 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Hitachi X200 Series
Page 19
“C” group: Intelligent Terminal Functions Func. Code C001/ C201 C002/ C202 C003/ C203 C004/ C204 C005/ C205 C011 C012 C013 C014 C015 C021
Name / Description Terminal [1] function Terminal [2] function
Thirty one option codes available (See page 20)
Default value Set -FE/FU value 00 01
Terminal [3] function
02/16
Terminal [4] function
03/13
Terminal [5] function
18
Terminal [1] active state Terminal [2] active state Terminal [3] active state Terminal [4] active state Terminal [5] active state Terminal [11] function y 00 Normally open [NO] y 01 Normally closed [NC] Twelve option codes available (See page 20)
C026
Relay output function
C028
AM signal selection y 00 motor speed y 01 motor current Terminal [11] active state y 00 Normally open [NO] y 01 Normally Alarm relay terminal active closed [NC] state
00
Output mode of low load current y 00 Disabled y 01 During accel, decel and constant speed y 02 During constant speed only Low load detection level
01
C031 C036 C038
C039 C041/ C241 C042 C043 C044 C052 C053 C070 C071 C072 C074 C075 C076
Twelve option codes available (See page 20)
00 00 00 00/01 00 01
Overload output signal level setting Frequency arrival setting for accel Frequency arrival setting for decel PID deviation level setting PID PV high limit PID PV low limit Selection of OPE/ModBus y 02 OPE y 03 ModBus Communication speed selection y 04 4800bps y 05 9600bps y 06 19200bps Node allocation Communication parity selection y 00 No parity y 01 Even parity y 02 Odd parity Communication stop bit selection Communication error select y 00 Trip (error codeE60) y 01 Decelerate to stop and trip (error code E60) y 02 Disable y 03 Free run stop (coasting) - 18 -
05
00 01
INV Rated current INV Rated current 0.0 0.0 3.0 100.0 0.0 02 06/04 1. 00 1 02
Page 20
Func. Code C077 C078 C081 C082 C086 C091 C101
C102
C141 C142 C143
C144 C145 C148 C149
Name / Description
Default value Set -FE/FU value y 04 Decelerate to a stop Communication error time-out 0.00 Communication wait time 0. O input span calibration 100.0 OI input span calibration 100.0 AM offset calibration 100.0 Debug mode enable 00 <Do not change> y 00 No Display y 01 Display Up/Down memory mode selection 00 y 00 Clear last frequency (return to default freq. F001) y 01 Keep last freq. adjusted by Up/Down Reset selection 00 y 00 Cancel trip state at input signal ON transition, stops INV if in Run Mode y 01 Cancel trip state at input signal OFF transition, stops INV if in Run Mode y 02 Cancel trip state at input signal ON transition, no effect if in Run Mode Input A select for logic output Twelve option 00 codes available Input B select for logic output 01 see page 20 Logic function select 00 y 00 [LOG] = A AND B y 01 [LOG] = A OR B y 02 [LOG] = A XOR B Terminal [11] ON delay 0.0 Terminal [11] OFF delay 0.0 Output relay ON delay 0.0 Output relay OFF delay 0.0
00
“H” group: Motor Constants Functions Func. Code
H003/ H203 H004/ H204 H006/ H206
Name / Description
Motor capacity
Factory set 4
Motor poles setting y2 y4 y6
Default -FE/FU y8
Motor stabilization constant
- 19 -
100
Set value
Page 21
Intelligent Input Terminal Listing Symbol FW RV CF1 CF2 CF3 CF4 JG DB SET 2CH FRS EXT USP SFT AT RS PTC STA STP F/R PID PIDC UP DWN UDC OPE ADD F-TM RDY SP-SET EMR -
Code 00 01 02 03 04 05 06 07 08 09 11 12 13 15 16 18 19 20 21 22 23 24 27 28 29 31 50 51 52 53 64 255
Input Terminal Name Forward Run/Stop Reverse Run/Stop Multi-speed select, Bit 0 (LSB) Multi-speed select, Bit 1 Multi-speed select, Bit 2 Multi-speed select, Bit 3 (MSB) Jogging External DC braking Set (select) 2nd motor data 2-stage accel and decel Free-run stop External trip Unattended start protection Software lock Analog input voltage/current selection Reset inverter PTC thermistor thermal protection Start (3-wire interface) Stop (3-wire interface) FWD,REV (3-wire interface) PID disable PID Reset Remote control Up function Remote control Down function Remote control data cleaning Operator control Add frequency enable Force Terminal Mode Inverter ready Special set Emergency stop (No function)
Intelligent Output Terminal Listing Symbol RUN FA1 FA2 OL OD AL Dc FBV NDc LOG ODc LOC
Code 00 01 02 03 04 05 06 07 08 09 10 43
Output Terminal Name Run signal Freq. arrival type 1 – constant speed Freq. arrival type 2 – over-frequency Overload advance notice signal Output deviation for PID control Alarm signal Analog input error PID second stage output Network error Logic output function Communication option error Low load detection
- 20 -
Page 22
Analog Input Configuration The following tables show the parameter settings required for various analog input signal types. A005 AT input Active
02 OFF [O]
03 ON POT
OFF [OI]
ON POT
04 OFF ON [O]
05 OFF ON [OI]
If [AT] is not assigned to any intelligent input terminal, it means AT=OFF in above table.
