The text of a spec sheet · part 2 of 3
Variable Frequency Drive X200 Series, pages 10 to 19
Pages 10 to 19 of 20
The original document is the PDF (969 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Hitachi X200 Series
Page 10
Function List Default Function Code
Others
Name b084
Initialization mode (parameters or trip history)
b085 b086 b087 b088
Country code for initialization Frequency scaling conversion factor STOP key enable Restart mode after FRS b089
Monitor display select for networked inverter b091 b092 b130 b131 b133 b134 b140 b150 b151
Stop mode selection Cooling fan control (see note below) Over-voltage LADSTOP enable Over-voltage LADSTOP level DC bus AVR selection Threshold voltage of DC bus AVR setting Over-current trip suppression Carrier mode Quick start enable
Unit
Range 00(Trip history clear)/01(Parameter initialization)/ 02(Trip history clear and parameter initialization) 00(JP)/01(CE)/02(US) 0.1 to 99.9 00(Enable)/01(Disable) 00(Restart from 0Hz)/01(Restart with frequency detection) 01(Output frequency)/02(Output current)/03(Rotation direction)/ 04(PV, PID feedback)/05(Input terminal status)/ 06(Output terminal status)/07(Scaled output frequency) 00(Deceleration and stop)/01(Free-run stop) 00(Always ON)/01(ON during RUN, OFF during STOP)/02(Temperature controlled) 00(Disable)/01(Enable) 330 to 395V/660 to 790V 00(Disabled)/01(Enabled) 330 to 395V/660 to 790V 00(Disable)/01(Enable) 00(Disable)/01(Enable) 00(Disable)/01(Enable)
-U(UL)
Lo
Hi
00
00
-
X
X
01 1.0 00 00
02 1.0 00 00
-
X
X
01
01
-
00 00 00 380/760 00 380/760 01 00 00
00 00 00 380/760 00 380/760 01 00 00
V V -
Default
Intelligent input terminal
Intelligent input terminal
Serial communication
Analog meter setting
Others
Name C001 C201 C002 C202 C003 C203 C004 C204 C005 C205 C011C015
Range
Unit -EF(CE)
-U(UL)
-
X
X
01
-
X
X
05 00 00 01
05 00 00 01
-
X X X X
X
01
01
-
X
Rated current
Rated current
A
0.0 0.0 3.0 100 0.0 02 06 1. 00 1
0.0 0.0 3.0 100 0.0 02 04 1. 00 1
Hz Hz % % % bit
X X X X X X X X X X X X X
Terminal [1] to [5] active state
00(NO)/01(NC)
00
00*
01
C038
Output mode of low load detection signal
C039 C041 C241 C042 C043 C044 C052 C053 C070 C071 C072 C074 C075
Low load detection level Overload level setting Overload level setting, 2nd motor Frequency arrival setting for acceleration Frequency arrival setting for deceleration PID deviation level setting Feedback comparison upper level Feedback comparison lower level SELECTION OF OPE/MODBUS Communication speed selection Node allocation Communication parity selection Communication stop bit selection
C076
Communication error mode
C077 C078 C081 C082 C086 C091 C101
Communication error time Communication wait time [O] input span calibration [OI] input span calibration [AM] terminal offset tuning Reserved (for factory adjustment) Up/Down memory mode selection
C102
Reset mode selection
C141 C142 C143 C144 C145 C148 C149
Input A select for logic output 1 Input A select for logic output 2 Logic function select ON delay time, output terminal 11 OFF delay time, output terminal 11 ON delay time, relay OFF delay time, relay
