The text of a manual · part 28 of 31

X200 Series Inverter Instruction Manual, pages 271 to 280

Pages 271 to 280 of 305

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 271

B−28

Appendix B

Appendix B

List of Holding Registers Func. Code A071

PID enable

A072

PID proportional gain

A073

A075

PID integral time constant PID derivative time constant PV scale conversion

A076

PV source setting

A077

Reverse PID action

A078

PID output limit

A081

AVR function select

A082

AVR voltage select

A085

Operation mode selection

A086

Energy saving mode tuning

A074

Name

R/W

Description

R/W Enables PID function, two option codes: 00 }PID Disable 01 }PID Enable R/W Proportional gain has a range of 0.2 to 5.0 R/W Integral time constant has a range of 0.0 to 150 seconds R/W Derivative time constant has a range of 0.0 to 100 seconds R/W Process Variable (PV), scale factor (multiplier), range of 0.01 to 99.99 R/W Selects source of Process Variable (PV), option codes: 00 }[OI] terminal (current in) 01 }[O] terminal (voltage in) 02 }ModBus network 10 }Calculate function output R/W Two option codes: 00 }PID input = SP-PV 01 }PID input = -(SP-PV) R/W Sets the limit of PID output as percent of full scale, range is 0.0 to 100.0% R/W Automatic (output) voltage regulation, selects from three type of AVR functions, three option codes: 00 }AVR enabled 01 }AVR disabled 02 }AVR enabled except during deceleration R/W 200V class inverter settings: 00}200 01}215 02}220 03}230 04}240 400V class inverter settings: 00}380 01}400 02}415 03}440 04}460 05}480 R/W Two option codes: 00}Normal operation 01}Energy-saver operation R/W Range is 0.0 to 100 %

Reg. 1068h

Network Data Range Res. 0, 1

1069h

2 to 50

0.1

106Ah

0 to 1500

0.1 sec

106Bh

0 to 1000

0.1 sec

106Ch

1 to 9999

0.01

106Dh

0, 1, 2, 3

106Eh

0, 1

106Fh

0 to 1000

0.1 %

1070h

0, 1, 2

1071h

0 to 5

1072h

0, 1

1073h

0 to 1000

0.1 %

Page 272

B−29

List of Holding Registers

A294

A095

A295

A096

A296

A097

A098

A101

A102

A103

Name

R/W

Description

Network Data Range Res. 1 to 0.01 sec 300000 *1 1075h

Reg. 1074h

Acceleration (2) time setting

R/W Duration of 2nd segment of acceleration, range is: R/W 0.01 to 3000 sec.

Acceleration (2) time setting, 2nd motor

R/W Duration of 2nd segment of acceleration, 2nd motor, range is: R/W 0.01 to 3000 sec.

Deceleration (2) time setting

R/W Duration of 2nd segment of deceleration, range is: R/W 0.01 to 3000 sec.

1076h

R/W Duration of 2nd segment of deceleration, 2nd motor, range is: R/W 0.01 to 3000 sec.

151Bh

R/W Two options for switching from 1st to 2nd accel/decel: 00 }2CH input from terminal 01 }Transition frequency Select method to R/W Two options for switching from switch to Acc2/Dec2 1st to 2nd accel/decel: profile, 2nd motor 00}2CH input from terminal 01}Transition frequency (2nd motor) Acc1 to Acc2 frequency R/W Output frequency at which transition point Accel1 switches to Accel2, range is 0.0 to 400.0 Hz Acc1 to Acc2 frequency R/W Output frequency at which transition point, 2nd Accel1 switches to Accel2, 2nd motor motor, range is 0.0 to 400.0 Hz Dec1 to Dec2 frequency R/W Output frequency at which transition point Decel1 switches to Decel2, range is 0.0 to 400.0 Hz Dec1 to Dec2 frequency R/W Output frequency at which transition point, 2nd Decel1 switches to Decel2, 2nd motor motor, range is 0.0 to 400.0 Hz Acceleration curve R/W Set the characteristic curve of selection Acc1 and Acc2, two options: 00}linear 01}S-curve Deceleration curve R/W Set the characteristic curve of selection Dec1 and Dec2, two options: 00}linear 01}S-curve [OI]-[L] input active R/W The output frequency range start frequency corresponding to the analog input range starting point, range is 0.0 to 400.0 Hz [OI]-[L] input active R/W The output frequency range end frequency corresponding to the current input range ending point, range is 0.0 to 400.0 Hz [OI]-[L] input active R/W The starting point (offset) for the range start current current input range, range is 0. to 100.%

