The text of a spec sheet · part 1 of 3

Variable Frequency Drive X200 Series, pages 1 to 9

Pages 1 to 9 of 20

The original document is the PDF (969 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 1 read from a scan by OCR; it may hold reading errors

HITACHI

Inspire the Next

VARIABLE FREQUENCY DRIVE

4 00 Series

© Hitachi Industrial Equipment Systems Co.,Ltd.

Page 2

Simple, Trip-less and Environment-friendly Compact Inverter!

2

Environment-friendly Inverter RoHS compliance for all models.

Integrated EMC Filter Cost and space reduction compared with external EMC filter. (European version only)

Level [dB V ]

VARIABLE FREQUENCY DRIVE

X200Series

1

Single-phase input: EN61800-3 cat.C1 Three-phase input : EN61800-3 cat.C2

120 110 100 90 80 70 60 50 40 30 20 10 0

No filter

Integrated EMC filter 150k 200k 500k

1M

2M

5M

Frequency [Hz]

10M

20M 30M

Conducted emission data (Example of X200-007SFEF)

3 4

Emergency Stop Function Shut off INV output by hardware without software(CPU) high quality emergency stop.

Improved Trip Avoidance Function Over current and over voltage suppressing function is incorporated. This function reduces inverter tripping. <set ramp=0.1s> 5A/div 500ms/div The X200 decelerates Motor and stops the motor rotation OC trip Motor using regenerative current energy from the motor even though the power start start is not supplied. OC suppression OFF

5

OC suppression ON

Non-stop operation at IPF This can achieve smooth retry even when the IPF (Instantaneous Power Failure) occurs. This is useful especially in Fan and pump application.

Mains

Motor current

Motor rotation

Model Configuration 1-/3-phase 200V class

Applicable Motor

3-phase 400V class kW (HP)

US version

European version

Japanese version

0.2(1/4)

X200-002NFU

X200-002SFEF

X200-002LFRF

0.4(1/2)

X200-004NFU

X200-004SFEF

0.55(3/4) 0.75(1)

US version

European version

X200-004LFRF

X200-004HFU

X200-004HFEF

X200-007LFRF

X200-007HFU

X200-007HFEF

X200-005SFEF X200-007NFU

1.1(1.5)

X200-007SFEF X200-011SFEF

1.5(2)

X200-015NFU

X200-015SFEF

X200-015LFRF

X200-015HFU

X200-015HFEF

2.2(3)

X200-022NFU

X200-022SFEF

X200-022LFRF

X200-022HFU

X200-022HFEF

3.0(4) 3.7(5)

X200-030HFEF X200-037LFU

X200-037LFRF X200-040HFU

X200-040HFEF

5.5(7.5)

X200-055LFU

X200-055LFRF

X200-055HFU

X200-055HFEF

7.5(10)

X200-075LFU

X200-075LFRF

X200-075HFU

X200-075HFEF

4.0(5)

1

Page 3

7

The X200 delivers "realtime" energy-saving operation for your fan and pump applications. This function insures that motor operates at minimum current in response to the torque required by the load.

Required power (%)

6

Automatic Energy-saving Function

9

100 91% 90 Damper control 80 70 76% 60 50 61% Energy 40 Saving 30 20 22% Inverter 10 control 0 0 10 20 30 40 50 60 70 80 90 100 Flow (%)

(during regenerating operation increase the DC bus voltage may over motor max. insulation voltage)

Since an inverter can be stuck and installed in a horizontal direction, a space can be used effectively. space needlessness

Micro Surge Voltage suppress function (Patent registered in Japan,USA & Korea) Hitachi original PWM control suppressing Motor terminal Voltage less than 2 times of INV DC voltage E. Lower than Hitachi motor Max. insulation voltage (1,250V)

Side-by-side installation

* Side-by-side installation has derating for carrier frequency and output current required

10

Versatile Functions

11

Global Performance

Motor terminal voltage

1,250V

• Pure analog monitor output(10-bit, 0-10VDC) • Low load detection • External thermistor terminal (PTC) • Cooling-fan on/off • Instantaneous power failure recovery • Second motor setting • 3-wire control • Analog input selection • Second acceleration/deceleration setting • Jogging • Auto-carrier frequency reduction • Unattended start protection (USP) • Analog input wire-break detection

E=650V, cable=100m

8

Network Compatibility

• Conformity to global standards CE, UL, c-UL and c-Tick approvals

RS-485 is provided as standard for Modbus-RTU serial communication PROFIBUS, CANopen option modules are available soon. 〈CE〉 ISO 14001 EC97J1095

ISO 9001 JQA-1153

〈UL, c-UL〉

〈c-Tick〉

Hitachi variable frequency drives (inverters) in this brochure are produced at the factory registered under the ISO 14001 standard for environmental management system and the ISO 9001 standard for inverter quality management system.