00(RUN:run signal), 01(FA1:Frequency arrival type 1 - constant speed), 02(FA2:Frequency arrival type 2 - over-frequency), 03(OL:overload advance notice signal), 04(OD:Output deviation for PID control), 05(AL:alarm signal), 06(DC:Wire brake detect on analog input), 07(FBV: Feedback voltage comparison), 08(NDc: Network Disconnection), 09(LOG: Logic operation result), 10(ODC: Option Card Detection Signal), 43(LOC:Low load detection) 00(Output frequency)/01(Output current) 00(NO)/01(NC) 00(NO)/01(NC) 00(Disabled)/01(During acceleration, deceleration and constant speed)/02(During constant speed only) 0.0 to 2.0*Rated current 0.0*Rated current to 2.0*Rated current 0.0 to 400.0 0.0 to 400.0 0.0 to 100.0 0.0 to 100.0 0.0 to 100.0 02(OPE or option)/03(485) 04(4800bps)/05(9600bps)/06(19200bps) 1. to 32. 00(No parity)/01(Even parity)/02(Odd parity) 1(1-bit)/2(2-bit) 00(Trip)/01(Trip after deceleration stop)/02(Disable)/ 03(FRS)/04(Deceleration stop) 0.00 to 99.99 0. to 1000. 0. to 200. 0. to 200. 0.0 to 10.0 00 (must not be changed) 00(Clear last frequency)/01(Keep last frequency adjusted by UP/DWN) 00(Cancel trip state at input signal ON transition)/ 01(Cancel trip state at signal OFF transition)/ 02(Cancel trip state at input signal ON transition) 00(RUN)/01(FA1)/02(FA2)/03(OL)/04(OD) 05(AL)/06(Dc)/07(FBV)/08(NDc)/10(ODc)/43(LOC) 00(AND)/01(OR)/02(XOR) 0.0 to 100.0 0.0 to 100.0 0.0 to 100.0 0.0 to 100.0
Run mode edit
Hi
00 00 01 01 16 16 13 13 18 18
Alarm relay function [AM] signal selection Terminal [11] active state Alarm relay active state
X X X X
X X X X X X X X X X
00 00 01 01 02 02 03 03 18 18
C026 C028 C031 C036
X X
X X X X X X X X X X
00(FW:Forward), 01(RV:Reverse), 02-05(CF1-CF4:Multispeed command), 06(JG:Jogging), 07(DB:External DC braking), 08(SET:Second motor constants setting), 09(2CH:Second accel./decel.), 11(FRS:Free-run stop), 12(EXT:External trip), 13(USP:Unattended start protection), 15(SFT:Software lock), 16(AT:Analog input selection), 18(RS:Reset), 19(PTC:Thermistor input), 20(STA:3-wire start), 21(STP:3-wire stop), 22(F/R:3-wire fwd./rev.), 23(PID:PID On/Off), 24(PIDC:PID reset), 27(UP:Remote-controlled accel.), 28(DWN:Remote-controlled decel.), 29(UDC:Remote-controlled data clearing), 31(OPE:Operator control), 50(ADD: Frequency setpoint), 51(F-TM: Force terminal enable), 52(RDY: Quick Start Enable), 53(S-ST: Special-Set (select) 2nd Motor Data), 64(EMR:Emergency stop), 255(NO:Not selected)
Terminal [11] function
X X X
Lo
Terminal [1] function Terminal [1] function, 2nd motor Terminal [2] function Terminal [2] function, 2nd motor Terminal [3] function Terminal [3] function, 2nd motor Terminal [4] function Terminal [4] function, 2nd motor Terminal [5] function Terminal [5] function, 2nd motor
C021
X X
Allowed [ X:: Not allowed ]
C Group: Intelligent terminal functions Function Code
Run mode edit
-EF(CE)
-
02
02
-
X
0.00 0. 100. 100. 0.0 00 00
0.00 0. 100. 100. 0.0 00 00 sec msec % % V -
X X
00
00
-
X
00 01 00 0.0 0.0 0.0 0.0
00 01 00 0.0 0.0 0.0 0.0 sec sec sec sec
X X X X X X X
X X
X
X X X
Note: C014: 01 for UL version. Allowed [ X:: Not allowed ]
H Group: Motor constants functions Default Function Code
Motor constants and gain
9
Name H003 H203 H004 H204 H006 H206
Motor capacity, 1st motor Motor capacity, 2nd motor Motor poles setting, 1st motor Motor poles setting, 2nd motor Motor stabilization constant, 1st motor Motor stabilization constant, 2nd motor
Unit
Range 0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/4.0/5.5 2/4/6/8 0. to 255.
