Page 241

Appendix A

Appendix A

A−6

Process Variable

A physical property of a process that is of interest because it affects the quality of the primary task accomplished by the process. For an industrial oven, temperature is the process variable. See also PID Loop and Error.

PWM

Pulse-width modulation: A type of AC adjustable frequency drive that accomplishes frequency and voltage control at the output section (inverter) of the drive. The drive output voltage waveform is at a constant amplitude, and by “chopping” the waveform (pulsewidthmodulating), the average voltage is controlled. The chopping frequency is sometimes called the Carrier Frequency.

Reactance

The impedance of inductors and capacitors has two components. The resistive part is constant, while the reactive part changes with applied frequency. These devices have a complex impedance (complex number), where the resistance is the real part and the reactance is the imaginary part.

Rectifier

An electronic device made of one or more diodes that converts AC power into DC power. Rectifiers are usually used in combination with capacitors to filter (smooth) the rectified waveform to closely approximate a pure DC voltage source.

Regenerative Braking

A particular method of generating reverse torque to a motor, an inverter will switch internally to allow the motor to become a generator and will either store the energy internally, deliver the braking energy back to the main power input, or dissipate it with a resistor.

Regulation

The quality of control applied to maintain a parameter of interest at a desired value. Usually expressed as a percent (±) from the nominal, motor regulation usually refers to its shaft speed.

Reverse Torque

The torque applied in the direction opposite to motor shaft rotation. As such, reverse torque is a decelerating force on the motor and its external load.

Rotor

The windings of a motor that rotate, being physically coupled to the motor shaft. See also Stator.

Saturation Voltage

For a transistor semiconductor device, it is in saturation when an increase in input current no longer results in an increase in the output current. The saturation voltage is the voltage drop across the device. The ideal saturation voltage is zero.

Sensorless Vector Control

A technique used in some variable-frequency drives (featured in some other Hitachi inverter model families) to rotate the force vector in the motor without the use of a shaft position sensor (angular). Benefits include an increase in torque at the lowest speed and the cost savings from the lack of a shaft position sensor.

Page 242

A−7

The setpoint is the desired value of a process variable of interest. See also Process Variable (PV) and PID Loop.

Single-phase power

An AC power source consisting of Hot and Neutral wires. An Earth Ground connection usually accompanies them. In theory, the voltage potential on Neutral stays at or near Earth Ground, while Hot varies sinusoidally above and below Neutral. This power source is named Single Phase to differentiate it from three-phase power sources. Some Hitachi inverters can accept single phase input power, but they all output three-phase power to the motor. See also Three-phase.

Slip

The difference between the theoretical speed of a motor at no load (determined by its inverter output waveforms) and the actual speed. Some slip is essential in order to develop torque to the load, but too much will cause excessive heat in the motor windings and/or cause the motor to stall.

Squirrel Cage

A “nick-name” for the appearance of the rotor frame assembly for an AC induction motor.

Stator

The windings in a motor that are stationary and coupled to the power input of the motor. See also Rotor.

Tachometer

1. A signal generator usually attached to the motor shaft for the purpose of providing feedback to the speed controlling device of the motor. 2. A speed-monitoring test meter that may optically sense shaft rotation speed and display it on a readout.

Thermal Switch

An electromechanical safety device that opens to stop current flow when the temperature at the device reaches a specific temperature threshold. Thermal switches are sometimes installed in the motor in order to protect the windings from heat damage. The inverter can use thermal switch signals to trip (shut down) if the motor overheats. See also Trip.

Thermistor

A type of temperature sensor that changes its resistance according to its temperature. The sensing range of thermistors and their ruggedness make them ideal for motor overheating detection. Hitachi inverters have built-in thermistor input circuits, which can detect an overheated motor and shut off (trip) the inverter output.

Three-phase power

An AC power source with three Hot connections that have phase offsets of 120 degrees is a 3-phase power source. Usually, Neutral and Earth Ground wires accompany the three Hot connections. Loads may be configured in a delta or Y configuration. A Y-connected load such as an AC induction motor will be a balanced load; the currents in all the Hot connections are the same. Therefore, the Neutral connection is theoretically zero. This is why inverters that generate 3-phase power for motors do not generally have a Neutral connection to the motor. However, the Earth Ground connection is important for safety reasons, and is provided.

Appendix A A Appendix

Setpoint (SP)

Page 243

Appendix A

Appendix A

A−8

Torque

The rotational force exerted by a motor shaft. The units of measurement consist of the distance (radius from shaft center axis) and force (weight) applied at that distance. Units are usually given as pound-feet, ounce-inches, or Newton-meters.