Model Name Indication Japanese version

CONTENTS

X200-004 H F E F F : Integrated EMC filter (European version)

X200-004HFRF

X200-007HFRF

Series Name

U : US version E : European version R : Japanese version

X200-015HFRF

F : With keypad

X200-022HFRF

X200-037HFRF

X200-055HFRF X200-075HFRF

Applicable Motor

Power Source

Capacity

N : 1 or 3-phase 200V class

002: 0.2kW(1/4HP)

S : 1-phase 200V class

| 075: 7.5kW(10HP)

L : 3-phase 200V class

Features 1-2 Standard Specifications 3 Dimensions 4 Operation and Programming 5 Operation / Terminal Functions 6 Function List 7-9 Protective Functions 10 Connecting Diagram 11-12 Wiring and Accessories 13 Torque characteristics/Derating Curves 14 For Correct Operation 15-16

H : 3-phase 400V class

2

Page 4

Standard Specifications 1-/3-phase 200V class European Version US Version Applicable motor size, 4-pole kW(HP) *1 230V Rated capacity 240V Rated output current (A) *2 Overload capacity(output current) Rated output voltage (V)

Model X200-

Output Ratings

Input Rating

002SFEF 002NFU 0.2(1/4) 0.5 0.5 1.4

004SFEF 004NFU 0.4(1/2) 1.0 1.0 2.6

0.8 0.8

1.0 0.9

Rated input voltage (V)

Enclosure *4 Cooling method -SFEF -NFU/LFU -SFEF -NFU/LFU

Integrated EMC filter Weight (kg)

011SFEF 015SFEF 022SFEF 015NFU 037LFU 55LFU 022NFU 1.5 (2) 3.7(5) 5.5(7.5) 1.1(1.5) 2.2(3) 2.8 6.3 9.6 1.9 3.9 2.9 6.6 9.9 2.0 4.1 7.1 5.0 15.9 24.0 10.0 150% for 60 sec. 3-phase (3-wire) 200 to 240V (corresponding to input voltage) SFEF: 1-phase 200 to 240V+10%, -15%, 50/60Hz ±5% NFU: 1-/3-phase 200 to 240V+10%, -15%, 50/60Hz ±5% LFU: 3-phase 200 to 240V+10%, -15%, 50/60Hz ±5% IP20 Self-cooling Force ventilation EN61800-3 category C1 filter 1.5 1.5 2.4 2.4 2.5 1.5 2.3 2.4 2.3 4.2 005SFEF 0.55(3/4) 1.1 1.2 3.0

007SFEF 007NFU 0.75(1) 1.5 1.6 4.0

075LFU 7.5(10) 12.7 13.3 32.0

4.2

3-phase 400V class European Version US Version Applicable motor size, 4-pole kW(HP) *1 Rated capacity 400V 480V Rated output current (A) *2 Overload capacity(output current) Rated output voltage (V) Rated input voltage (V)

Model X200-

Output Ratings

Input Rating Enclosure *4 Cooling method

004HFEF 004HFU 0.4(1/2) 1.0 1.2 1.5

007HFEF 007HFU 0.75(1) 1.7 2.0 2.5

Self-cooling -HFEF -HFU -HFEF -HFU

Integrated EMC filter Weight (kg)

1.5 1.4

2.3 2.2

030HFEF 022HFEF 040HFEF 022HFU 040HFU 2.2(3) 4(5) 3(4) 3.8 5.9 5.4 4.5 7.1 6.4 5.5 8.6 7.8 150% for 60 sec. 3-phase (3-wire) 380 to 480V (corresponding to input voltage) 3-phase 380 to 480V +10%, -15%, 50/60Hz±5% IP20 Force ventilation EN61800-3 category C2 filter 2.4 2.4 2.4 2.4 2.3 2.3 2.3 -

015HFEF 015HFU 1.5 (2) 2.6 3.1 3.8

055HFEF 055HFU 5.5(7.5) 9.0 10.8 13.0

075HFEF 075HFU 7.5(10) 11.1 13.3 16.0

4.2 4.2

4.2 4.2

General Specifications

Control

Item Control method Output frequency range *5 Frequency accuracy *6 Frequency setting resolution Voltage/Frequency Characteristic Acceleration/deceleration time Starting torque *7 Carrier frequency range Protective functions Specification

Input terminal

Functions

Specification Intelligent output terminal Output signal

Function Analog output terminal Display

Specification Function Specification Function

Operator Status LED Interface Frequency setting Operation FW/RV Run

Environment

Operating temperature Storage temperature Humidity Vibration Location Other functions Coating color Options

Operator keypad External signal Serial port Operator Keypad External signal Serial port

