Page 261

B−18

Store New Register Data (ENTER command)

Appendix B

Appendix B

After being written in a selected holding register by the Write in Holding Register command (06h) or in selected holding registers by the Write in Holding Registers command (10h), new data is temporary and still outside the storage element of the inverter. If power to the inverter is shut off, this new data is lost and the previous data returns. The ENTER command is used to store this new data in the storage element of the inverter. Follow the instructions below to submit the ENTER command. Submitting an ENTER Command: x Write any data in all memory (of a holding register at 0900h) by the Write in Holding Register command [06h].

NOTE: The ENTER command takes much time to run. You can check its progress by monitoring the Data Writing signal (of a coil at 001Ah). NOTE: The service life of the storage element of the inverter is limited (to about 100,000 write operations). Frequent use of the ENTER command may shorten its service life.

Page 262

B−19

ModBus Data Listing ModBus Coil List The following tables list the primary coils for the inverter interface to the network. The table legend is given below. x Coil Number - The network register address offset for the coil. The coil data is a single bit (binary) value. x R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data x Description - The meaning of each of the states of the coils List of Coil Numbers Coil Number 0000h 0001h

(Reserved) Run command

0002h

FW/RV command

0003h

External trip (EXT)

0004h

Trip reset (RS)

0005h 0006h 0007h 0008h 0009h 000Ah 000Bh 000Dh 000Eh

(Reserved) (Reserved) Intelligent input terminal 1 Intelligent input terminal 2 Intelligent input terminal 3 Intelligent input terminal 4 Intelligent input terminal 5 (Not used) Run/Stop status

000Fh

FW/RV status

0010h

Inverter ready

0011h 0012h 0013h

(Reserved) (Reserved) (Reserved)

Name

R/W

Description

R

R/W 0…Stop 1…Run (enable when A003=03) R/W 0…RV 1…FW (enable when A003=03) R/W 0…No trip event 1…Trip occurred R/W 0…No reset condition 1…Reset R

R

R/W 0…OFF *1 R/W 1…ON R/W R/W R/W

R 0…Stop (corresponds to D003 monitor) 1…Run R 0…FW 1…RV R 0…Not ready 1…Ready R

R

R

Appendix B Appendix B x Name - The functional name of the coil

Page 263

B−20

List of Coil Numbers Coil Number 0014h

Appendix B

R/W

Alarm signal

R R R R

0019h 001Ah

PID deviation signal Overload signal Frequency arrival signal (set frequency or above) Frequency arrival signal (at constant speed) Run Mode signal Data writing

001Bh 001Ch 001Dh 001Eh 001Fh

CRC error Overrun error Framing error Parity error Check sum error

R R R R R

0015h 0016h 0017h

Appendix B

Name

0018h

Description 0…Normal 1…Trip 0…OFF 1…ON

R R R

0…Normal status 1…Writing 0…No error *2 1…Error

Note 1:

ON usually when either the control circuit terminal board or a coil is ON. Among control circuit terminal board (intelligent input terminals) and coils, the control circuit terminal board has a high priority. If the master cannot reset the coil ON status due to a transmission line break, please turn ON and OFF the control circuit terminal board to make the coil to OFF status.

Note 2:

The content of a transmission error is held until the error is reset. (The error can be reset while the inverter is running.)

Page 264

B−21

ModBus Holding Registers The following tables list the holding registers for the inverter interface to the network. The table legend is given below. x Function Code - The inverter’s reference code for the parameter or function (same as inverter keypad display) x Name - The standard functional name of the parameter or function for the inverter x Description - How the parameter or setting works (same as Chapter 3 description). x Reg. - The network register address offset for the value. Some values have a highbyte and low-byte address. x Range - The numerical range for the network value that is sent and/or received TIP: The network values are binary integers. Since these values cannot have an embedded decimal point, for many parameters it represents the actual value (in engineering units) multiplied by a factor of 10 or 100. Network communications must use the listed range for network data. The inverter automatically divides received values by the appropriate factor in order to establish the decimal point for internal use. Likewise, the network host computer must apply the same factor when it needs to work in engineering units. However, when sending data to the inverter, the network host computer must scale values to the integer range listed for network communications. x Resolution - This is the quantity represented by the LSB of the network value, in engineering units. When the network data range is greater than the inverter’s internal data range, this 1-bit resolution will be fractional. List of Holding Registers Func. Code

Name Output frequency command

Inverter status

Process Variable (PV)

