RM7890A1056, RM7890B1048 7800 SERIES Relay Modules Installation Instructions, pages 20 to 28

Pages 20 to 28 of 28

The original document is the PDF (996 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Honeywell RM7890

Page 20

RM7890A1056, RM7890B1048 7800 SERIES RELAY MODULES

Flame Signal With Hot Combustion Chamber (All Installations) 1. 2. 3.

4. 5. 6. 7. 8. 9.

4.

With all initial start-up tests and burner adjustments completed, operate the burner until the combustion chamber is at the maximum expected temperature. Observe the equipment manufacturer warm-up instructions. Recycle the burner under these hot conditions and measure the flame signal. Check the pilot alone, the main burner flame alone, and both together (unless monitoring only the pilot flame when using an intermittent pilot). Check the signal at both High and Low Firing Rate positions and while modulating, if applicable. Check the FFRT of the flame amplifier and relay module. Lower the setpoint of the operating controller and observe the time it takes for the burner flame to go out. This should be within the maximum FFRT. If the flame signal is too low or unsteady, check the flame detector temperature. Relocate the detector if the temperature is too high. If necessary, realign the sighting to obtain the proper signal and response time. If the response time is still too slow, replace the Plug-in Flame Signal Amplifier. If the detector is relocated or resighted, or the amplifier is replaced, repeat all required Checkout tests.

5.

SAFETY SHUTDOWN TESTS (ALL INSTALLATIONS) Perform these tests at the end of Checkout, after all other tests are completed. If used, the external alarm should turn on. Press the RESET push button on the relay module to restart the system. 1.

2.

3.

6.

Opening a Preignition Interlock during STANDBY. a. *Preignition ILK* fault is displayed on the Keyboard Display Module (KDM). Fault code 10 or 33 is displayed to denote the fault. b. Safety shutdown occurs. Detection of flame 40 seconds after entry to STANDBY from RUN, fault code 9. Detection of flame from 10 seconds up to 30 seconds into PREPURGE time. a. Simulate a flame to cause the flame signal voltage level to be at least 1.25 Vdc for 40 seconds after entry to STANDBY from RUN. b. *Flame Detected* fault is displayed on the Keyboard Display Module. Fault code 9 or 15 or 18 is displayed to denote the fault. c. Safety shutdown occurs. Failure to ignite pilot. a. Close pilot and main fuel manual shutoff valve(s). b. Cycle burner on. c. Automatic pilot valve(s) should be energized but the pilot cannot ignite. d. *Pilot Flame Fail* fault is displayed on the Keyboard Display Module. Fault code 28 is displayed four or ten seconds, depending on the jumper configuration selection for Pilot Flame Establishing Period (PFEP) after the pilot valve(s) is energized to denote the fault. e. Safety shutdown occurs.

66-1150 - 02

20

Failure to ignite main (only interrupted pilot application). a. Open the manual pilot valve(s); leave the main fuel manual shutoff valve(s) closed. b. Depress the RESET button. c. Start the system. d. The pilot should ignite and the flame signal should be at least 1.25 Vdc but the main burner cannot light. e. The flame signal should drop below 1.25 Vdc within the FFRT of the amplifier and the relay module after the interrupted pilot goes out. f. *Main Flame Ign.* fault is displayed on the Keyboard Display Module. Fault code 19 is displayed to denote the fault. g. Safety shutdown occurs. Loss of flame during RUN. a. Open the main fuel manual shutoff valve(s) and open manual pilot shutoff valve(s). b. Depress the RESET button. c. Start the system. Start-up should be normal and the main burner should light normally. d. After the sequence is in the normal RUN period for at least 10 seconds with the main burner firing, close the manual main shutoff valve(s) to extinguish the main burner flame. (On intermittent pilot applications, also, close the pilot manual shutoff valve[s].) e. The flame signal should drop below 1.25 Vdc within the FFRT of the amplifier and the relay module after the main flame and/or pilot goes out. f. *Main Flame Fail* fault is displayed on the Keyboard Display Module. Fault code 17 is displayed to denote the fault. g. Safety shutdown occurs. (RM7890 Relay Modules will recycle if jumper JR2 is intact, then lock out on failure to light the pilot.) Opening a Preignition Interlock after the first five seconds of STANDBY. a. Open the main fuel manual shutoff valve(s) and open manual pilot shutoff valve(s). b. Depress the RESET button. c. *Preignition ILK* fault is displayed on the Keyboard Display Module. Fault code 33 is displayed to denote the fault. d. Safety shutdown occurs.

IMPORTANT 1. If the relay module fails to shut down on any of these tests, take corrective action; refer to Troubleshooting and the relay module diagnostic and return to the beginning of all Checkout tests. 2. When all Checkout tests are completed, reset all switches to the original status.