General Specifications Line-to-line sine wave pulse-width modulation (PWM) control 0.5 to 400Hz Digital command :±0.01%, Analog command±0.4% (25 ±10˚C) Digital: 0.1Hz, Analog: (max frequency)/1000 V/f control,V/f variable (constant torque, reduced torque) 0.01 to 3000 sec. (linear, sigmoid), two-stage accel./decel. 100%/6Hz 2.0 to 12kHz Over-current, over-voltage, under-voltage, overload, overheat, ground fault at power-on, input over-voltage, external trip, EEPROM error, CPU error, USP error, Termister error, Driver error, Emergency stop 10kohm input impedance, sink/source logic selectable FW(Forward), RV(Reverse), CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run stop), EXT(External trip), USP(Unattended start protection), SFT(Software lock), AT(Analog input selection), RS(Reset), PTC(Thermistor input) *8, STA(3-wire start), STP(3-wire stop), F/R(3-wire fwd./rev.), PID(PID On/Off), PIDC(PID reset), UP/DWN(Remote-controlled accel./decel.) , UDC(Remote-controlled data clearing), OPE(Operator control), ADD(ADD frequency enable), FTM(force terminal mode), RDY(quick start enable),S-ST(Special-Set 2nd Motor Data),EMR(Emergency stop), NO(Not selected) 27V DC 50mA max open collector output, 1 terminals 1c output 250V AC/30V DC 2.5A relay (AL0, AL1, AL2 terminals) RUN(run signal), FA1(Frequency arrival type 1 - constant speed), FA2(Frequency arrival type 2 - over-frequency), OL(overload advance notice signal), OD(Output deviation for PID control), AL(alarm signal), DC(Wire brake detect on analog input), FBV(PID Second Stage Output), NDC(ModBus Network Detection Signal), LOG(Logic Output Function), ODC(Option Card Detection Signal), LOC(Low load) 0 to 10V DC Analog Frequency monitor, analog current monitor 4-digits 7 segment LEDs

Parameter setting, output frequency, output current, scaled value of output frequency, trip history, I/O terminal condition, output voltage. Rotation direction, PID Feedback, RON time, Power-on time. Power, Alarm, Run, Prg, Hz and A Potentiometer, RUN, STOP/RESET, UP, DOWN, FUN and STR keys Up and Down keys / Value settings or analog setting via potentiometer on operator keypad 0 to 10 V DC, 4 to 20 mA RS485 interface (Modbus RTU) Run key / Stop key (change FW/RV by function command) FW Run/Stop (NO contact), RV set by terminal assignment (NC/NO), 3-wire input available RS485 interface (Modbus RTU) -10 to 50˚C(carrier derating required for aambient temperature higher than 40°C), no freezing -20 to 65˚C 20 to 90% RH 5.9mm/s2 (0.6G) 10 to 55Hz Altitude 1,000 m or less, indoors (no corrosive gasses or dust)

AVR (Automatic Voltage Regulation), V/f characteristic selection, accel./ decel. curve selection, frequency upper/lower limit, 16 stage multispeed, PID control, frequency jump, external frequency input bias start/end, jogging, cooling fan On/Off, trip history etc. Blue Remote operator with copy function (SRW-0EX), input/output reactors, DC reactors, radio noise filters, braking resistors, braking units, LCR filter, communication cables (ICS-1, 3)

Note 1: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When using other motors, care must be taken to prevent the rated motor current (50/60 Hz) from exceeding the rated output current of the inverter. Note 2: The output voltage decreases as the main supply voltage decreases (except when using the AVR function). In any case, the output voltage cannot exceed the input power supply voltage. Note 3: The braking torque via capacitive feedback is the average deceleration torque at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not continuous regenerative braking torque. The average decel torque varies with motor loss. This value decreases when operating beyond 50 Hz. If a large regenerative torque is required, the optional regenerative braking resistor should be used. Note 4: The protection method conforms to JEM 1030. Note 5: To operate the motor beyond 50/60 Hz, consult the motor manufacturer for the maximum allowable rotation speed. Note 6: The output frequency may exceed the maximum frequency setting (A004 or A204) for automatic stabilization control. Note 7: At the rated voltage when using a Hitachi standard 3-phase, 4pole motor. Note 8: Only terminal 5 is assignable the PTC (thermistor) function.

3

Page 5

Dimensions X200-002SFEF, NFU

●

80(3.15)

80(3.15) 67(2.64)

67(2.64) 5(0.20)

13(0.51) ●

X200-007SFEF,NFU

● ●

X200-011SFEF X200-037LFU

110(4.33)

●

155(6.10)

X200-015〜022SFEF, NFU X200-007〜040HFEF, HFU

110(4.33)

98(3.86)

98(3.86)

5(0.20)

Exhaust

4.4(0.17)

Wall

Air Intake

6(0.24)

011SFEF, 007HFEF, HFU: without FAN

X200-055〜075HFEF 2-φ6(0.24)

Wall

4.4(0.17)

235(9.25)

180(7.09) 164(6.46)

250(9.84)

●

155(6.10)

55(2.17)

128(5.04)

28(1.10)

5(0.20)

2.6(0.10) 6(0.24)

165(6.50)

X200-055〜075LFU,HFU

Wall

4.4(0.17)

189(7.44)

176(6.93)

6(0.24)

6(0.24)

5(0.20)

5(0.20)

●

●

176(6.93)

X200-005SFEF X200-004HFEF,HFU

2.6(0.10)

2.6(0.10) ●

107(4.21)

27(1.06)

5(0.20)

93(3.66)

5(0.20)

Wall

4.4(0.17)

143(5.63)

155(6.10)

Wall

4.4(0.17)

143(5.63)

6(0.24)

6(0.24)

5(0.20)

●

[Unit: mm(inch)] Inches for reference only

X200-004SFEF, NFU

189(7.44)

●

4

Page 6

Operation and Programming The X200 series can be easily operated with the digital operator provided as standard.

4X-KITmini

Screw

The digital operator can also be detached and used for remote-control. An operator with copy function is also available as an option.

Panel External Gasket

Power LED

Parameter Display Displays frequency, motor current,

Lights when the power rotational speed of the input to the drive is ON.

Front Cover motor, and an alarm code.

Internal Gasket 1

Display Unit LEDs RUN Key

Indicates the unit associated

Press to run the motor.

to drive or reset an stop

Internal Gasket 2

Monitor LEDs

STOP/RESET Key Press

Seal with the parameter display.

Rear Cover

Shows drive's status.

the alarm.

Potentiometer

Function Key You can mount an optional keypad

Press to set or monitor a with the potentiometer part no.

parameter value.

OPE-SRmini for a NEMA1 rated

Press up or parameters for removing the potentiometer down and installation. The kit also provides

Store Key

Up/Down Keys to sequence functions shown

Press to write the new through on value to the EEPROM.

the display, and increment/decrement values.

knob to meet NEMA 4X requirements, as shown (part no. 4X-KITmini).

1. Setting the maximum output frequency (1)

or the value previously monitored is displayed.

Power on

(2)Function code appears.

Press

(5)

appears.

key.

(3)

appears.

Press

Press until appears.

(6)Preset value is displayed.

Press

Press

(4)

until

*Pressing

2. Running the motor(by potentiometer) or the value previously monitored is displayed.

(8)Returns to and the setting is complete.

Press key to store the value. *To run the motor, go back to monitor mode or basic setting mode.

appears.

(1)

key.

(7)Newly set value is displayed.

Press to set desired value.

key.

or the code number set in the end of last setting is displayed.

key for a while and back to (2)The motor runs at the frequency set by the potentiometer.

(3)The motor stops.

Power on Press key and turn the potentiometer clockwise.

Press key to stop the motor.

(Output frequency monitor)

3. Monitoring output current value (1)

Power on or the value previously monitored is displayed.

Press

(2)Function code appears.

key.

(3)

Press until appears.

5

(4)Output current value is displayed.

appears.

Press key.

Page 7

Operation / Terminal Functions Hardware switches Switch symbol

Switch Name

SW7

RS-485 communication/key pad selection switch

Switch Name Description Select communication connector distination. *1 485 RS-485 communicaiton via Modbus protocol OPE [default] Keypad (option) Select frequency and run command input source.

SW7 485

SW8

The SW8 is for the emergency signal input. If you turn this DIP switch ON, the inverter is ready to receive emergency signal from the dedicated terminal #3. Inverter shuts off the output by means of pure hardware when a signal is given to the terminal. Each signals related to this emergency input must be in accordance with the norm. Additionally, the logic input terminal assign will be changed automatically if the SW8 is made ON.

ON OPE

OFF

Emergency stop ON/OFF

SW8

Note 1:The standard keypad OPE (OPE-SRmini) can be used either the switch is set to 485 or OPE. Note 2:Input terminal selection (EMR) cannot be chosen from an operaator. If the slide switch SW8 is turned ON, it divides automatically and is attached.

RS-485 communication/ operator selection switch Emergency stop ON/Off switch

Terminal Description Terminal arrangement

Terminal Symbol Terminal Symbol L1,L2,N/L3 U/T1,V/T2,W/T3

Terminal Name Main power supply input terminals

¥ X200- 002~004SFEF,

+1,+ +-

004~040HFEF, 004~040HFU 055~075LFU,

055~075HFU

055~075HFEF

Ground connection terminal

L1

SFEF

/

N

SFEF

L1

/

N

NFU,LFU

L1

L2

L3/N

HFEF,HFU

R/L1 S/L2 T/L3

Jumper

Screw Diameter and Terminal Width Model

¥ X200- 005~022SFEF, 007~022NFU, 037LFU

002~004NFU

Inverter output terminals DC reactor connection terminals External braking unit connection terminals

L1

NFU,LFU

Screw diameter (mm)

Terminal width W (mm)

002 - 004NFU/SFEF 007- 022NFU, 037LFU

M3.5

7.1

005 - 022SFEF 004- 040HFU/HFEF 055- 075LFU/HFU/HFEF

M4

9.2

M5

12

L2

Jumper

L3/N Jumper

Jumper

Jumper -

Jumper

+ +1 U/T1 V/T2 W/T3

Control circuit terminals

Jumper

U/T1 V/T2 W/T3

-

+

+1

Terminal arrangement AL2 AL1 AL0

AM

H

O

OI

L

5

4

3

2

1

L

PCS P24 CM2

11

Short bar:default position (Source logic)

Terminal function

Input/monitor signals

Terminal name AM L P24 PCS 5 4 3 2

Ranges and Notes 0 to10V DC, 1mA max. 24V DC, 30mA (do not short to terminal L) -

1

Description Voltage analog output Common for inputs +24V for logic inputs Intelligent input common Intelligent (programable) input terminals, selection from: FW(Forward), RV(Reverse), CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run stop), EXT(External trip), USP(Unattended start protection), SFT(Software lock), AT(Analog input selection), RS(Reset), PTC(Thermistor input), STA(3-wire start), STP(3-wire stop), F/R(3-wire fwd./rev.), PID(PID On/Off), PIDC(PID reset), UP/DWN(Remote-controlled accel./decel.), UDC(Remote-controlled data clearing), OPE(Operator control), ADD(Frequency setpoint), FTM(Force terminal enable), RDY(Quick start enable), S-ST(Special-Set 2nd Motor Data), EMR(Emergency stop) or NO(Not selected).

H

+10V analog reference

10V DC, 10mA max H

O

OI

L

H

O

OI

L

H

O

L

+

-

VR (1kΩ-2kΩ)

-

DC0-10V Input inpedance 10kΩ

DC4-20mA Input inpedance 250Ω

Analog input, current

L

Common for inputs

11

Intelligent (programable) output terminals, selection from: RUN(run signal), FA1(Frequency arrival type 1 -constant speed), FA2(Frequency arrival type 2 -over-frequency), OL(overload advance notice signal), OD(Output deviation for PID control), AL(alarm signal), DC(Wire brake detect on analog input), FBV(Feedback voltage comparison), NDc(Network Disconnection), LOG(Logic operation result), ODC(Option Card Detection signal), LOC(Low Load Detection). Common for intelligent output terminals

AL0

Operated by closing switch. (Input logic is selectable)

4 to 20mA DC, input impedance 250ohm

Assign [AT] for input terminal to selecting frequency source from voltage or current.

Open collector output L level at operation (ON) 27V DC, 50mA max.

AC250V

AL2 AL1

1-5

0 to 10V DC, input impedance10kohm

+

OI

CM2

Relay output

OI

Analog input, voltage

Freqency setting

Output signals

O

P24 SW

Relay contact (alarm output) terminals (programable, function is selectable same as intelligent output terminals).

AL2

AL1

AL0

<Initial setting> Normal : AL0-AL1 closed Trip/Power OFF : AL0-AL2 closed

2.5A (Resistive load) 0.2A (cos =0.4) DC30V 3.0A (Resistive load) 0.7A (cos =0.4) (minimum) AC100V 10mA DC 5V 100mA

6

Page 8

Function List The parameter tables in this chapter have a column titled "Run Mode Edit." An Ex mark x means the parameter cannot be edited; a Check mark means the parameter can be edited. The table example to the right contains two adjacent marks "x ". These two marks (that can also be "xx" or " ") correspond to low-access or high-access levels to Run Mode edits (note Lo and Hi in column heading).

[ X:: Allowed Not allowed ]

Monitoring and main profile parameters Function Code

Name d001 d002 d003 d004

Output frequency monitor Output current monitor Rotation direction monitor Process variable, PID feedback monitor d005

Intelligent input terminal status d006

Intelligent output terminal status d007 d013 d016 d017 d018 d080 d081 d082 d083 d102 d104 F001 F002 F202 F003 F203 F004 A-b-C-H-P--

Scaled output frequency monitor Output voltage monitor Cumulative operation RUN time monitor Cumulative power-on time monitor Cooling fin temperature monitor Trip counter Trip monitor 1 Trip monitor 2 Trip monitor 3 DC bus voltage monitor Electronic themal monitor Output frequency setting Acceleration time (1) setting Acceleration time (2) setting Deceleration time (1) setting Deceleration time (2) setting Keypad Run key routing A Group: Standard functions b Group: Fine-tuning functions C Group: Intelligent terminal functions H Group: Motor constants functions P Group: Expansion Card Functions

Range 0.0 to 400.0 0.0 to 999.9 F(Forward)/o(Stop)/r(Reverse) 0.00 to 99.99/100.0 to 999.9/1000. to 9999. 54

32

AL

Monitor

Main Profile Parameters

Expanded functions

Run mode edit

Default

Unit

Lo

Hi

-

Hz A -

-

-

ON OFF e.g. :1,2 : ON 3,4,5 : OFF

-

-

-

-

ON OFF e.g. :11 AL

-

-

-

-

0.0 10.0 10.0 10.0 10.0 00

V hr hr ˚C events V % Hz sec sec sec sec -

-

-

X

X

1

11

: ON : OFF

0.00 to 99.99/100.0 to 999.9/1000. to 9999./1000 to 9999(10000 to 99999) 0.0 to 600.0 0. to 9999./1000 to 9999/ 100 to 999 (10000 to 99900) 0. to 9999./1000 to 9999 0.0 to 200.0 0. to 9999. Displays trip event information 0.0 to 999.9 0.0 to 100.0 0.0/start freq. to 400.0 0.01 to 99.99/100.0 to 999.9/1000. to 3000. 0.01 to 99.99/100.0 to 999.9/1000. to 3000. 0.01 to 99.99/100.0 to 999.9/1000. to 3000. 0.01 to 99.99/100.0 to 999.9/1000. to 3000. 00(Forward)/01(Reverse)

[ X:: Allowed Not allowed ]

A Group: Standard functions Default Function Code

Basic setting

Analog input setting

Multi-speed and jogging

V/f Characteristic

DC braking

Frequency limit and jump frequency

7

Name A001 A201 A002 A202 A003 A203 A004 A204 A005 A011 A012 A013 A014 A015 A016 A020 A035 A220 A038 A039 A041 A241 A042 A242 A043 A243 A044 A244 A045 A245 A051 A052 A053 A054 A055 A056 A061 A261 A062 A262 A063 A064 A065 A066 A067 A068

Unit

Range -EF(CE)

-U(UL) 00 00 02 02 60. 60. 60. 60. 02 0.0 0.0 0.0 100. 01 8.

Hz Hz Hz Hz Hz Hz % % -

Frequency source setting Frequency source setting, 2nd motor Run command source setting Run command source setting, 2nd motor Base frequency setting Base frequency setting, 2nd motor Maximum frequency setting Maximum frequency setting, 2nd motor [AT] selection [O]-[L] input active range start frequency [O]-[L] input active range end frequency [O]-[L] input active range start voltage [O]-[L] input active range end voltage [O]-[L] input start frequency enable External frequency filter time constant

30 to maximum freq. 30 to maximum freq. 30 to 400 30 to 400 02(O/VR)/03(OI/VR)/04(O)/05(OI) 0.0 to maximum freq. 0.0 to maximum freq. 0 to 100 0 to 100 00(use set value)/01(use 0 Hz) 1 to 17

01 01 01 01 50. 50. 50. 50. 02 0.0 0.0 0.0 100. 01 8.

Multi-speed frequency setting (0-15)

0.0/start freq. to maximum freq.

0.0

0.0

Hz

Multi-speed frequency (2nd), setting 2nd motor Jog frequency setting Jog stop mode Torque boost select Torque boost select 2nd motor Manual torque boost value Manual torque boost value, 2nd motor Manual torque boost frequency adjustment Manual torque boost frequency adjustment, 2nd motor V/f characteristic curve selection V/f characteristic curve selection, 2nd motor V/f gain setting V/f gain setting, 2nd motor DC braking enable DC braking frequency setting DC braking wait time DC braking force during deceleration DC braking time for deceleration DC braking / edge or level detection for [DB] input Frequency upper limit setting Frequency upper limit setting, 2nd motor Frequency lower limit setting Frequency lower limit setting, 2nd motor Jump (center) frequency setting 1 Jump (hysteresis) frequency setting 1 Jump (center) frequency setting 2 Jump (hysteresis) frequency setting 2 Jump (center) frequency setting 3 Jump (hysteresis) frequency setting 3

0.0/start freq. to maximum freq. 0.00/start freq. to 9.99 00(free-run stop)/01(deceleration and stop)/02 (DC braking) 00(Manual)/01(Automatic) 00(Manual)/01(Automatic) 0.0 to 20.0 0.0 to 20.0 0.0 to 50.0 0.0 to 50.0 00(VC)/01(Reduced torque)/06 (Reduced torque 1) 00(VC)/01(Reduced torque)/06 (Reduced torque 1) 20 to 100 20 to 100 00(Disable)/01(Enable)/02(Frequency detection) 0.0 to 60.0 0.0 to 5.0 0. to 100. 0.0 to 60.0 00(Edge)/01(Level) 0.0/Freq. lower limit setting to maximum freq. 0.0/Freq. lower limit setting (2nd) to maximum freq. (2nd) 0.0/Start freq. to freq. upper limit setting 0.0/Start freq. (2nd) to freq. upper limit setting (2nd) 0.0 to 400. 0.0 to 10.0 0.0 to 400. 0.0 to 10.0 0.0 to 400. 0.0 to 10.0

0.0 1.00 00 00 00 1.8 0.0 10.0 0.0 00 00 100. 100. 00 0.5 0.0 0. 0.0 01 0.0 0.0 0.0 0.0 0.0 0.5 0.0 0.5 0.0 0.5

0.0 1.00 00 00 00 1.8 0.0 10.0 0.0 00 00 100. 100. 00 0.5 0.0 0. 0.0 01 0.0 0.0 0.0 0.0 0.0 0.5 0.0 0.5 0.0 0.5

Hz Hz % % % % % % Hz sec % sec Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz

00(Keypad potentiometer)/01(Control terminal)/ 02(Function F001 setting)/03(RS485)/10(Calculation result) 01(Control terminal)/02(Run key on keypad)/03(RS485)

Run mode edit

Lo

Hi

X X X X X X X X X X X X X X X

X X X X X X X X

X X X

X X X X X X X X X X X X X X X X X X X X

X X

X X

Page 9

Function List [ X:: Allowed Not allowed ]

A Group: Standard functions Default Function Code

PID Control

AVR function Automatic Energy Saving

Operation mode and acc./dec. function

External freq. tuning

Frequency caluculation

Name A071 A072 A073 A074 A075 A076 A077 A078 A081

PID Enable PID proportional gain PID integral time constant PID derivative time constant PV scale conversion PV source setting Reverse PID action PID output limit AVR function select

A082

AVR voltage select

A085 A086 A092 A292 A093 A293 A094 A294 A095 A295 A096 A296 A097 A098 A101 A102 A103 A104 A105 A141 A142 A143 A145 A146 A151 A152 A153 A154 A155

Operation mode selection Energy saving mode tuning Acceleration (2) time setting Acceleration (2) time setting, 2nd motor Deceleration (2) time setting Deceleration (2) time setting, 2nd motor Select method to switch to Acc2/Dec2 profile Select method to switch to Acc2/Dec2 profile, 2nd motor Acc1 to Acc2 frequency transition point Acc1 to Acc2 frequency transition point, 2nd motor Dec1 to Dec2 frequency transition point Dec1 to Dec2 frequency transition point, 2nd motor Acceleration curve selection Deceleration curve selection [OI]-[L] input active range start frequency [OI]-[L] input active range end frequency [OI]-[L] input active range start current [OI]-[L] input active range end current [OI]-[L] input start frequency enable A input select for calculate function B input select for calculate function Calculation symbol ADD frequency ADD direction select Pot. input active range start frequency Pot. input active range end frequency Pot. input active range start current Pot. input active range end current Pot.input start frequency enable

Unit

Range 00(Disable)/01(Enable) 0.2 to 5.0 0.0 to 150.0 0.00 to 100.0 0.01 to 99.99 00([OI] terminal)/01([O] terminal)/02(RS485)/10(Calculation result) 00(OFF)/01(ON) 0.0 to 100.0 00(Enable)/01(Disable)/02(Enabled except during deceleration) 200V class: 200/215/220/230/240 400V class: 380/400/415/440/460/480 00(Normal)/01(Energy-saver) 0.0 to 100.0 0.01 to 99.99/100.0 to 999.9/1000. to 3000. 0.01 to 99.99/100.0 to 999.9/1000. to 3000. 0.01 to 99.99/100.0 to 999.9/1000. to 3000. 0.01 to 99.99/100.0 to 999.9/1000. to 3000. 00(2CH from input terminal)/01(transition freq.) 00(2CH from input terminal)/01(transition freq.) 0.0 to 400.0 0.0 to 400.0 0.0 to 400.0 0.0 to 400.0 00(Linear)/01(S-curve) 00(Linear)/01(S-curve) 0.0 to 400.0 0.0 to 400.0 0. to 100. 0. to 100. 00(Use setting value)/01(0Hz) 00(Digital operator)/01(Keypad potentiometer) 02(O input)/03(OI input)/04(RS485) 00(A141+A142)/01(A141-A142)/02(A141*A142) 0.0 to 400.0 00(Plus)/01(Minus) 0.0 to 400.0 0.0 to 400.0 0.0 to 100.0 0.0 to 100.0 00(Use offect (A151 value))/01(Use 0Hz)

-U(UL)

00 1.0 1.0 0.00 1.00 00 00 0.0 00

00 1.0 1.0 0.00 1.00 00 00 0.0 00 sec sec % -

X

X X X X X

X

230/400

230/460

V

X

X

00 50.0 15.00 15.00 15.00 15.00 00 00 0.0 0.0 0.0 0.0 00 00 0.0 0.0 0.0 100. 01 01 02 00 0.0 00 0.0 0.0 0.0 100. 01

00 50.0 15.00 15.00 15.00 15.00 00 00 0.0 0.0 0.0 0.0 00 00 0.0 0.0 0.0 100. 01 01 02 00 0.0 00 0.0 0.0 0.0 100. 01 sec sec sec sec sec Hz Hz Hz Hz Hz Hz % % Hz Hz Hz % % -

X X

X X

X X X X X X X X X X X X X X X X

X X X X X X X X

Lo

Default Name b001

Selection of automatic restart mode b002 b003

Allowable under-voltage power failure time Retry wait time before motor restart Instantaneous power failure / under-voltage trip alarm enable Number of restarts on power failure / under-voltage trip events Start frequency to be used in case of frequency pull-in restart b004 Restart after instantaneous power failure b005 b011 b012

Electronic thermal setting b212

Electronic thermal setting, 2nd motor b013 b213 b021 b221 b022 b222 b023 b223 b028 b228 b029

Electronic thermal characteristic Electronic thermal characteristic, 2nd motor Overload restriction operation mode Overload restriction operation mode, 2nd motor Overload restriction setting Overload restriction setting, 2nd motor Deceleration rate at overload restriction Deceleration rate at overload restriction, 2nd motor Overload restriction source selection Overload restriction source selection, 2nd motor Deceleration rate of frequency pull-in restart b030

Current level of frequency pull-in restart

Range

Lock b031

Software lock mode selection

Others b050 b051 b052 b053 b054 b055 b056 b057 b080 b082 b083

Selection of the non stop operation Non stop operarion start voltage setting OV-LAD Stop level of non stop operation setting Deceleration time of non stop operation setting Frequency width of quick deceleration setting DC bus AVR P-gain DC bus AVR I-time DC bus AVR D-time [AM] terminal analog meter adjustment Start frequency adjustment Carrier frequency setting

X X X X X X

Unit -EF(CE)

-U(UL)

Run mode edit

Lo

00(Alarm output)/01(Restart at 0Hz)/02(Resume after freq. matching)/03(Resume freq. matching then trip) 0.3 to 25.0 0.3 to 100.0

00

00

-

X

1.0 1.0

1.0 1.0 sec sec

X X

00(Disable)/01(Enable)

00

00

-

X

00(Restart 16 times)/01(Always restart)

00

00

-

X

-

X

A

X

00(frequency at previous shutoff)/01(Max. Hz)/02(Set frequency)

0.2*Rated current to 1.0*Rated current

Overload restriction

Hi

[ X:: Allowed Not allowed ] b Group: Fine-tuning functions Function Code

Run mode edit

-EF(CE)

00(Reduced torque)/01(Constant torque)/02(Reduced torque 2) 00(Disable)/01(Enable)/02(Enable for during acceleration) 0.2*Rated current to 1.5*Rated current 0.1 to 3000.0 00(b022/b222 setting level)/01([O]-[L] analog input) 0.1 to 3000.0 0.2*Rated current to 2.0*Rated current 00([SFT] input blocks all edits)/01([SFT] input blocks edits except F001 and Multispeed parameters/02(No access to edits)/03(No access to edits except F001 and Multi-speed parameters)/10(High-level access,including b031) 00(Disabled)/01(Enabled stop)/02(Enabled restart) 0.0 to 1000.0 0.0 to 1000.0 0.01 to 3000 0.0 to 10.0 0.2 to 5.0 0.0 to 150.0 0.0 to 100.0 0. to 255. 0.5 to 9.9 2.0 to 12.0

00

00

Rated current Rated current 01 01 01 01 1.5*Rated current 1.0 1.0 00 00 0.5 Rated current

Rated current Rated current 01 01 01 01 1.5*Rated current 30.0 30.0 00 00 0.5 Rated current

01 00 0.0 0.0 1.0 0.0 0.2 0.2 0.0 100. 0.5 3.0

Hi

X

A

X

A A sec sec sec

X X X X X X X X X X X

X

A

X

X

01

-

X

00 0.0 0.0 1.0 0.0 0.2 0.2 0.0 100. 0.5 3.0

V V sec Hz sec sec Hz kHz

X X X X X X X X

X X X X X X X X

X X

X

8