R/W

Description

R/W Inverter output frequency (set A001=03 to enable this network register), range is 0.0 to 400.0 Hz R 00...Initial status 01...(Reserved) 02...Stop Mode 03...Run Mode 04...Free-run stop (FRS) 05...Jogging 06...DC braking 07...Retry 08...Trip alarm 09...Under-voltage R/W PID loop PV value from the network (set A076=02 to enable this setting), range is 0.0 to 100.0%

Reg. 0002h

Network Data Range Res. 0 to 4000 0.1 Hz

0003h

0 to 9

0005h

0 to 1000

0.1%

Appendix B Appendix B x R/W - The read-only(R) or read-write access(R/W) permitted to the data in the inverter

Page 265

B−22

The following table lists holding registers for the “D” Group Monitor Functions. List of Holding Registers

Appendix B

Appendix B

Func. Code D001

Name

R/W

Description

Output frequency monitor

R

D002

Output current monitor *1

R

D003

Rotation direction monitor

R

Real-time display of output frequency to motor, from 0.0 to 400.0 Hz Filtered display of output current to motor (100 ms internal filter time constant), range is 0 to 200% of inverter rated current Three different indications: 00...Stop 01...Forward 02...Reverse Displays the scaled PID process variable (feedback) value (A075 is scale factor), range is 0.00 to 9999.00 Displays the state of the intelligent input terminals [x], Bit 0 = [1] to Bit 4 = [5] Displays the state of the intelligent output terminals [x], Bit 0 = [11], Bit 1 = (Don’t Care), Bit 2 = [AL] Displays the output frequency scaled by the constant in B086. Decimal point indicates range: 0.00 to 39960.00 Voltage of output to motor, range is 0.00 to 200.00% Displays total time the inverter has been in RUN mode in hours. Range is 0 to 999999

D004 Process Variable (PV), (high) PID feedback monitor D004 (low) D005 Intelligent input terminal status D006

Intelligent output terminal status

D007 Scaled output (high) frequency monitor D007 (low) D013 Output voltage monitor D016 Cumulative operation (high) RUN time monitor D016 (low) D017 Cumulative power-on (high) time monitor D017 (low) D018 Fin temperature monitor D080 Trip counter

R R R

R

R R R R R R R R R

D102

DC voltage monitor

R

D104

Electronic thermal monitor

R

Note 1:

Reg. 1002h

Network Data Range Res. 0 to 4000 0.1 Hz

1003h

0 to 2000

0.1%

1004h

0,1,2

1005h

0 to 999900

0.00% times const.

1007h

0 to 63

1008h

0 to 7

1009h

0 to 3996000

0.01 Hz times const.

0 to 20000 0 to 999999

0.01%

1006h

100Ah 100Ch 100Eh

1 hour

100Fh

Displays total time the inverter has been in RUN mode in hours. Range is 0 to 999999

1010h

Display the Fin temperature in 0.0~200.0qC Number of trip events, range is 0 to 65535 Voltage of DC bus inside inverter,Range is 0.0 to 999.9 Accumulated value of electronic thermal detection, range is from 0.0 to 100.0

116Ah

0 to 999999

1 hour

0 to 2000

0.1qC

0011h 0 to 65535

1011h

116Ch

0 to 9999

1 trip event 0.1 V

116Dh

0 to 1000

0.1 %

Assume that the inverter current rating is 1000 (for D002).

Page 266

B−23

List of Holding Registers Func. Code

Name

Trip monitor 1

D082

Trip monitor 2

D083

Trip monitor 2

R R R R R R R R R R R R R R R R R R R R R R R R

Description Trip monitor 1: factor code Frequency Current Voltage Run time (high) Run time (low) ON time (high) ON time (low) Trip monitor 2: factor code Frequency Current Voltage Run time (high) Run time (low) ON time (high) ON time (low) Trip monitor 3: factor code Frequency Current Voltage Run time (high) Run time (low) ON time (high) ON time (low)

Network Data Reg. Res. 0012h

0014h 0.1 Hz 0016h 0.1A 0017h 1.V 0018h 1. h 0019h 001Ah 1. h 001Bh 001Ch

001Eh 0.1 Hz 0020h 0.1A 0021h 1.V 0022h 1. h 0023h 1. h 0024h 0025h 0026h

0028h 0.1 Hz 002Ah 0.1A 002Bh 1.V 002Ch 1. h 002Dh 002Eh 1. h 002Fh

Appendix B Appendix B

D081

R/W

Page 267

B−24

Appendix B

Appendix B

List of Holding Registers Func. Code F002 (high) F002 (low) F202 (high) F202 (low) F003 (high) F003 (low) F203 (high) F203 (low) F004

Name Acceleration (1) time setting *1

R/W

Description

R/W Standard default acceleration, range is 0.01 to 3000 sec. R/W

Reg. 1014h 1015h

Acceleration (1) time setting, 2nd motor *1

R/W Standard default acceleration, 2nd motor, range is 0.01 to 3000 R/W sec.