Deceleration (2) time setting, 2nd motor Select method to switch to Acc2/Dec2 profile

1 to 300000 *1

0.01 sec

1 to 300000 *1

0.01 sec

0.01 sec

151Ch

1 to 300000 *1

1078h

0, 1

0 to 4000

0.1 Hz

0 to 4000

0.1 Hz

107Dh

0, 1

107Eh

0, 1

1080h

0 to 4000

0.1 Hz

1082h

0 to 4000

0.1 Hz

1083h

0 to 100

1%

1519h 151Ah

1077h

151Dh

107Ah

151Fh

107Ch

1521h

Appendix B Appendix B

Func. Code A092 (high) A092 (low) A292 (high) A292 (low) A093 (high) A093 (low) A293 (high) A293 (low) A094

Page 273

B−30

List of Holding Registers

Appendix B

Appendix B

Func. Code A104

Name [OI]-[L] input active range end voltage

A105

[OI]-[L] input start frequency enable

A141

A input select for calculate function

A142

B input select for calculate function

A143

Calculation symbol

A145

ADD frequency

A146

ADD direction select

A151

POT active range start frequency

A152

POT input active range end frequency

A153

POT input active range start POT input active range end POT input start frequency enable

A154 A155

Note 1:

R/W

Description

R/W The ending point (offset) for the current input range, range is 0. to 100.% R/W Two options; select codes: 00 }Use offset (A101 value) 01 }Use 0Hz R/W Five options: 00}Digital operator 01}Keypad potentiometer 02}[O] input 03}[OI] input 04}Network variable R/W Five options: 00}Digital operator 01}Keypad potentiometer 02}[O] input 03}[OI] input 04}Network variable R/W Calculates a value based on the A input source (A141 selects) and B input source (A142 selects). Three options: 00}ADD (A input + B input) 01}SUB (A input - B input) 02}MUL (A input * B input) R/W An offset value that is applied to the output frequency when the [ADD] terminal is ON. Range is 0.0 to 400.0 Hz R/W Two options: 00}Plus (adds A145 value to the output frequency setting) 01}Minus (subtracts A145 value from the output frequency etting) R/W The output frequency corresponding to the POT range starting point, range is 0.0 to 400.0 Hz R/W The output frequency corresponding to the POT range ending point, range is 0.0 to 400.0 Hz R/W The starting point (offset) for the POT range, range is 0. to 100.% R/W The ending point (offset) for the POT range, range is 0. to 100.% R/W Two options; select codes: 00}Use offset (A151 value) 01}Use 0Hz

Reg. 1084h

Network Data Range Res. 0 to 100 1%

1085h

0, 1

108Eh

0 to 4

108Fh

0 to 4

1090h

0, 1, 2

1091h

0 to 4000

0.1 Hz

1093h

0, 1

1095h

0 to 4000

0.1 Hz

1097h

0 to 4000

0.1 Hz

1098h

0 to 100

1%

1099h

0 to 100

1%

109Ah

0, 1

When the value is 10000 (100.0 seconds), a value in the second decimal place is ignored. (for A092/A292 and A093/A293).

Page 274

B−31

The following table lists the holding registers for the “B” Group Fine Tuning Functions. List of Holding Registers Func. Code B001

B003

B004

B005

B011

B012 B212

B013 B213

Selection of automatic restart mode

R/W

Description

R/W Select inverter restart method, Four option codes: 00}Alarm output after trip, no automatic restart 01}Restart at 0Hz 02}Resume operation after frequency matching 03}Resume previous freq. after freq. matching, then decelerate to stop and display trip info Allowable underR/W The amount of time a power voltage power failure input under-voltage can occur time without tripping the power failure alarm. Range is 0.3 to 25 sec. If under-voltage exists longer than this time, the inverter trips, even if the restart mode is selected. Retry wait time before R/W Time delay after under-voltage motor restart condition goes away, before the inverter runs motor again. Range is 0.3 to 100 seconds. Instantaneous power R/W Two option codes: failure / under-voltage 00}Disable trip alarm enable 01}Enable Number of restarts on R/W Two option codes: power failure / under00}Restart 16 times voltage trip events 01}Always restart Start freq to be used in R/W Three option codes: case of freq pull-in 00}freq at previous shutoff restart 01}start from max. Hz 02}start from set frequency Level of electronic R/W Set a level between 20% and 100% for the rated inverter thermal setting Level of electronic R/W current. thermal setting, 2nd motor Electronic thermal R/W Select from three curves, option characteristic codes: *1 Electronic thermal R/W 00}Reduced torque 1 01}Constant torque characteristic, 2nd motor 02} Reduced torque 2