Transistor

A solid state, three-terminal device that provides amplification of signals and can be used for switching and control. While transistors have a linear operating range, inverters use them as high-powered switches. Recent developments in power semiconductors have produced transistors capable of handling high voltages and currents, all with high reliability. The saturation voltage has been decreasing, resulting in less heat dissipation. Hitachi inverters use state-of-theart semiconductors to provide high performance and reliability in a compact package. See also IGBT and Saturation Voltage.

Trip Event

An event that causes the inverter to stop operation is called a “trip” event (as in tripping a circuit breaker). The inverter keeps a history log of trip events. They also require an action to clear.

Watt Loss

A measure of the internal power loss of a component, the difference between the power it consumes and what its output delivers. An inverter’s watt loss is the input power minus the power delivered to the motor. The watt loss is typically highest when an inverter is delivering its maximum output. Therefore, watt loss is usually specified for a particular output level. Inverter watt loss specifications are important when designing enclosures.

Bibliography Title Variable Speed Drive Fundamentals, 2nd Ed. Electronic Variable Speed Drives

Hitachi Inverter Technical Guide Book

Author and Publisher Phipps, Clarence A. The Fairmont Press, Inc. / Prentice-Hall, Inc. 1997 Brumbach, Michael E. Delmar Publishers 1997 ISBN 0-8273-6937-9 Published by Hitachi, Ltd. Japan 1995 Publication SIG-E002

Page 244

B−1

ModBus Network Communications page

-

Introduction...................................................................................... 2

-

Connecting the Inverter to ModBus ............................................... 3

-

Network Protocol Reference ........................................................... 6

-

ModBus Data Listing ..................................................................... 19

Appendix B Appendix B

In This Appendix…

B

Page 245

B−2

Introduction X200 Series inverters have built-in RS-485 serial communications, featuring the ModBus RTU protocol. The inverters can connect directly to existing factory networks or work with new networked applications, without any extra interface equipment. The specifications for X200 serial communications are in the following table.

Appendix B

Appendix B

Item

Specifications

User-selectable

Transmission speed Communication mode Character code LSB placement Electrical interface

4800 / 9600 / 19200 bps Asynchronous Binary Transmits LSB first RS-485 differential transceiver

Data bits

8-bit (ModBus RTU mode)

(ASCII mode not available)

Parity

None / even / odd

Stop bits Startup convention Wait time for response

1 or 2 bits One-way start from host device 0 to 1000 msec.

Connections Connector

Station address numbers from 1 to 32 RS45 modular jack Overrun, Fleming block check code, CRC-16, or horizontal parity

Error check

9 U U U U 9 9 U 9 9

The network diagram below shows a series of inverters communicating with a host computer. each inverter must have a unique address, from 1 to 32, on the network. In a typical application, a host computer or controller is the master and each of the inverter(s) or other devices is a slave.

1

X200

2

X200

32

X200

Page 246

B−3

Connecting the Inverter to ModBus Follow these steps in this section to connect the inverter to the ModBus network. 1. Open Serial Port Cover - The inverter keypad has a hinged dust cover protecting the serial port connector. Lift the cover from the bottom edge, and tilt upward as shown below.

RJ45 connector

3. Cable Wiring - The inverter communications port uses RS485 differential transceiver. The pinout is shown to the right and listed below. Be sure the cable connection you make matches the diagram. Pin 1 2 3 4 5 6 7 8

Symbol

SP SN

Description Not used. Do not connect Not used. Do not connect Not used. Do not connect Not used. Do not connect Send data positive Send data negative Not used. Do not connect Not used. Do not connect

12345678

Appendix B Appendix B

2. Modular Interconnect Removal - With the serial port cover opened, notice the RJ45 modular connector behind it. Connect the serial cable and engage the locking tab in the connector.

Page 247

B−4

ModBus Network

Appendix B

Appendix B

4. Terminate Network Wiring - The RS-485 wiring must be terminated at each physical end to suppress electrical reflections and help decrease transmission errors. The X200 communications port does not include a termination resistor. Therefore, you will need to add termination to the inverter if it is at the end of the network wiring. Select termination resistors that match the characteristic impedance of the network cable. The diagram below shows a network with the needed termination resistor at each end.

SP

SN

Host device

5. Set Inverter OPE/485 Switch - The inverter serial port accepts a connection to either the inverter keypad or the network. After removing the keypad, you will need to set a DIP switch S7 on the inverter to configure the port for ModBus communications. Setting the switch will require removing the front housing cover. Remember to power OFF the inverter before removing the cover or changing the DIP switch S7 setting. Refer to “Front Housing Cover” on page 2–3 for detailed instructions. Locate the OPE/485 DIP switch as shown in the figure below. Carefully move the switch to the upper position labeled “485” (slide in direction of arrow). Then replace the front housing cover.

