The text of a manual · part 4 of 31
X200 Series Inverter Instruction Manual, pages 31 to 40
Pages 31 to 40 of 305
The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Hitachi X200 Series
Page 31
1−10
Getting started
Getting started
General Specifications The following table applies to all X200 inverters. Item Protective housing *1 Control method Carrier frequency Output frequency range *4 Frequency accuracy
General Specifications IP00 Sinusoidal Pulse Width Modulation (PWM) control 2kHz to 12kHz (default setting: 3kHz) 0.5 to 400Hz Digital command: 0.01% of the maximum frequency Analog command: 0.4% of the maximum frequency (25qC r 10qC) Frequency setting resolution Digital: 0.1Hz; Analog: max. frequency/1000 Volt./Freq. characteristic V/f control (constant torque, reduced torque) Overload capacity 150% rated current for 1 minute Acceleration/deceleration time 0.01 to 3000 seconds, linear and S-curve accel/decel, second accel/decel setting available Input Freq. Operator panel Up and Down keys / Value settings signal setting Potentiometer Analog setting External signal 0 to 10 VDC (input impedance 10k Ohms), 4 to 20mA (input *9 impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W) FWD/ Operator panel Run/Stop (Forward/Reverse run change by command) REV run External signal Forward run/stop, Reverse run/stop Intelligent input FW (forward run command), RV (reverse run command), CF1~CF4 terminal (multi-stage speed setting), JG (jog command), DB (external braking), SET (set second motor), 2CH (2-stage accel./decel. command), FRS (free run stop command), EXT (external trip), USP (startup function), SFT (soft lock), AT (analog current input select signal), RS (reset), PTC (thermistor thermal protection), STA (start), STP (stop), F/R (forward/reverse), PID (PID disable), PIDC (PID reset), UP (remote control up function), DWN (remote control down function), UDC (remote control data clearing), OPE (operator control), ADD (add frequency enable), F-TM (force terminal mode), RDY (Run ready), SP-SET (Special set) , EMR (Emergency Stop) Output Intelligent output RUN (run status signal), FA1,FA2 (frequency arrival signal), OL (overload advance notice signal), OD (PID error deviation signal terminal signal), AL (alarm signal), Dc (analog input disconnect detect), FBV (PID two-stage control output), NDc (network detection signal), LOG (Logic output), ODc (comm. watchdog error), LOC (Low load) Frequency monitor Analog output; Select output frequency or output current monitor Alarm output contact ON for inverter alarm (1c contacts, both normally open or closed avail.) Other functions AVR function, curved accel/decal profile, upper and lower limiters, 16-stage speed profile, fine adjustment of start frequency, carrier frequency change (2 to 12kHz) *10, frequency jump, gain and bias setting, process jogging, electronic thermal level adjustment, retry func., trip history monitor, 2nd setting select, fan ON/OFF selection. Protective function Over-current, over-voltage, under-voltage, overload, extreme high temperature, CPU error, memory error, ground fault detection at startup, electronic thermal Operating Temperature Operating (ambient): -10 to 40qC(*10), / Storage: -25 to 70qC(*11) environment Humidity 20 to 90% humidity (non-condensing) Vibration *12 5.9m/s2 (0.6G), 10 to 55 Hz Location Altitude 1,000m or less, indoors (no corrosive gasses or dust) Coating color Blue Options Remote operator unit, copy unit, cables for the units, braking unit, braking resistor, AC reactor, DC reactor, noise filter
Page 32
1−11
Signal Ratings
Signal / Contact Built-in power for inputs Discrete logic inputs Discrete logic outputs Analog output Analog input, current Analog input, voltage +10V analog reference Alarm relay contacts
Ratings 24VDC, 30mA maximum 27VDC maximum 50mA maximum ON state current, 27 VDC maximum OFF state voltage 0 to 10VDC, 1mA 4 to 19.6 mA range, 20mA nominal 0 to 9.8 VDC range, 10VDC nominal, input impedance 10k: 10VDC nominal, 10mA maximum 250 VAC, 2.5A (R load) max., 0.2A (I load, P.F.=0.4) max. 100 VAC, 10mA min 30 VDC, 3.0A (R load) max., 0.7A (I load, P.F.=0.4) max.) 5 VDC, 100mA min.