Reg. 10A5h

Network Data Range Res. 0, 1, 2, 3

10A6h

3 to 250

0.1 sec

10A7h

3 to 1000

0.1 sec

10A8h

0, 1

10A9h

0, 1

1170

0, 1, 2

10ADh

2000 to 10000

0.01 %

0, 1, 2

1527h

10AEh 1528h

Appendix B Appendix B

B002

Name

Page 275

B−32

List of Holding Registers

Appendix B

Appendix B

Func. Code B021

Name Overload restriction operation mode

B221

Overload restriction operation mode, 2nd motor

B022

Overload restriction level setting

B222

Overload restriction level setting, 2nd motor Deceleration rate at overload restriction Deceleration rate at overload restriction, 2nd motor Source of overload restriction selection

B023 B223

B028

B228

B029

B030

Source of overload restriction selection, 2nd motor Deceleration rate of frequency pull-in restart setting Current level of frequency pull-in restart setting

B031

Software lock mode selection

B050

Selection of the non stop operation

B051

Non stop operation start voltage setting

R/W

Description

R/W Select the operation mode during overload conditions, three options, option codes: 00}Disables 01}Enabled for acceleration and constant speed 02}Enabled for constant speed only R/W Sets the level for overload restriction, between 20% and 150% of the rated current of the R/W inverter, setting resolution is 1% of rated current

Reg. 10B5h

Network Data Range Res. 0, 1, 2

1529h

10B6h

2000 to 15000

0.01%

1 to 300

0.1 sec

0, 1

1171h

1 to 30000

0.1 sec

1172h

200 to 20000

0.01%

10BCh

0, 1, 2, 3

10C9h

0, 1

152Ah

R/W Sets the deceleration rate when inverter detects overload, range R/W is 0.1 to 30.0, resolution 0.1

10B7h

R/W Two option codes: 00}set value of B022 01}[O] input R/W Two option codes: 00}set value of B222 01}[O] input R/W Sets the deceleration rate when frequency pull-in restart, range is 0.1 to 3000.0, resolution 0.1 R/W Sets the current level of frequency pull-in restart, range is 0.2*inverter rated current to 2.0*inverter rated current, resolution 0.1 R/W Prevents parameter changes, in four options, option codes: 00}all parameters except B031 are locked when [SFT] terminal is ON 01}all parameters except B031 and output frequency F001 are locked when [SFT] terminal is ON 02}all parameters except B031 are locked 03}all parameters except B031 and output frequency F001 are locked 10}High level access including B031 R/W Two option codes: 00}Disabled 01}Enabled R/W Setting of DC bus voltage to start non stop operation. Range is 0.0 to 1000.0

10BBh

152Bh

152Ch

10CAh 0 to 10000

0.1 V

Page 276

B−33

List of Holding Registers Func. Code B052

B053

B054

B055

B080

B082

B083

B084

B085

OV-LAD Stop level of non stop operation setting Deceleration time of non stop operation setting Frequency width of quick deceleration setting DC bus AVR P-gain

R/W

Description

R/W Setting the OV-LAD stop level of non stop operation. Range is 0.0 to 1000.0 R/W Range is 0.1 to 3000

R/W Setting of the first quick deceleration width. Range is 0.0 to 10.0 R/W Proportional gain adjustment for DC bus AVR function. Range is: 0.2 to 5.0 DC bus AVR I-time R/W Integration time adjustment for DC bus AVR function. Range is: 0.0 to 150.0 [AM]analog signal gain R/W Adjust of analog output at terminal [AM], range is 0 to 255 Start frequency R/W Sets the starting frequency for adjustment the inverter output, range is 0.5 to 9.9 Hz Carrier frequency R/W Sets the PWM carrier (internal setting switching frequency), range is 2.0 to 12.0 kHz Initialization mode R/W Select the type of initialization to (parameters or trip occur, three option codes: history) 00}Trip history clear 01}Parameter initialization 02} Trip history clear and parameter initialization Country for R/W Select default parameter values initialization for country on initialization, three option codes: 00}Japan 01}Europe 02}US

