For the Hitachi X200 Series

Page 11

xx Warnings and Cautions for Troubleshooting and Maintenance WARNING: Wait at least five (5) minutes after turning OFF the input power supply before performing maintenance or an inspection. Otherwise, there is the danger of electric shock.

… 6-2

WARNING: Make sure that only qualified personnel will perform maintenance, inspection, and part replacement. Before starting to work, remove any metallic objects from your person (wristwatch, bracelet, etc.). Be sure to use tools with insulated handles. Otherwise, there is a danger of electric shock and/or injury to personnel.

… 6-2

WARNING: Never remove connectors by pulling on its wire leads (wires for cooling fan and logic P.C.board). Otherwise, there is a danger of fire due to wire breakage and/or injury to personnel.

… 6-2

CAUTION: Do not connect the megger to any control terminals such as intelligent I/O, analog terminals, etc. Doing so could cause damage to the inverter.

… 6-10

CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has a surge protector between the main circuit terminals above and the chassis ground.

… 6-10

CAUTION: Do not connect the megger to any control circuit terminals such as intelligent I/O, analog terminals, etc. Doing so could cause damage to the inverter.

… 6-10

CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has a surge protector between the main circuit terminals above and the chassis ground.

… 6-10

HIGH VOLTAGE: Be careful not to touch wiring or connector terminals when working with the inverters and taking measurements. Be sure to place the measurement circuitry components above in an insulated housing before using them.

… 6-14

General Warnings and Cautions iv

WARNING: Never modify the unit. Otherwise, there is a danger of electric shock and/or injury. CAUTION: Withstand voltage test and insulation resistance tests (HIPOT) are executed before the units are shipped, so there is no need to conduct these tests before operation. CAUTION: Do not attach or remove wiring or connectors when power is applied. Also, do not check signals during operation. CAUTION: Be sure to connect the grounding terminal to earth ground. CAUTION: When inspecting the unit, be sure to wait five minutes after turning OFF the power supply before opening the cover.

Page 12

xi xi CAUTION: Do not stop operation by switching OFF electromagnetic contactors on the primary or secondary side of the inverter. Ground fault interrupter Power Input

Inverter L1, L2, L3

U, V, W

Motor

PCS

FW

When there has been a sudden power failure while an operation instruction is active, then the unit may restart operation automatically after the power failure has ended. If there is a possibility that such an occurrence may harm humans, then install an electromagnetic contactor (Mgo) on the power supply side, so that the circuit does not allow automatic restarting after the power supply recovers. If the optional remote operator is used and the retry function has been selected, this will also cause automatic restarting when a Run command is active. So, please be careful. CAUTION: Do not insert leading power factor capacitors or surge absorbers between the output terminals of the inverter and motor. Surge absorber

Ground fault interrupter Power Input

Inverter L1, L2, L3

U, V, W

GND lug

Motor

Leading power factor capacitor

When there has been a sudden power failure while an operation instruction is active, then the unit may restart operation automatically after the power failure has ended. If there is a possibility that such an occurrence may harm humans, then install an electromagnetic contactor (Mgo) on the power supply side, so that the circuit does not allow automatic restarting after the power supply recovers. If the optional remote operator is used and the retry function has been selected, this will also cause automatic restarting when a Run command is active. So, please be careful. CAUTION: MOTOR TERMINAL SURGE VOLTAGE SUPPRESSION FILTER (For the 400V CLASS) In a system using an inverter with the voltage control PWM system, a voltage surge caused by the cable constants such as the cable length (especially when the distance between the motor and the inverter is 10m or more) and cabling method may occur at the motor terminals. A dedicated filter of the 400V class for suppressing this voltage surge is available. Be sure to install a filter in this situation.

Page 13

xiixii CAUTION: EFFECTS OF POWER DISTRIBUTION SYSTEM ON INVERTER In the case below involving a general-purpose inverter, a large peak current can flow on the power supply side, sometimes destroying the converter module: 1. The unbalance factor of the power supply is 3% or higher. 2. the power supply capacity is at least 10 times greater than the inverter capacity (or the power supply capacity is 500kVA or more). 3. Abrupt power supply changes are expected, due to conditions such as: a. Several inverters are interconnected with a short bus. b. A thyristor converter and an inverter are interconnected with a short bus. c. An installed phase advance capacitor opens and closes. Where these conditions exist or when the connected equipment must be highly reliable, you MUST install an input side AC-reactor of 3% (at a voltage drop at rated current) with respect to the supply voltage on the power supply side. Also, where the effects of an indirect lightening strike are possible, install a lightening conductor. CAUTION: SUPPRESSION FOR NOISE INTERFERENCE FROM INVERTER The inverter uses many semiconductor switching elements such as transistors and IGBTs. Thus, a radio receiver or measuring instrument located near the inverter is susceptible to noise interference. To protect the instruments from erroneous operation due to noise interference, they should be used well away from the inverter. It is also effective to shield the whole inverter structure. The addition of an EMI filter on the input side of the inverter also reduces the effect of noise from the commercial power line on external devices. Note that the external dispersion of noise from the power line can be minimized by connecting an EMI filter on the primary side of the inverter. x SFEF model has integrated filter complies to EN61800-3 category C1. x HFEF model has integrated filter complies to EN61800-3 category C2.