1501h

Deceleration (1) time setting *1

R/W Standard default deceleration, range is 0.01 to 3000 sec. R/W

1016h

R/W Standard default deceleration, 2nd motor, range is 0.01 to 3000 R/W sec.

1503h

R/W Two options; select codes: 00...Forward 01...Reverse

1018h

Deceleration (1) time setting, 2nd motor *1

Keypad Run key routing

Note 1:

Network Data Range Res. 1 to 0.01 sec. 300000

1 to 300000

0.01 sec.

1 to 300000

0.01 sec.

1 to 300000

0.01 sec.

0, 1

1502h

1017h

1504h

When the value is 10000 (100.0 seconds), a value in the second decimal place is ignored.

Page 268

B−25

The following table lists the holding registers for the “A” Group Standard Functions. List of Holding Registers Func. Code A001

Name Frequency source setting

Run command source setting

A003

Base frequency setting

A203

Base frequency setting, 2nd motor Maximum frequency setting Maximum frequency setting, 2nd motor [AT] selection

A004 A204 A005

A011

O–L input active range start frequency

A012

O–L input active range end frequency

A013

O–L input active range start voltage

A014

O–L input active range end voltage

A015

O–L input start frequency enable

A016

External frequency filter time constant

Description

R/W Five options; select codes: 00...Keypad potentiometer 01...Control terminal 02...Function F001 setting 03...ModBus network input 10...Calculate function output R/W Three options; select codes: 01...Control terminal 02...Run key on keypad, or digital operator 03...ModBus network input R/W Settable from 30 Hz to the maximum frequency R/W Settable from 30 Hz to the 2nd maximum frequency R/W Settable from the base frequency up to 400 Hz R/W Settable from the 2nd base frequency up to 400 Hz R/W Five options, select codes: 00... Select between [O] and [OI] at [AT] 02... Select between [O] and keypad potentiometer 03... Select between [OI] and keypad potentiometer 04... Only [O] input active 05... Only [OI] input active R/W The output frequency corresponding to the analog input range starting point, Range is 0.0 to 400.0 R/W The output frequency corresponding to the analog input range ending point, range is 0.0 to 400.0 R/W The starting point (offset) for the active analog input range, range is 0. to 100 R/W The ending point (offset) for the active analog input range, range is 0. to 100. R/W Two options; select codes: 00...Use offset (A011 value) 01...Use 0 Hz R/W Range n = 1 to 16, where n = number of samples for average. Set 17 to use 16-samples for avg., plus deadband +0.1/-0.2Hz

Reg. 1019h

101Ah

Network Data Range Res. 0 to 3, 10

1, 2, 3

101Bh 30 to max. freq. 150Ch 30 to max. freq.2 101Ch 30 to 400

1 Hz 1 Hz

150Dh

30 to 400

1 Hz

101Dh

0, 2, 3, 4, 5

1020h

0 to 4000

0.1 Hz

1022h

0 to 4000

0.1 Hz

1023h

0 to 100

1%

1024h

0 to 100

1%

1025h

0, 1

1026h

1 to 17

1 sample

1 Hz

Appendix B Appendix B

A002

R/W

Page 269

B−26

List of Holding Registers

Appendix B

Appendix B

Func. Code A020

Name Multi-speed 0 setting

R/W

Description

R/W Defines the first speed of a multi-speed profile, range is 0.0 / start frequency to 400 Hz A020 = Speed 0 (1st motor) R/W Defines the first speed of a multi-speed profile, range is 0.0 / start frequency to 400 Hz A220 = Speed 0 (2nd motor) R/W R/W R/W R/W R/W R/W Defines 15 more speeds, R/W range is 0.0 / start frequency to R/W 400 Hz. A021= Speed 1... R/W A035 = Speed 15 R/W R/W R/W R/W R/W R/W R/W Defines limited speed for jog, range is 0.00 / start frequency to 9.99 Hz R/W Define how end of jog stops the motor; three options: 00...Free-run stop 01...Controlled deceleration 02...DC braking to stop R/W Two options: R/W 00...Manual torque boost 01...Automatic torque boost R/W Can boost starting torque between 0 and 20% above normal R/W V/f curve, range is 0.0 to 20.0% R/W Sets the frequency of the V/f breakpoint A in graph (top of R/W previous page) for torque boost, range is 0.0 to 50.0%