SW7 485 SW8 ON OPE OFF

At this point the electrical network connection is complete. The next step will show how to configure parameters and settings related to ModBus communications.

Page 248

B−5

6. Inverter Parameter Setup - The inverter has several settings related to ModBus communications. The table below lists them together. The Required column indicates which parameters must be set properly to allow communications. You may need to refer to the host computer documentation in order to match some of its settings. Func. Code A001

Name

Required

Frequency source setting

A002

Run command source setting

9 B089

Monitor display select for networked inverter

C070

Selection of OPE/ModBus

C071

Communication speed selection

9 9

C072

Node allocation

C074

Communication parity selection

9 9

C075

Communication stop bit selection

C076

Communication error select

9

C077

Communication error time-out

C078

Communication wait time

9

00}Keypad potentiometer 01}Control terminal 02}Function F001 setting 03}ModBus network input 10}Calculate function output 01}Control terminal 02}Run key on keypad, or digital operator 03} ModBus network input 01}Output frequency monitor 02}Output current monitor 03}Rotation direction monitor 04}Process variable (PV), PID feedback monitor 05}Intelligent input terminal status 06}Intelligent output terminal status 07}Scaled output frequency monitor 02...OPE or option 03...ModBus (485) 04}4800 bps 05}9600 bps 06}19200 bps Network address, range is 1 to 32 00}No parity 01}Even parity 02}Odd parity Range is 1 to 2 00}Trip (Error code E60) 01}Decelerate to a stop and trip (Error code E60) 02}Disable 03}Free run stop (coasting) 04}Decelerate to a stop Comm. Watchdog timer period, range is 0.00 to 99.99 sec. Time the inverter waits after receiving a message before it transmits. Range is 0. to 1000. ms

NOTE: When you edit and store any of the parameters above, the inverter causes it to take effect immediately. ModBus transmission occurs only after you set the OPE/485 DIP switch to the “485” position and turn on the inverter again. Note that parameters C070 to C078 cannot be changed via the network. To edit them, you must disconnect the inverter from the ModBus and wait for about 30sec until the inverter’s internal keypad begin functioning. Then use this keypad to edit the parameters. Please don’t connect other external programming devices to RJ45 connector, because the bus mode is in RS485 mode. It may cause the inverter or external programming devices to be damaged when DIP switch is in “485” position.

Appendix B Appendix B

9

Settings

Page 249

B−6

Network Protocol Reference Transmission procedure

Appendix B

Appendix B

The transmission between the external control equipment and the inverter takes the procedure below.

x Query - A frame sent from the external control equipment to the inverter x Response - A frame returned from inverter to the external control equipment The inverter returns the response only after the inverter receives a query from the external control equipment and does not output the response positively. Each frame is formatted (with commands) as follows: Frame Format Header (silent interval) Slave address Function code Data Error check Trailer (silent interval)

Message Configuration: Query Slave address: x This is a number of 1 to 32 assigned to each inverter (slave). (Only the inverter having the address given as a slave address in the query can receive the query.) x When slave address “0” is specified, the query can be addressed to all inverters simultaneously. (Broadcasting) x In broadcasting, you cannot call and loop back data.

Page 250

B−7

Data: x A function command is set here. x The data format used in the X200 series is corresponding to the Modbus data format below. Name of Data Coil Holding Register

Description Binary data that can be referenced and changed ( 1 bit long) 16-bit data that can be referenced and changed

Specify a function you want to make the inverter execute. Function codes available to the X200 series are listed below.

Function Code

Function

01h 03h 05h 06h 08h 0Fh 10h

Read Coil Status Read Holding Resistor Write in Coil Write in Holding Register Loopback Test Write in Coils Write in Registers

Maximum data size Maximum number of (bytes available data elements available per message) per message 4 32 coils (in bits) 4 4 registers (in bytes) 1 1 coil (in bits) 1 1 register (in bytes)

4 32 coils (in bits) 4 4 registers (in bytes)

Error check: Modbus-RTU uses CRC (Cyclic Redundancy Check) for error checking. x The CRC code is 16-bit data that is generated for 8-bit blocks of arbitrary length. x The CRC code is generated by a generator polynomial CRC-16 (X16+ X15+ X2+ 1). Header and trailer (silent interval): Latency is the time between the reception of a query from the master and transmission of a response from the inverter. x 3.5 characters (24 bits) are always required for latency time. If the latency time shorter than 3.5 characters, the inverter returns no response. x The actual transmission latency time is the sum of silent interval (3.5 characters long) + C078 (transmission latency time).

Appendix B Appendix B

Function code: