X200 Series Inverter Instruction Manual, pages 291 to 300

Pages 291 to 300 of 305

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 291

C−8

Intelligent Terminal Functions

Appendix C

Appendix C

“C” Group Parameters Func. Code C001 C201 C002 C202 C003 C203 C004 C204 C005 C205 C011 C012 C013 C014 C015 C021 C026 C028 C031 C036 C038

Name

C039

Terminal [1] function Terminal [1] function, 2nd motor Terminal [2] function Terminal [2] function, 2nd motor Terminal [3] function Terminal [3] function, 2nd motor Terminal [4] function Terminal [4] function, 2nd motor Terminal [5] function Terminal [5] function, 2nd motor Terminal [1] active state Terminal [2] active state Terminal [3] active state Terminal [4] active state Terminal [5] active state Terminal [11] function Alarm relay terminal function [AM] signal selection Terminal [11] active state Alarm relay active state Output mode of low load detection signal Low load detection level

C041

Overload level setting

C241

Overload level setting, 2nd motor

C042

Frequency arrival setting for acceleration Frequency arrival setting for deceleration PID deviation level setting PID FBV function high limit PID FBV function variable low limit Selection of OPE / ModBus Communication speed selection Node allocation Communication parity selection Communication stop bit selection Communication error select Communication error time-out Communication wait time O input span calibration OI input span calibration

C043 C044 C052 C053 C070 C071 C072 C074 C075 C076 C077 C078 C081 C082

Default Setting -FE -FU (EU) (USA) 00 00 00 00 01 01 01 01 02 16 02 16 03 13 03 13 18 18 18 18 00 00 00 00 00 00 00 01 00 00 01 01 05 05 00 00 00 00 01 01 01 01 Rated current for each inverter model Rated current for each inverter model Rated current for each inverter model 0.0 0.0

B031 =10 U U U U U U U U U U U U U U U U U 9 U U 9 9 9 9 9

0.0

0.0

9

3.0 100.0 0.0 02 06 1. 00 1 02 0.00 0. 100.0 100.0

3.0 100.0 0.0 02 04 1. 00 1 02 0.00 0. 100.0 100.0

9 9 9 9 9 9 9 9 9 9 9 9 9

User Setting

Page 292

C−9

“C” Group Parameters Func. Code C086 C091 C101 C102 C141 C142 C143 C144 C145 C148 C149

Name AM offset calibration Debug mode enable Up/Down memory mode selection Reset selection Input A select for logic output Input B select for logic output Logic function select Terminal [11] ON delay Terminal [11] OFF delay Output relay ON delay Output relay OFF delay

Default Setting -FE -FU (EU) (USA) 0.0 0.0 00 00 00 00 00 00 00 00 01 01 00 00 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

B031 =10

User Setting

9 9 9 9 U U U 9 9 9 9

“H” Group Parameters Func. Name Code H003 Motor capacity H203

Motor capacity, 2nd motor

H004 H204 H006 H206

Motor poles setting Motor poles setting, 2nd motor Motor stabilization constant Motor stabilization constant, 2nd motor

Default Setting -FE -FU (EU) (USA) Specified by the capacity of each inverter model 4 4 4 4 100 100 100 100

B031 =10

User Setting

U U U U 9 9

Expansion Card Functions “P” parameters will be appeared when the expansion option is connected. “P” Group Parameters Default Setting B031 Func. -FE -FU =10 Name Code (EU) (USA) U P044 Network comm. Watchdog timer 1.00 1.00 U P045 Inverter action on network comm error 01 01 U P046 Polled I/O output instance number 21 21 U P047 Polled I/O input instance number 71 71 U P048 Inverter action on network idle mode 01 01 U P049 Network motor poles setting for RPM 0 0

User Setting

AppendixAppendix C C

Motor Constants Functions

Page 293

This page is a scan with no text; see it in the PDF.

Page 294

D−1

CE-EMC Installation Guidelines In This Appendix…

D page

-

CE-EMC Installation Guidelines...................................................... 2

-

Hitachi EMC Recommendations ..................................................... 5

Appendix D

Page 295

D−2

CE-EMC Installation Guidelines You are required to satisfy the EMC directive (89/336/EEC) when using an X200 inverter in an EU country. To satisfy the EMC directive and to comply with standard, follow the guidelines in this section. 1. As user you must ensure that the HF (high frequency) impedance between adjustable frequency inverter, filter, and ground is as small as possible. x Ensure that the connections are metallic and have the largest possible contact areas (zinc-plated mounting plates). 2. Avoid conductor loops that act like antennas, especially loops that encompass large areas. x Avoid unnecessary conductor loops. x Avoid parallel arrangement of low-level signal wiring and power-carrying or noise-prone conductors. 3. Use shielded wiring for the motor cable and all analog and digital control lines.