Network Data Reg. Range Res. 10CBh 0 to 10000 0.1 V

10CCh 1 to 30000

0.1 sec

10CEh

0 to 100

0.1 Hz

1173h

2 to 50

0.1

1174h

0 to 1500

0.1s

10CFh

0 to 255

10D1h

5 to 99

0.1 Hz

10D2h

20 to 120

0.1 Hz

10D3h

0, 1, 2

10D4h

Appendix B

B056

Name

Page 277

B−34

List of Holding Registers Func. Name Code B086 Frequency scaling conversion factor B087

Appendix B

B089

B091

B092

B130

B131

Description

R/W Specify a constant to scale the displayed frequency for D007 monitor, range is 0.1 to 99.9 STOP key enable R/W Select whether the STOP key on the keypad is enabled, two option codes: 00}Enabled 01}Disabled Restart mode after R/W Selects how the inverter resumes FRS operation with free-run stop (FRS) is cancelled, two options: 00}Restart from 0Hz 01}Restart from frequency detected from real speed of motor (frequency matching) Monitor display R/W Selects the parameter displayed on the select for networked keypad display when the inverter is inverter networked, 7 options: 01}Output frequency monitor 02}Output current monitor 03}Rotation direction monitor 04}Process variable (PV), PID feedback monitor 05}Intelligent input terminal status 06}Intelligent output terminal status 07}Scaled output frequency monitor Stop mode selection R/W Select how the inverter stops the motor, two option codes: 00}DEC (decelerate to stop) 01}FRS (free run to stop) Cooling fan control R/W Selects when the fan is ON per inverter operation, three options: 00}Fan is always ON 01}Fan is ON during run, OFF during stop (5 min. delay from ON to OFF) 02}Fan is temperature controlled Over-voltage R/W Pauses deceleration ramp when DC bus LADSTOP enable voltage rises above threshold level, in order to avoid over-voltage trip. Two option codes: 00}Disable 01}Enable Over-voltage R/W Sets the threshold level for over-voltage LADSTOP level LADSTOP. When the DC bus voltage is above the threshold value, the inverter stops deceleration until the DC bus voltage is less than the threshold setting again. Two voltage ranges with 1V resolution: 330 to 395V (200V class) 660 to 790V (400V class)

Network Data Reg. Range Res. 10D5h 1 to 999 0.1

10D6h

0, 1

10D7h

0, 1

10D8h

1 to 7

10DAh

0, 1

10DBh

0, 1, 2

10F5h

0, 1

10F6h 330 to 395, 660 to 790

1V

Appendix B

B088

R/W

Page 278

B−35

List of Holding Registers Func. Name Code B133 DC bus AVR selection

B140

B150

B151

Description

R/W Two option codes: 00}Disabled 01}Enabled Threshold voltage of R/W Setting of threshold voltage of DC bus DC bus AVR setting voltage to start DC bus AVR function. Range is: 200V class}330 to 395 400V class}660 to 790 Over-current trip R/W Two option codes: suppression 00}Disable 01}Enable Carrier mode R/W Automatically reduces the carrier frequency as the ambient temperature increases. 00}Disable 01}Enable Selection of RDY R/W Select Ready function. function 00}Disable 01}Enable

Note 1:

Network Data Reg. Range Res. 1176h 0, 1

1177h 330 to 395, 660 to 790

1V

10F7h

0, 1

10F8h

0, 1

10F9h

0, 1

Assume that the inverter current rating is 10000 (for B013/B213).

Appendix B

Appendix B

B134

R/W

Page 279

B−36

The following table lists the holding registers for the “C” Group Intelligent Input Functions. List of Holding Registers Func. Name Code C001 Terminal [1] function C201 Terminal [1] function, 2nd motor C002 Terminal [2] function

R/W R/W

C202

R/W

Appendix B

C203 C004 C204 C005 C205 C011 C012 C013 C014 C015 C021 C026 C028

Terminal [3] function, 2nd motor Terminal [4] function Terminal [4] function, 2nd motor Terminal [5] function Terminal [5] function, 2nd motor Terminal [1] active state Terminal [2] active state Terminal [3] active state Terminal [4] active state Terminal [5] active state Terminal [11] function Alarm relay terminal function [AM] signal selection