noise

EMI Filter

Inverter

R1

R2

L1

U

S1

S2

L2

V

T1

T2

L3

W

EMI Filter

Motor

Inverter Motor

Completely ground the enclosure panel, metal screen, etc. with as short a wire as possible.

Remote Operator

Grounded frame Conduit or shielded cable -- to be grounded

CAUTION: When the EEPROM error E08 occurs, be sure to confirm the setting values again. CAUTION: When using normally closed active state settings (C011 to C015) for externally commanded Forward or Reverse terminals [FW] or [RV], the inverter may start automatically when the external system is powered OFF or disconnected from the inverter! So do not use normally closed active state settings for Forward or Reverse terminals [FW] or [RV] unless your system design protects against unintended motor operation.

Page 14

xiii xiii CAUTION: In all the instrumentations in this manual, covers and safety devices are occasionally removed to describe the details. While operating the product, make sure that the covers and safety devices are placed as they were specified originally and operate it according to the instruction manual. CAUTION: Do not discard the inverter with household waste. Contact an industrial waste management company in your area who can treat industrial waste without polling the environment. UL“ Cautions, Warnings and Instructions xii

Warnings and Cautions for Troubleshooting and Maintenance The warnings and instructions in this section summarizes the procedures necessary to ensure an inverter installation complies with Underwriters Laboratories£ guidelines. WARNING: “USE 60/75qC Cu wire only” or equivalent. For models X200-005S, -007S, -011S, -022S, -007N, -015N, -015L, -022L, -037L, -055L, -075L. WARNING: “USE 75qC Cu wire only” or equivalent. For models X200-002S, -004S, -002N, -004N, -002L, -004L, -007L, -022H, -030H, -037H, -040H, -055H, 075H. WARNING: “USE 60qC Cu wire only” or equivalent. For models X200-004H, -007H, and –015H. WARNING: “Open Type Equipment” WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical amperes, 240V maximum when protected by Class CC, G, J or R fuses or circuit breaker having an interrupting rating not les than 100,000 rms symmetrical amperes, 240 volts maximum”. For models with suffix S, N or L. WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical amperes, 480V maximum when protected by Class CC, G, J or R fuses or circuit breaker having an interrupting rating not les than 100,000 rms symmetrical amperes, 480 volts maximum.” For models with suffix H. WARNING: “Install device inn pollution degree 2 environment.” WARNING: “Maximum Surrounding Air Temperature 50qC”. or equivalent. WARNING: “Caution-Risk of electric discharge time is at least 5 minutes.” WARNING: “Solid state motor overload protection is provided in each model”. WARNING: “Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electric Code and any additional local codes” or equivalent.

Page 15

xiv xiv Terminal Tightening Torque and Wire Size The wire size range and tightening torque for field wiring terminals are presented in the tables below. Input Voltage

200V Class

400V Class

Motor Output kW

HP

0.2 0.4 0.55 0.75 1.1 1.5 2.2 3.7 5.5 7.5 0.4 0.75 1.5 2.2 3.0 4.0 5.5 7.5

1/4 1/2 3/4 1 1 1/2 2 3 5 7 1/2 10 1/2 1 2 3 4 5 7 1/2 10

Inverter Model X200-002SFEF/NFU X200-004SFEF/NFU X200-005SFEF X200-007SFEF/NFU X200-011SFEF X200-015SFEF/NFU X200-022SFEF/NFU X200-037LFU X200-055LFU X200-075LFU X200-004HFEF/HFU X200-007HFEF/HFU X200-015HFEF/HFU X200-022HFEF/HFU X200-030HFEF X200-040HFEF/HFU X200-055HFEF/HFU X200-075HFEF/HFU

Terminal Connector Logic and Analog connectors Relay connector

Wiring Size Range (AWG) 30 – 16 30 – 14

Power Terminal Wiring Size Range (AWG)

Torque Ft-lbs

(N-m)

0.6

0.8

0.9

1.2

10 12

0.9

1.2

8

1.5

2.0

0.9

1.2

1.5

2.0

14 (75qC only) 12

16 (60qC only) 14 (75qC only) 10

Torque Ft-lbs (N-m) 0.16 – 0.19 0.22 – 0.25 0.37 – 0.44 0.5 – 0.6

Wire Connectors WARNING: Field wiring connections must be made by a UL Listed and CSA certified ring lug terminal connector sized for the wire gauge being used. The connector must be fixed using the crimping tool specified by the connector manufacturer. Terminal (ring lug) Cable support

Cable

Page 16

xv xv Circuit Breaker and Fuse Sizes The inverter’s connections to input power must include UL Listed inverse time circuit breakers with 600V rating, or UL Listed fuses as shown in the table below. Input Voltage

Single/ ThreePhase 200V

ThreePhase 400V

Inverter Model X200-002SFEF/NFU X200-004SFEF/NFU X200-005SFEF X200-007SFEF/NFU X200-011SFEF X200-015SFEF/NFU X200-022SFEF/NFU X200-037LFU X200-055LFU X200-075LFU X200-004HFEF/HFU X200-007HFEF/HFU X200-015HFEF/HFU X200-022HFEF/HFU X200-030HFEF X200-040HFEF/HFU X200-055HFEF/HFU X200-075HFEF/HFU

Circuit Breaker / Fuse

Ratings (A) 10 15

Inverse time circuit Breaker

20 30 40 50 3 6 10

Distribution Fuse (Class J) 15 20 25

Motor Overload Protection Hitachi X200 inverters provide solid state motor overload protection, which depends on the proper setting of the following parameters: x

B012 “electronic overload protection” x B212 “electronic overload protection, 2nd motor” Set the rated current [Amperes] of the motor(s) with the above parameters. The setting range is 0.2 * rated current to 1.0 * rated current. WARNING: When two or more motors are connected to the inverter, they cannot be protected by the electronic overload protection. Install an external thermal relay on each motor.

Page 17

xvi xvi

Table of Contents Safety Messages Hazardous High Voltage...............................................................................................................i General Precautions – Read These First! ................................................................................. ii Index to Warnings and Cautions in This Manual ....................................................................iv General Warnings and Cautions.................................................................................................x UL Cautions, Warnings and Instructions .............................................................................. xiii Circuit Breaker and Fuse Sizes ................................................................................................xv

Table of Contents Revisions ............................................................................................................................... xviii Contact Information ................................................................................................................xix

Chapter 1: Getting Started Introduction ............................................................................................................................ 1-2 X200 Inverter Specifications .................................................................................................. 1-5 Introduction to Variable-Frequency Drives ........................................................................ 1-19 Frequently Asked Questions ................................................................................................ 1-24

Chapter 2: Inverter Mounting and Installation Orientation to Inverter Features ........................................................................................... 2-2 Basic System Description ....................................................................................................... 2-7 Step-by-Step Basic Installation ............................................................................................. 2-8 Powerup Test ......................................................................................................................... 2-24 Using the Front Panel Keypad ............................................................................................ 2-26

Chapter 3: Configuring Drive Parameters Choosing a Programmable Device ......................................................................................... 3-2 Using the Keypad Devices ..................................................................................................... 3-3 “D” Group: Monitoring Functions .......................................................................................... 3-6 “F” Group: Main Profile Parameters ..................................................................................... 3-9 “A” Group: Standard Functions ........................................................................................... 3-10 “B” Group: Fine Tuning Functions ...................................................................................... 3-32 “C” Group: Intelligent Terminal Functions ......................................................................... 3-49 “H” Group: Motor Constants Functions .............................................................................. 3-65

Page 18

xvii xvii Chapter 4: Operations and Monitoring Introduction ............................................................................................................................ 4-2 Connecting to PLCs and Other Devices ................................................................................ 4-4 Control Logic Signal Specifications ....................................................................................... 4-6 Intelligent Terminal Listing ................................................................................................... 4-7 Using Intelligent Input Terminals ........................................................................................ 4-8 Using Intelligent Output Terminals .................................................................................... 4-36 Analog Input Operation ....................................................................................................... 4-55 Analog Output Operation ..................................................................................................... 4-57 PID Loop Operation .............................................................................................................. 4-58 Configuring the Inverter for Multiple Motors .................................................................... 4-60