GettingGetting started started
Detailed ratings are in “Control Logic Signal Specifications” on page 4-6.
Page 33
1−12
Getting started
Derating Curves The maximum available inverter current output is limited by the carrier frequency and ambient temperature. The carrier frequency is the inverter’s internal power switching frequency, settable from 2kHz to 12kHz. Choosing a higher carrier frequency tends to decrease audible noise, but it also increases the internal heating of the inverter, thus decreasing (derating) the maximum current output capability. Ambient temperature is the temperature just outside the inverter as inside the control cabinet where the inverter is mounted. A higher ambient temperature decreases (derates) the inverter’s maximum current output capacity. Individual mounting An inverter may be mounted individually in an enclosure or side-by-side with other Enclosure inverter(s)As shown below. Side-by-side mounting causes greater derating than mounting inverters separately. Graphs for either mounting methods are included in this section. Refer to “Ensure Adequate Ventilation” on page 2-10 for minimum clearance dimensions for both mounting configurations.
Side-by-side mounting
Enclosure
Use the following derating curves to help determine the optimal carrier frequency setting for your inverter and find the output current derating. Be sure to use the proper curve for your particular X200 inverter model number. Legend for Graphs: Ambient temperature 40qC max., individual mounting Ambient temperature 50qC max., individual mounting Ambient temperature 40qC max., side-by-side mounting
Page 34
1−13
Derating curves:
X200-002SFEF/NFU
Getting started
100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz 2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
X200-004SFEF/NFU 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz
X200-005SFEF 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz
Page 35
1−14
Derating curves, continued…
Getting started
X200-007SFEF/NFU 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz 2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
X200-011SFEF 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz
X200-015SFEF/NFU 100% 90% % of rated output current
80% 70% 60% 50% 40% kHz
30%
Page 36
1−15
Derating curves, continued…
X200-022SFEF/NFU
Getting started
100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz 2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
X200-037LFU 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz
X200-055LFU 100% 90% % of rated output current
80% 70% 60% 50% 40% kHz
30%
Page 37
1−16
Derating curves, continued…
Getting started
X200-075LFU 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz 2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
X200-004HFEF/HFU 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz
X200-007HFEF/HFU 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz
Page 38
1−17
Derating curves, continued…
X200-015HFEF/HFU
Getting started
100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz 2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
X200-022HFEF/HFU 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz
X200-030HFEF 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz
Page 39
1−18
Derating curves, continued…
Getting started
X200-040HFEF/HFU 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz 2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
2
4
6 8 Carrier frequency
10
12
X200-055HFEF/HFU 100% 90% % of rated output current
80% 70% 60% 50% 40% 30% kHz
X200-075HFEF/HFU 100% 90% % of rated output current
80% 70% 60% 50% 40% kHz
30%
Page 40
1−19
The Purpose of Motor Speed Control for Industry Hitachi inverters provide speed control for 3-phase AC induction motors. You connect AC power to the inverter, and connect the inverter to the motor. Many applications benefit from a motor with variable speed, in several ways: x Energy savings – HVAC x Need to coordinate speed with an adjacent process – textile and printing presses x Need to control acceleration and deceleration (torque) x Sensitive loads – elevators, food processing, pharmaceuticals
What is an Inverter The term inverter and variable-frequency drive are related and somewhat interchangeable. An electronic motor drive for an AC motor can control the motor’s speed by varying the frequency of the power sent to the motor. An inverter, in general, is a device that converts DC power to AC power. The figure below shows how the variable-frequency drive employs an internal inverter. The drive first converts incoming AC power to DC through a rectifier bridge, creating an internal DC bus voltage. Then the inverter circuit converts the DC back to AC again to power the motor. The special inverter can vary its output frequency and voltage according to the desired motor speed.
Power Input L1 L2
Variable-frequency Drive Converter Rectifier
Internal DC Bus
Motor
Inverter
U/T1 V/T2
L3
W/T3
The simplified drawing of the inverter shows three double-throw switches. In Hitachi inverters, the switches are actually IGBTs (insulated gate bipolar transistors). Using a commutation algorithm, the microprocessor in the drive switches the IGBTs on and off at a very high speed to create the desired output waveforms. The inductance of the motor windings helps smooth out the pulses.
Getting started
Getting started
Introduction to Variable-Frequency Drives