A220

Multi-speed 0 setting 2nd motor

A021 A022 A023 A024 A025 A026 A027 A028 A029 A030 A031 A032 A033 A034 A035 A038

Multi-speed 1 setting Multi-speed 2 setting Multi-speed 3 setting Multi-speed 4 setting Multi-speed 5 setting Multi-speed 6 setting Multi-speed 7 setting Multi-speed 8 setting Multi-speed 9 setting Multi-speed 10 setting Multi-speed 11 setting Multi-speed 12 setting Multi-speed 13 setting Multi-speed 14 setting Multi-speed 15 setting Jog frequency setting

A039

Jog stop mode

A041 A241

Torque boost select Torque boost select, 2nd motor Manual torque boost value Manual torque boost value, 2nd motor Manual torque boost frequency adjustment Manual torque boost frequency adjustment, 2nd motor V/f characteristic curve R/W Two available V/f curves; two select codes: selection V/f characteristic curve R/W 00...Constant torque 01...Reduced torque selection, 2nd motor 06...Reduced torque1 V/f gain setting R/W Sets voltage gain of the inverter, range is 20. to 100.% V/f gain setting, 2nd R/W motor

A042 A242 A043 A243

A044 A244

A045 A245

Reg. 1029h

Network Data Range Res. 0 / start 0.1 Hz freq. to 4000

150Fh

0 / start 0.1 Hz freq. to 4000

102Bh 102Dh 102Fh 1031h 1033h 1035h 1037h 1039h 103Bh 103Dh 103Fh 1041h 1043h 1045h 1047h 1048h

0 / start 0.1 Hz freq. to 4000

1049h

0 / start 0.01 Hz freq. to 999 0, 1, 2

104Ah 1510h

0, 1

104Bh

0 to 200

0.1 %

0 to 500

0.1 %

0, 1, 6

20 to 100

1%

1511h 104Ch 1512h

104Dh 1513h

104Eh 1514h

Page 270

B−27

List of Holding Registers Func. Code A051

A052

A054 A055

A056

A061

A261

A062

A262

A063, A065, A067

A064, A066, A068

DC braking enable

R/W

Description

R/W Two options; select codes: 00...Disable 01... Enable 02... Frequency detection DC braking frequency R/W The frequency at which DC setting braking begins, range is from the start frequency (B082) to 60 Hz DC braking wait time R/W The delay from the end of controlled deceleration to start of DC braking (motor free runs until DC braking begins), range is 0.0 to 5.0 sec. DC braking force for R/W Level of DC braking force, deceleration settable from 0 to 100% DC braking time for R/W Sets the duration for DC deceleration braking, range is 0.0 to 60.0 seconds DC braking / edge or R/W Two options; select codes: level detection for [DB] 00... Edge detection input 01... Level detection Frequency upper limit R/W Sets a limit on output frequency setting less than the maximum frequency (A004). Range is from frequency lower limit (A062) to maximum frequency (A004). 0.0.. setting is disabled >0.1 setting is enabled Frequency upper limit R/W Sets a limit on output frequency setting, 2nd motor less than the maximum frequency (A204). Range is from frequency lower limit (A262) to maximum frequency (A204). 0.0.. setting is disabled >0.1 setting is enabled Frequency lower limit R/W Sets a limit on output frequency setting greater than zero. Range is start frequency (B082) to frequency upper limit (A061) 0.0 setting is disabled >0.0 setting is enabled Frequency lower limit R/W Sets a limit on output frequency setting, 2nd motor greater than zero. Range is start frequency (B082) to frequency upper limit (A261) 0.0 setting is disabled >0.0 setting is enabled Jump (center) R/W Up to 3 output frequencies can be frequency setting defined for the output to jump past to avoid motor resonances (center frequency) Range is 0.0 to 400.0 Hz Jump (hysteresis) R/W Defines the distance from the frequency width center frequency at which the setting jump around occurs Range is 0.0 to 10.0 Hz

Reg. 1051h

Network Data Range Res. 0, 1, 2

1052h (B082 x 10) 0.1 Hz to 600

1053h

0 to 50

1054h

0 to 100

1%

1055h

0 to 600

0.1 sec

1056h

0, 1

105Ah (A062 x 10) 0.1 Hz to (A004 x 10), 0=disable >1=enable

1517h (A262 x 10) to (A204 x 10), 0=disable >1=enable

105Bh (B082 x 10) 0.1 Hz to (A061 x 10), 0=disable >1=enable 1518h (B082 x 10) to (A261 x 10), 0=disable >1=enable 105Dh 1060h 1063h

0 to 4000

0.1 Hz

105Eh 1061h 1064h

0 to 100

0.1 Hz

Appendix B Appendix B

A053

Name