-EF(CE)
-U(UL)
Factory set 4 4 100 100
Factory set 4 4 100 100 kW kW poles poles -
Run mode edit
Lo
Hi
X X X X
X X X X
Page 11
Function List Allowed [ X:: Not allowed ]
P Group: Expansion Card Functions
Run mode edit
Default Function Code
Option Setting
Name
Range
P044
Network comm watchdog timer
P045
Inverter action on network comm error
P046 P047
Polled I/O output instance number Polled I/O input instance number
P048
Inverter action on network idle mode
P049
Network motor poles setting for RPM
Unit
0.00 to 99.99 00(Trip (Error Code E70)) 01(Decelerate to stop and trip (Error Code E70)) 02(Hold last speed), 03(Free run stop), 04(Decelerate and stop) 20/21/100 70/71/101 00(Trip (Error Code E70)) 01(Decelerate to stop and trip (Error Code E70)) 02(Hold last speed), 03(Free run stop), 04(Decelerate and stop) 00 to 38
-EF(CE)
-U(UL)
Lo
Hi
1.00
1.00 sec.
X
X
01
01
-
X
X
21 71
21 71
-
X X
X X
01
01
-
X
X
0
0
-
X
X
Note: The "P" Group parameters do not appear in the parameter list shown on the keypad display unless the expansion card is installed on the inverter.
Protective Functions Error Codes Name
Over current
Overload protection *1 Over voltage protection EEPROM error *2,3 Under-voltage error CPU error External trip USP *4 Ground fault *5 Input over-voltage Inverter thermal trip Driver error Thermistor Emergency Stop Communications error
Display on digital Display on remote operator/copy unit operator
Cause(s)
The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF.
While at constant speed During deceleration During acceleration
OC.Decel
Others
Over.C
OC.Drive
OC.Accel
When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output.
Over.L
When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor.
Over.V
When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor. A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque. The inverter trips and turns OFF its output. A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor. A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor. When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present. The inverter trips and does not go into Run Mode until the error is cleared. The inverter is protected by the detection of ground faults between the inverter output and the motor during powerup tests. This feature protects the inverter, and does not protect humans. When the input voltage is higher than the specified value, it is detected 100 seconds after powerup and the inverter trips and turns OFF its output. When the inverter internal temperature is above the threshold, the thermal sensor in the inverter module detects the excessive temperature of the power devices and trips, turning the inverter output OFF. An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause. The inverter has turned OFF the IGBT module output. When a thermistor is connected to terminals [PTC] and [CM1] and the inverter has sensed the temperature is too high, the inverter trips and turns OFF the output.
EEPROM Under.V CPU EXTERNAL USP GND.Flt OV.SRC OH FIN DRIV TH
Emergency stop signal given.
EMERGENCY
The inverter's watchdog timer for the communications network has timed out.
COMM
Note 1: Reset operations acceptable 10 seconds after the trip. Note 2: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values are still correct. Note 3: EEPROM error may occer at power-on after shutting down the power while copying data with remote operator or initializing data. Shut down the power after completing copy or initialization. Note 4: USP error occures at reseting trip after under-voltage error (E09) if USP is enabled. Reset once more to recover. Note 5: Ground fault error (E14) cannot be released with resetting. Shut the power and check wiring.
How to access the details about the present fault 1
Error code
2
1
Output frequency at trip point
2
1
Motor current at trip point
2
1
Voltage between P(+) and N(-) at trip point 1
2
2
1
Cumulative inverter RUN time at trip point
2
Cumulative power-on time at trip point
10
Page 12
Connecting Diagram Source type logic
X200
R(L1) Power source 1-/3-phase 200~240V+10%, -15% 3-phase 380~480V+10%, -15% 50/60Hz 5%
(T1) U
S(L2)
(T2) V
T/N(L3)
Motor
(T3) W
DC24V
P24 5
(+1)PD DC link choke
(+)P 4
Dynamic breaking umit (BRD)
(-)N
R1
AL1
R2
AL2 P
2 AL2 1
AL1 AL0
Intelligent relay output contacts
PCS Short bar
L
DC 0~10V(8bit) AM
DC10V
H 11 Frequency setting 1k ~2k Current input 4mA~20mA
O
Intelligent output terminal CM2
OI 10k L
250
Note 1: Common terminals are depend on logic. Terminal Common
1,2,3,4,5 Sink logic : L Source logic : PCS
H,O,OI
11
L
CM2
Note 2: Please choose proper inverter input volotage rating.
11
RB
N
3
Intelligent input terminals (5 terminals) Source type
P RB
Page 13
Connecting Diagram Sink type logic
X200
R(L1)
Power source 1-/3-phase 200~240V+10%, -15% 3-phase 380~480V+10%, -15% 50/60Hz 5%
S(L2)
(T2) V DC24V
T/N(L3) P24 Short bar
PCS 5
(T3) W
Motor
(+1)PD (+)P
DC link choke
(-)N
4
Intelligent input terminals (5 terminals) Sink type
(T1) U
3 AL2 AL1 AL0
2 1
Dynamic breaking umit (BRD) P RB RB R1 AL1 N R2 AL2 P Intelligent relay output contacts
L DC 0~10V(8bit)
AM
DC10V
H Frequency setting 1k ~2k Current input 4mA~20mA
11
O OI L
250
10k
CM2
Intelligent output terminal
Note 1: Common terminals are depend on logic. Terminal 1,2,3,4,5 H,O,OI 11 Sink logic : L Common Source logic : PCS L CM2 Note 2: Please choose proper inverter input volotage rating.
12
Page 14
Wiring and Accessories
Power Supply
Input Voltage
Fuse 200V
400V
Applicable Motor (kW(HP))
Model
Wireing Power Lines
Signal Lines
Fuse (Class J)
0.2(1/4)
X200-002NFU/SFEF
AWG 14 mm2 2.0
0.4(1/2)
X200-004NFU/SFEF
14
2.0
0.55(3/4)
X200-005SFEF
14
2.0
0.75(1)
X200-007NFU/SFEF
14
2.0
1.1(1.5)
X200-011SFEF
10
5.5
1.5(2)
X200-015NFU/SFEF
10
5.5
2.2(3)
X200-022NFU/SFEF
10
5.5
3.7(5)
X200-037LFU
12
3.5
5.5(7.5)
X200-055LFU
10
5.3
7.5(10)
X200-075LFU
8
8.4
0.4(1/2)
X200-004HFU/HFEF
16
1.25
0.75(1)
X200-007HFU/HFEF
16
1.25
6
1.5(2)
X200-015HFU/HFEF
16
1.25
10
2.2(3)
X200-022HFU/HFEF
14
2.0
3(4)
X200-030HFEF
14
2.0
4.0(5)
X200-040HFU/HFEF
14
2.0
5.5(7.5)
X200-055HFU/HFEF
12
3.3
20
7.5(10)
X200-075HFU/HFEF
12
3.3
25
18 to 28 AWG 0.14 to 0.75mm2 shelded wire
No fuse required
3
18 to 28 AWG 0.14 to 0.75mm2 shelded wire
10 15 15
Note 1: Field wiring connection must be made by a UL and c-UL listed closed-loop terminal connector sized for the wire gauge involved. Connector must be fixed using the crimping tool specified by the connector manufacturer. Note 2: Be sure to use large wire gauges for power wiring if the distance exceeds 20m (66ft). Note 3: Use 0.75mm2 /18 AWG wire for the relay terminals (AL0, AL1 and AL2) signal wire.
L1
L2
Name
Function
Input side AC reactor
This is useful in suppressing harmonics induced on the power supplylines, or when the main power voltage imbalance exceeds 3% (and power source capacity is more than 500kVA), or to smooth out line fluctuations. It also improves the power factor.
Radio noise filter
Electrical noise interference may occur on nearby equipment such as a radio receiver. This magnetic choke filter helps reduce radiat-ed noise (can also be used on output).
EMC filter
Reduces the conducted noise on the power supply wiring generated by the inverter. Connect to the inverter input side.
Radio noise filter (Capacitor filter)
This capacitor filter reduces radiated noise from the main power wires in the inverter input side.
L3 +1
+ Inverter
U(T1) V(T2) W(T3)
DC link choke
Suppresses harmonics generated by the inverter.
Braking resistor
This is useful for increasing the inverter’s control torque for high duty-cycle (on-off) applications, and improving the decelerating capability.
Braking unit Output side noise filter
Radio noise filter
IM
13
Motor
Reduces radiated noise from wiring in the inverter output side. Electrical noise interference may occur on nearby equipment such as a radio receiver. This magnetic choke filter helps reduce radiated noise (can also be used on input).
AC reactor
This reactor reduces the vibration in the motor caused by the inver-ter’s switching waveforms, by smoothing the waveforms to approximate commercial power quality. It is also useful when wiring from the inverter to the motor is more than 10m in length, to reduce harmonics.
LCR filter
Sine wave shaping filter for the output side.
Page 15
Torque characteristics/Derating Curves Torque characteristics
Base frequency = 60Hz
Base frequency = 50Hz Short time performance
Short time performance 150
150
0.2〜4kW
130
Output torque (%)
Output torque (%)
130
Continuous performance
100 95
5.5, 7.5kW
80
100 90
0.2〜4kW
Continuous performance
5.5, 7.5kW 75 55
0.2〜4kW
55 45
45 35
0.2〜4kW
35
5.5, 7.5kW
5.5, 7.5kW 1
6
20
60
1
120
5
16.7
Output frequency (Hz)
50
120
Output frequency (Hz)
Derating Curves Use the following derating curves to help determine the optimal carrier frequency setting for your inverter and find the output current derating. Be sure to use the proper curve for your particular X200 inverter model number.
Ambient temperature 40℃ max., side-by-side mounting
A
200V class
100%
037LFU
80% 75%
100%
80% 037LFU
75% 70%
60% 2
4
6
8
10
Carrier frequency(kHz)
400V class
95%
2
12
055HFEF/HFU
100%
95% 037LFU
90%
85%
80%
075HFRF 030HFEF
85% 80% 040HFEF/HFU 037HFRF
75%
6
8
10
Carrier frequency(kHz)
400V class
75%
12
055HFEF/HFU
100%
2
4
6
8
10
Carrier frequency(kHz)
400V class
12
004〜030、055、075HFEF/HFU
95%
075HFEF/HFU
90%
4
004〜015、075HFEF/HFU
% of rated output current
% of rated output current
007SFEF/NFU、 011SFEF
002〜022SFEF/NFU、 055、075LFU
200V class
65%
004〜022 HFEF/HFU
70%
% of rated output current
% of rated output current
% of rated output current
85%
90% 85%
100%
015SFEF/ NFU
95%
90%
70%
002〜004、022SFEF/NFU、 005SFEF、055LFU
200V class
075LFU
002〜022SFEF/NFU、 055,075LFU
95%
Ambient temperature 40℃ max., individual mounting
C
% of rated output current
100%
Ambient temperature 50℃ max., individual mounting
B
90% 022HFEF/HFU
85% 80%
030HFEF
75% 70%
95%
90% 040HFEF/HFU
85%
80%
040HFEF/HFU
65% 2
4
6
8
10
Carrier frequency(kHz)
12
60%
2
4
6
8
10
Carrier frequency(kHz)
12
75%
2
4
6
8
10
Carrier frequency(kHz)
12
14
Page 16
For Correct Operation Application to Motors Application to general-purpose motors Operating frequency
The overspeed endurance of a general-purpose motor is 120% of the rated speed for 2 minutes (JIS C4,004). For operation at higher than 60Hz, it is required to examine the allowable torque of the motor, useful life of bearings, noise, vibration, etc. In this case, be sure to consult the motor manufacturer as the maximum allowable rpm differs depending on the motor capacity, etc.
Torque characteristics
The torque characteristics of driving a general-purpose motor with an inverter differ from those of driving it using commercial power (starting torque decreases in particular). Carefully check the load torque characteristic of a connected machine and the driving torque characteristic of the motor.
Motor loss and temperature increase
The torque characteristics of driving a general-purpose motor with an inverter differ from those of driving it using commercial power
Noise
When run by an inverter, a general-purpose motor generates noise slightly greater than with commercial power.
Vibration
When run by an inverter at variable speeds, the motor may generate vibration, especially because of (a) unbalance of the rotor including a connected machine, or (b) resonance caused by the natural vibration frequency of a mechanical system. Particularly, be careful of (b) when operating at variable speeds a machine previously fitted with a constant speed motor. Vibration can be minimized by (1) avoiding resonance points using the frequency jump function of the inverter, (2) using a tire-shaped coupling, or (3) placing a rubber shock absorber beneath the motor base.
Power transmission mechanism
Under continued, low-speed operation, oil lubrication can deteriorate in a power transmission mechanism with an oil-type gear box (gear motor) or reducer. Check with the motor manufacturer for the permissible range of continuous speed. To operate at more than 60 Hz, confirm the machine , s ability to withstand the centrifugal force generated.
Application to special motors Gear motor
The allowable rotation range of continuous drive varies depending on the lubrication method or motor manufacturer. (Particularly in case of oil lubrication, pay attention to the low frequency range.)
Brake-equipped motor
For use of a brake-equipped motor, be sure to connect the braking power supply from the primary side of the inverter.
Pole-change motor
There are different kinds of pole-change motors (constant output characteristic type, constant torque characteristic type, etc.), with different rated current values. In motor selection, check the maximum allowable current for each motor of a different pole count. At the time of pole changing, be sure to stop the motor. Also see: Application to the 400V-class motor.
Submersible motor
The rated current of a submersible motor is significantly larger than that of the general-purpose motor. In inverter selection, be sure to check the rated current of the motor.
Explosion-proof motor
Inverter drive is not suitable for a safety-enhanced explosion-proof type motor. The inverter should be used in combination with a pressure-proof explosion-proof type of motor. *Explosion-proof verification is not available for X200 Series.
Synchronous (MS) motor High-speed (HFM) motor
In most cases, the synchronous (MS) motor and the high-speed (HFM) motor are designed and manufactured to meet the specifications suitable for a connected machine. As to proper inverter selection, consult the manufacturer.
Single-phase motor
A single-phase motor is not suitable for variable-speed operation by an inverter drive. Therefore, use a three-phase motor.
Application to the 400V-class motor A system applying a voltage-type PWM inverter with IGBT may have surge voltage at the motor terminals resulting from the cable constants including the cable length and the cable laying method. Depending on the surge current magnification, the motor coil insulation may be degraded. In particular, when a 400V-class motor is used, a longer cable is used, and critical loss can occur, take the following countermeasures: (1) install the LCR filter between the inverter and the motor, (2) install the AC reactor between the inverter and the motor, or (3) enhance the insulation of the motor coil.
Notes on Use Drive Run/Stop
Run or stop of the inverter must be done with the keys on the operator panel or through the control circuit terminal. Do not operate by installing a electromagnetic contactor (MC) in the main circuit.
Emergency motor stop
When the protective function is operating or the power supply stops, the motor enters the free run stop state. When an emergency stop is required or when the motor should be kept stopped, use of a mechanical brake should be considered.
High-frequency run
A max. 400Hz can be selected on the X200 Series. However, a two-pole motor can attain up to approx. 24,000 rpm, which is extremely dangerous. Therefore, carefully make selection and settings by checking the mechanical strength of the motor and connected machines. Consult the motor manufacturer when it is necessary to drive a standard (general-purpose) motor above 60 Hz. A full line of high-speed motors is available from Hitachi.
Installation location and operating environment Avoid installation in areas of high temperature, excessive humidity, or where moisture can easily collect, as well as areas that are dusty, subject to corrosive gasses, mist of liquid for grinding, or salt. Install the inverter away from direct sunlight in a well-ventilated room that is free of vibration. The inverter can be operated in the ambient temperature range from -10 to 50˚C.(Carrier frequency and output current must be reduced in the range of 40 to 50˚C.)
15
Page 17
For Correct Operation Main power supply
Installation of an AC reactor on the input side
In the following examples involving a general-purpose inverter, a large peak current flows on the main power supply side, and is able to destroy the converter module. Where such situations are foreseen or the connected equipment must be highly reliable, install an AC reactor between the power supply and the inverter. Also, where influence of indirect lightning strike is possible, install a lightning conductor. (A) The unbalance factor of the power supply is 3% or higher. (Note) (B) The power supply capacity is at least 10 times greater than the inverter capacity (the power supply capacity is 500 kVA or more). (C) Abrupt power supply changes are expected. Examples: (1) Several inverters are interconnected with a short bus. (2) A thyristor converter and an inverter are interconnected with a short bus. (3) An installed phase advance capacitor opens and closes. In cases (A), (B) and (C), it is recommended to install an AC reactor on the main power supply side. Note: Example calculation with VRS = 205V, VST = 201V, VTR = 200V VRS : R-S line voltage, VST : S-T line voltage, VTR : T-R line voltage Max. line voltage (min.) - Mean line voltage x100 Mean line voltage 205-202 VRS-(VRS+VST+VTR)/3 x100 = = x100 =1.5(%) 202 (VRS+VST+VTR)/3
Unbalance factor of voltage =
Using a private power generator
An inverter run by a private power generator may overheat the generator or suffer from a deformed output voltage waveform of the generator. Generally, the generator capacity should be five times that of the inverter (kVA) in a PWM control system, or six times greater in a PAM control system.
Notes on Peripheral Equipment Selection Wiring connections
Wiring between inverter and motor
(1) Be sure to connect main power wires with R(L1), S(L2), and T(L3) terminals (input) and motor wires to U(T1), V(T2), and W(T3) terminals (output). (Incorrect connection will cause an immediate failure.) (2) Be sure to provide a grounding connection with the ground terminal ( ).
Electromagnetic contactor
When an electromagnetic contactor is installed between the inverter and the motor, do not perform on-off switching during running operation.
Thermal relay
When used with standard applicable output motors (standard three-phase squirrel-cage four-pole motors), the X200 Series does not need a thermal relay for motor protection due to the internal electronic protective circuit. A thermal relay, however, should be used: • during continuous running outside a range of 30 to 60 Hz. • for motors exceeding the range of electronic thermal adjustment (rated current). • when several motors are driven by the same inverter; install a thermal relay for each motor. • The RC value of the thermal relay should be more than 1.1 times the rated current of the motor. Where the wiring length is 10 m or more, the thermal relay tends to turn off readily. In this case, provide an AC reactor on the output side or use a current sensor.
Installing a circuit breaker
Install a circuit breaker on the main power input side to protect inverter wiring and ensure personal safety. Choose an invertercompatible circuit breaker. The conventional type may malfunction due to harmonics from the inverter. For more information, consult the circuit breaker manufacturer.
IWiring distance
The wiring distance between the inverter and the remote operator panel should be 20 meters or less. When this distance isexceeded, use CVD-E (current-voltage converter) or RCD-E (remote control device). Shielded cable should be used on thewiring. Beware of voltage drops on main circuit wires. (A large voltage drop reduces torque.)
Earth leakage relay Phase advance capacitor
If the earth leakage relay (or earth leakage breaker) is used, it should have a sensitivity level of 15 mA or more (per inverter). Do not use a capacitor for power factor improvement between the inverter and the motor because the high-frequency components of the inverter output may overheat or damage the capacitor.
High-frequency Noise and Leakage Current (1) High-frequency components are included in the input/output of the inverter main circuit, and they may cause interference in a transmitter, radio, or sensor if used near the inverter. The interference can be minimized by attaching noise filters (option) in the inverter circuitry. (2) The switching action of an inverter causes an increase in leakage current. Be sure to ground the inverter and the motor.
Because a DC bus capacitor deteriorates as it undergoes internal chemical reaction, it should normally be replaced every five years. Be aware, however, that its life expectancy is considerably shorter when the inverter is subjected to such adverse factors as high temperatures or heavy loads exceeding the rated current of the inverter.The approximate lifetime of the capacitor is as shown in the figure at the right when it is used 12 hours daily (according to the " Instructions for Periodic Inspection of General-Purpose Inverter " (JEMA).)Also, such moving parts as a cooling fan should be replaced. Maintenance inspection and parts replacement must beperformed by only specified trained personnel.
Ambient temperature(˚C)
Lifetime of Primary Parts 50 40 30 2.5
5
10
Capacltor lifetime(years)
Precaution for Correct Usage • Before use, be sure to read through the Instruction Manual to insure proper use of the inverter. • Note that the inverter requires electrical wiring; a trained specialist should carry out the wiring. • The inverter in this catalog is designed for general industrial applications. For special applications in fields such as aircraft, outer space, nuclear power, electrical power, transport vehicles, clinics, and underwater equipment, please consult with us in advance. • For application in a facility where human life is involved or serious losses may occur, make sure to provide safety devices to avoid a serious accident. • The inverter is intended for use with a three-phase AC motor. For use with a load other than this, please consult with us. Information in this brochure is subject to change without notice.
16
Page 18
MEMO
17
Page 19
MEMO
18