Chapter 5: Inverter System Accessories Introduction ............................................................................................................................ 5-2 Component Description .......................................................................................................... 5-3 Dynamic Braking .................................................................................................................... 5-5

Chapter 6: Troubleshooting and Maintenance Troubleshooting ...................................................................................................................... 6-2 Monitoring Trip Events, History, & Conditions .................................................................... 6-5 Restoring Factory Default Settings ....................................................................................... 6-8 Maintenance and Inspection .................................................................................................. 6-9 Warranty ............................................................................................................................... 6-16

Appendix A: Glossary and Bibliography Glossary ...................................................................................................................................A-2 Bibliography ............................................................................................................................A-8

Appendix B: ModBus Network Communications Introduction ............................................................................................................................B-2 Connecting the Inverter to ModBus ......................................................................................B-3 Network Protocol Reference ...................................................................................................B-6 ModBus Data Listing ...........................................................................................................B-19

Appendix C: Drive parameter Setting Tables Introduction ............................................................................................................................C-2 Parameter Settings for Keypad Entry ..................................................................................C-2

Appendix D: CE-EMC Installation Guidelines CE-EMC Installation Guidelines ...........................................................................................D-2 Hitachi EMC Recommendations ............................................................................................D-5

Index

Page 19

xviii xviii Revisions Revision History Table No.

Revision Comments Initial release of manual NT301X This manual is valid with QRG (NT3011X) and Caution (NTZ301X) Description was reviewed. Page xiii: Corrected UL warning description Pages 1-5 to 1-9: corrected watt loss values Page 1-9: Added torque characteristics Pages 1-12 to 1-17: Added derating curves Page 3-16: Corrected manual torque boost explanation Page 3-34: Corrected electronic thermal explanation Page 3-39: Corrected parameter range of b050 Page 3-46 and C-6: Corrected run mode edit of b055 and b056 Pages 4-5 to 4-11: Corrected terminal name of PCS Pages 4-32 to 4-35: Added explanation and certificate Pages 4-40 to 4-41: Corrected the timing chart of FA2 Page 4-61: Removed H007 (no H007 on X200 inverter) Page 6-6: Corrected thermistor connected terminal number (#6Æ#5) of E21 description Page 6-16: Corrected warranty period Page D-4: Corrected EMC installation condition Other minor corrections throughout. Added 5.5kW and 7.5kW information. Pages xiii, xiv, xv, 1-7, 1-9, 1-15, 1-18, 3-65, 5-6, 5-7, 6-11

Date of Issue March 2007

Operation Manual No. NT301X

March 2007 Sept 2007

NT301XA NT301XC

Page 20

xix xix Contact Information

Hitachi America, Ltd. Power and Industrial Division 50 Prospect Avenue Tarrytown, NY 10591 U.S.A. Phone: +1-914-631-0600 Fax: +1-914-631-3672

Hitachi Australia Ltd. Level 3, 82 Waterloo Road North Ryde, N.S.W. 2113 Australia Phone: +61-2-9888-4100 Fax: +61-2-9888-4188

Hitachi Europe GmbH Am Seestern 18 D-40547 Dusseldorf Germany Phone: +49-211-5283-0 Fax: +49-211-5283-649

Hitachi Industrial Equipment Systems Co., Ltd. AKS Building, 3, kanda Neribei-cho Chiyoda-ku, Tokyo, 101-0022 Japan Phone: +81-3-4345-6910 Fax: +81-3-4345-6067

Hitachi Asia Ltd. 16 Collyer Quay #20-00 hitachi Tower, Singapore 049318 Singapore Phone: +65-538-6511 Fax: +65-538-9011

Hitachi Industrial Equipment Systems Co., Ltd. Narashino Division 1-1, Higashi-Narashino 7-chome Narashino-shi, Chiba 275-8611 Japan Phone: +81-47-474-9921 Fax: +81-47-476-9517

Hitachi Asia (Hong Kong) Ltd. 7th Floor, North Tower World Finance Centre, Harbour City Canton Road, Tsimshatsui, Kowloon Hong Kong Phone: +852-2735-9218 Fax: +852-2735-6793

NOTE: To receive technical support for the Hitachi inverter you purchased, contact the Hitachi inverter dealer from whom you purchased the unit, or the sales office or factory contact listed above. Please be prepared to provide the following inverter nameplate information: 1. Model 2. Date of purchase 3. Manufacturing number (MFG No.) 4. Symptoms of any inverter problem If any inverter nameplate information is illegible, please provide your Hitachi contact with any other legible nameplate items. To reduce unpredictable downtime, we recommend that you stock a spare inverter.