C031

Terminal [11] active state

C036

Alarm relay active state

C038

Output mode of low load detection signal

C039

Low load detection level

C041

Overload level setting

C241

Overload level setting, 2nd motor Frequency arrival setting for acceleration

C042

C043

Frequency arrival setting for deceleration

Description

R/W

R/W R/W

See “Input Terminal Configuration” on page 3-49

R/W R/W R/W

Network Data Reg. Range Res. 1103h 0, 1, 2, 3,

1532h 4, 5, 6, 7, 8, 9, 11, 1104h 12, 13, 15, 16, 1533h 18, 19, 20, 21, 1105h 22, 23, 1534h 24, 27, 28, 29, 1106h 31, 50, 1535h 51, 52, 53, 64, 255 1107h

R/W

1536h

R/W Select logic conversion, two option R/W codes: R/W 00}normally open [NO] R/W 01}normally closed [NC] R/W R/W See “Output Terminal R/W Configuration” on page 3-54

110Bh 0, 1 110Ch 0, 1 110Dh 0, 1 110Eh 0, 1 110Fh 0, 1 1114h 0, 1, 2, 3, 4, 5, 6, 7, 1119h 8, 9, 10, 43 111Bh 0, 1

R/W Two available functions: 00}motor speed 01}motor current R/W Select logic conversion: 111Dh 0, 1 00}normally open [NO] 01}normally closed [NC] R/W Select logic conversion: 1122h 0, 1 00}normally open [NO] 01}normally closed [NC] R/W Three option codes: 1178h 0, 1, 2 00}Disabled 01}During acceleration, deceleration and constant speed 02}During constant speed only R/W Set the level of low load detection, 1179h 0 to range is 0.0 to 2.0*rated current 20000 R/W Sets the overload signal level 1124h 0 to between 0% and 200% (from 0 to two 20000 R/W time the rated current of the 153Ah inverter) R/W Sets the frequency arrival setting 1126h 0 to 4000 threshold for the output frequency *1 during acceleration, range is 0.0 to 400.0 Hz R/W Sets the frequency arrival setting 1128h 0 to 4000 threshold for the output frequency during deceleration, range is 0.0 to 400.0 Hz

0.01% 0.01%

0.1 Hz

0.1 Hz

Appendix B

C003

Terminal [2] function, 2nd motor Terminal [3] function

R/W

Page 280

B−37

List of Holding Registers

C052

PID FBV function high limit

C053

PID FBV function variable low limit

C070

Selection of OPE / ModBus

C071

Communication speed selection Node allocation Communication parity selection Communication stop bit selection Communication error select Communication error time-out Communication wait time O input span calibration

C072 C074 C075 C076 C077 C078 C081

C082

C086

C091

C101

R/W

Description

R/W Sets the allowable PID loop error magnitude (absolute value), SP-PV, range is 0.0 to 100%, resolution is 0.1% R/W When the PV exceeds this value, the PID loop turns OFF the PID second stage output, range is 0.0 to 100% R/W When the PV goes below this value, the PID loop turns ON the PID second stage output, range is 0.0 to 100% R/W Two option codes: 02}OPE or option 03}ModBus (485)

Network Data Reg. Range Res. 1129h 0 to 1000 0.1 %

112Eh 0 to 1000

0.1 %

112Fh 0 to 1000

0.1 %

1137h

2, 3

1138h

1139h 113Bh

113Ch

113Dh

113Eh

113Fh

NOTE: These network settings are not accessible to ModBus. Use the inverter keypad or digital operator to edit. Refer to “Network Communication Settings” on page 3–60.

R/W Scale factor between the external frequency command on terminals L–O (voltage input) and the frequency output, range is 0.0 to 200% OI input span calibration R/W Scale factor between the external frequency command on terminals L–OI (voltage input) and the frequency output, range is 0.0 to 200% AM offset calibration R/W Offset adjustment of AM output. Range is 0.0 to 10.0 Adjust together with B080 (AM gain adjustment) Debug mode enable Displays debug parameters. Two option codes: 00}Disable 01}Enable Up/Down memory mode Controls speed setpoint for the selection inverter after power sycle. Two option codes: 00}Clear last frequency (return to default frequency F001) 01}Keep last frequency adjusted by UP/DWN

1141h 0 to 2000

0.1 %

1142h 0 to 2000

0.1 %

1145h

0 to 100

0.1 V

1149h

0, 1

Appendix B

Appendix B

Func. Name Code C044 PID deviation level setting