Note: Analog input O and OI cannot be used at the same time.
Analog Output Function Listing The following table shows all three functions available for assignment to the analog output terminal: y Terminal [AM], option set by C028 Option Code 00
Function Name Output frequency
01
Output current
Description
Corresponding Signal Range Actual motor speed, 0 to max. freq. in Hz represented by PWM signal Motor current (% of 0 to 200% maximum rated output current), represented by PWM signal
- 21 -
Page 23
UL® Cautions, Warnings, and Instructions Wiring Warnings for Electrical Practices and Wire Sizes The warnings and instructions in this section summarize the procedures necessary to ensure an inverter installation complies with Underwriters Laboratories® guidelines.
WARNING: “USE 60/75°C Cu wire only” or equivalent. For models X200-005S, -007S, -011S, -022S, -007N, -015N, -015L, -022L, -037L, -055L, -075L. WARNING: “USE 75°C Cu wire only” or equivalent. For models X200-002S, -004S, -002N, -004N, -002L, -004L, -007L, -022H, -030H, -037H, -040H, -055H, 075H. WARNING: “USE 60°C Cu wire only” or equivalent. For models X200-004H, -007H, and -015H. WARNING: “Open Type Equipment” WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical amperes, 240V maximum when protected by Class CC, G, J or R fuses or circuit breaker having an interrupting rating not les than 100,000 rms symmetrical amperes, 240 volts maximum”. For models with suffix S, N or L. WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical amperes, 480V maximum when protected by Class CC, G, J or R fuses or circuit breaker having an interrupting rating not les than 100,000 rms symmetrical amperes, 480 volts maximum.” For models with suffix H. WARNING: “Install device in pollution degree 2 environment.” WARNING: “Maximum Surrounding Air Temperature 50°C”. or equivalent. WARNING: “Caution-Risk of electric shock⎯capacitor discharge time is at least 5 minutes.” WARNING: “Solid state motor overload protection is provided in each model”. WARNING: “Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electric Code and any additional local codes” or equivalent.
- 22 -
Page 24
Terminal Tightening Torque and Wire Size The wire size range and tightening torque for field wiring terminals are presented in the tables below. Input Voltage
200V
Motor Output
Inverter Model
Power Terminal Wiring Size Range (AWG)
kW
HP
0.2
1/4
X200-002SFE/NFU
0.4
1/2
X200-004SFE/NFU
0.55
3/4
X200-005SFE
0.75
1
X200-007SFE/NFU
1.1
1 1/2
1.5
2
X200-015SFE/NFU
2.2
3
X200-022SFE/NFU
10
3.7
5
X200-037LFU
5.5
7 1/2
X200-055LFU
7.5
10
X200-075LFU
X200-011SFE
Torque Ft-lbs
(N-m)
0.6
0.8
0.9
1.2
10
0.9
1.2
8
1.5
2.0
0.9
1.2
1.5
2.0
14 (75°C only)
12
0.4
1/2
X200-004HFE/HFU
0.75
1
X200-007HFE/HFU
1.5
2
X200-015HFE/HFU
2.2
3
X200-022HFE/HFU
3.0
4
X200-030HFE
4.0
5
X200-040HFE/HFU
5.5
7 1/2
X200-055HFE/HFU
7.5
10
X200-075HFE/HFU
Terminal Connector
Wiring Size Range (AWG)
Ft-lbs
(N-m)
Logic and Analog connectors Relay connector
30 – 16 30 – 14
0.16 – 0.19 0.37 – 0.44
0.22 – 0.25 0.5 – 0.6
400V Class
16 (75°C only)
14 (75°C only)
10
Torque
Wire Connectors WARNING: Field wiring connections must be made by a UL Listed and CSA certified ring lug terminal connector sized for the wire gauge being used. The connector must be fixed using the crimping tool specified by the connector manufacturer.
- 23 -
Terminal (ring lug)
Cable support
Cable
Page 25
Circuit Breaker and Fuse Sizes The inverter’s connections to input power for 400V class units must include UL Listed inverse time circuit breakers with 600V rating, or UL Listed fuses as shown in the table below. Input Voltage
Single/ ThreePhase 200V
ThreePhase 400V
Circuit breaker / Fuse
Inverter Model X200-002SFFE/NFU X200-004SFFE/NFU X200-005SFFE X200-007SFFE/NFU X200-011SFFE X200-015SFFE/NFU X200-022SFFE/NFU X200-037LFU X200-055LFU X200-075LFU X200-004HFE/HFU X200-007HFE/HFU X200-015HFE/HFU X200-022HFE/HFU X200-030HFE X200-040HFE/HFU X200-055HFE/HFU X200-075HFE/HFU
Ampere rating for Fuse or Breaker 10
Inverse time circuit breaker
15 20 30
Distribution Fuse (Class J)
40 50 3 6 10 10 15 15 20 25
Motor Overload Protection Hitachi X200 inverters provide solid state motor overload protection, which depends on the proper setting of the following parameters: • B012 “electronic overload protection” • B212 “electronic overload protection, 2nd motor” Set the rated current [Amperes] of the motor(s) with the above parameters. The setting range is 0.2 * rated current to 1.0 * rated current. WARNING: When two or more motors are connected to the inverter, they cannot be protected by the electronic overload protection. Install an external thermal relay on each motor.
- 24 -