Appendix D x Allow the effective shield area of these lines to remain as large as possible; i.e., do not strip away the shield (screen) further away from the cable end than absolutely necessary. x With integrated systems (for example, when the adjustable frequency inverter is communicating with some type of supervisory controller or host computer in the same control cabinet and they are connected at the same ground + PE-potential), connect the shields of the control lines to ground + PE (protective earth) at both ends. With distributed systems (for example the communicating supervisory controller or host computer is not in the same control cabinet and there is a distance between the systems), we recommend connecting the shield of the control lines only at the end connecting to the adjustable frequency inverter. If possible, route the other end of the control lines directly to the cable entry section of the supervisory controller or host computer. The shield conductor of the motor cables always must connected to ground + PE at both ends. x To achieve a large area contact between shield and ground + PE-potential, use a PG screw with a metallic shell, or use a metallic mounting clip. x Use only cable with braided, tinned copper mesh shield (type “CY”) with 85% coverage. x The shielding continuity should not be broken at any point in the cable. If the use of reactors, contactors, terminals, or safety switches in the motor output is necessary, the unshielded section should be kept as short as possible. x Some motors have a rubber gasket between terminal box and motor housing. Very often, the terminal boxes, and particularly the threads for the metal PG screw connections, are painted. Make sure there is always a good metallic connection between the shielding of the motor cable, the metal PG screw connection, the terminal box, and the motor housing. If necessary, carefully remove paint between conducting surfaces.

Page 296

D−3

4. Take measures to minimize interference that is frequently coupled in through installation cables. x Separate interfering cables with 0.25m minimum from cables susceptible to interference. A particularly critical point is laying parallel cables over longer distances. If two cables intersect (one crosses over the other), the interference is smallest if they intersect at an angle of 90°. Cables susceptible to interference should therefore only intersect motor cables, intermediate circuit cables, or the wiring of a rheostat at right angles and never be laid parallel to them over longer distances. 5. Minimize the distance between an interference source and an interference sink (interference- threatened device), thereby decreasing the effect of the emitted interference on the interference sink. x You should use only interference-free devices and maintain a minimum distance of 0.25 m from the adjustable frequency inverter. 6. Follow safety measures in the filter installation.

To achieve a protective ground connection for the filter: x Ground the filter with a conductor of at least 10 mm2 cross-sectional area. x Connect a second grounding conductor, using a separate grounding terminal parallel to the protective conductor. (The cross section of each single protective conductor terminal must be sized for the required nominal load.)

Integrated EMC Filter The X200 series inverters for European market (-SFE, and HFE models) have integrated filter complies to EN61800-3 as shown below. 200V class (-SFE models) – EN61800-3 category C1 400V class (-HFE models) – EN61800-3 category C2 Please refer to the next page for the installation.

Appendix D x If using external EMC filter, ensure that the ground terminal (PE) of the filter is properly connected to the ground terminal of the adjustable frequency inverter. An HF ground connection via metal contact between the housings of the filter and the adjustable frequency inverter, or solely via cable shield, is not permitted as a protective conductor connection. The filter must be solidly and permanently connected with the ground potential so as to preclude the danger of electric shock upon touching the filter if a fault occurs.

Page 297

D−4

Installation for X200 series (example of SFEF models) Power supply 1-ph. 200V

Metal plate (earth)

PE

Appendix D

L1,N

U,V,W

PE

Cable clamp *

Shielded cable

Cable clamp *

Motor 3~

*) Both earth portions of the shielded cable must be connected to the earth point by cable clamps.

Page 298

D−5

Hitachi EMC Recommendations WARNING: This equipment should be installed, adjusted, and serviced by qualified personal familiar with construction and operation of the equipment and the hazards involved. Failure to observe this precaution could result in bodily injury. Use the following checklist to ensure the inverter is within proper operating ranges and conditions. 1. The power supply to X200 inverters must meet these specifications: x Voltage fluctuation ±10% or less x Voltage imbalance ±3% or less x Frequency variation ±4% or less x Voltage distortion THD = 10% or less 2. Installation measure: x Use a filter designed for X200 inverter. 3. Wiring:

x The carrier frequency setting must be less than 5 kHz to satisfy EMC requirements. x Separate the power input and motor wiring from the signal/process circuit wiring. 4. Environmental conditions - when using a filter, follow these guidelines: x Ambient temperature: –10 to 40 °C x Humidity: 20 to 90% RH (non-condensing) x Vibration: 5.9 m/sec2 (0.6 G) 10 ~ 55Hz x Location: 1000 meters or less altitude, indoors (no corrosive gas or dust)

Appendix D x Shielded wire (screened cable) is required for motor wiring, and the length must be less than 5 meters.

Page 299

This page is a scan with no text; see it in the PDF.

Page 300

Index−1

Index

A A Group functions 3–10 AC reactors 5–3 Acceleration 1–23, 3–9 characteristic curves 3–27 second function 3–25 two-stage 4–17 Access levels 3–5, 3–36, 4–21 Accessories 5–2 ADD frequency 3–30 enable input 4–30 Alarm signal 4–37, 4–44 Algorithms, torque control 3–5, 3–65 Ambient temperature 2–10, A–2 Analog inputs calibration settings 3–61 current/voltage select 4–22 disconnect detect 4–46 operation 4–55 settings 3–13, 3–28 wiring examples 4–53 Analog outputs configuration 3–56 operation 4–57 Arrival frequency A–2 Automatic restart 3–32 Automatic voltage regulation 2–32, 3–23

B B Group functions 3–32 Base frequency 2–31, A–2 setting 3–12 Bibliography A–8 Braking 1–22 dynamic 5–5 settings 3–18 Braking resistor 5–5, A–2 Braking unit 5–5 Break-away torque A–2 C C Group functions 3–49 Calculate function 3–29 Capacitor life curve 6–11 Carrier frequency 3–40, A–2 Cautions general x index to... iv inverter mounting 2–9 operating procedures 4–2 CE approval A–2 CE-EMC guidelines D–2 Chassis ground connection 1–25, 2–23