TROUBLESHOOTING The POWER LED provides fault identification when the Relay Module locks out on an alarm. Fault identification is a series of fast- and slow-blinking LED lights. The fast blinks identify the tens portion of the fault code (three fast blinks is 30), while the slow blinks identify the units portion of the fault code (two slow blinks is 2). Three fast blinks followed by two slow blinks would be fault code 32. (See Table 9 for Blinking Fault Code List.)

Page 21

RM7890A1056, RM7890B1048 7800 SERIES RELAY MODULES

The LED code repeats as long as the fault exists. To clear the fault, press the RESET button. The S7800 KDM displays a sequence status message indicating: STADBY, PURGE, PILOT IGN, MAIN IGN, RUN and POSTPURGE. The selectable messages also provide visual indication of current status and historical status of the equipment, such as: Flame Signal, Total Cycles, Total Hours, Fault History, Diagnostic Information, and Expanded Annunciator terminal status (if used). With this information, most problems can be diagnosed without extensive trial and error testing. Diagnostic Information and History Data are available to assist in troubleshooting the relay module. The relay module provides diagnostic information to aid the service mechanic in obtaining information when troubleshooting the system. Information available in the Diagnostic Information includes Device Type, Device Suffix, Software Revision, Manufacturing Code, Flame Amplifier Type, Flame Failure Response Time, Selectable Jumper Configuration Status, Run/Test Switch Status and Terminal Status.

Historical Information Index The relay module has nonvolatile memory that allows the relay module to retain historical information for the six most recent lockouts. Each of the six lockout files retains the cycle when the fault occurred, the hour of operation when the fault occurred, a fault code, a fault message and burner status when the fault occurred. IMPORTANT Some older relay modules cannot operate without a KDM, extension cable assembly with KDM, or a Data ControlBus™ Module installed. SERVICE NOTES: 1. 2.

3.

Diagnostic Information Index The relay module monitors input/output terminals and can display the status of the terminal at the KDM (example: Pilot Valve T8 1). See the applicable relay module installation instructions for a complete terminal description and number. The display shows the actual status of the terminal. If voltage is detected at the terminal, 1 is displayed, but if no voltage is detected at the terminal, 0 is displayed.

4.

If the KDM is scrambled, remove and reinstall the KDM, and reset the 7800 SERIES Relay Module. Reset the 7800 SERIES Relay Module by pressing the RESET pushbutton on the 7800 SERIES Relay Module, or by pressing a remote reset pushbutton wired through the KDM, Data ControlBus™ Module, or Remote Reset Module. A power-up reset causes an electrical reset of the relay module but does not reset a lockout condition. Use the access slots in the sides of the Q7800A,B Wiring Subbase to check terminal voltage. Maximum ambient temperature of a C7012E,F;Series 1 through 6, is reduced to 125°F because of the duty cycle operation of the relay module.

Table 10. Blinking Fault Codes and Recommended Troubleshooting . Blink Code

System Failure

Recommended Troubleshooting

Code 1-1 *Low AC Line Voltage*

Low AC Line detected.

Code 1-2 *AC Quality Problem*

Excessive noise or device running on slow, fast, or AC line dropout detected.

1. Check the relay module and display module connections. 2. Reset and sequence the Relay Module. 3. Check the 7800 power supply and make sure that frequency and voltage meet specifications. 4. Check the backup power supply, as appropriate.

Code 2-1 *Unexpected Flame Signal*

Flame sensed when no flame is expected during STANDBY or PURGE.

1. 2. 3. 4. 5. 6. 7.

Check that flame is not present in the combustion chamber; correct any errors. Make sure that the flame amplifier and flame detector are compatible. Check the wiring and correct any errors. Remove the flame amplifier and inspect its connections. Reseat the amplifier. Reset and sequence the relay module. If the code reappears, replace the flame amplifier and/or the flame detector. If the fault persists, replace the relay module.

Code 2-2 *Flame Signal Absent*

No-flame time present at the end of the PIlot Flame Establishing Period; lost during the Main Flame Establishing Period or during RUN.

1. 2. 3. 4.

Measure the flame signal. If one exists, verify that it meets specifications. Make sure that the flame amplifier and flame detector are compatible. Inspect the main fuel valve(s) and valve connection(s). Verify that the fuel pressure is sufficient to supply fuel to the combustion chamber. Inspect the connections to the fuel pressure switches. Make sure they are functioning properly. Inspect the Airflow Switch and make sure that it is functioning properly. Check the flame detector sighting position; reset and recycle. Measure the flame signal strength. Verify that it meets specifications. If not, refer to the flame detector and/or flame amplifier checkout procedures in the installation instructions. Replace the flame amplifier and/or the flame detector, if necessary. If the fault persists, replace the relay module.

5. 6.

7. 8.

21

66-1150 - 02

Page 22

RM7890A1056, RM7890B1048 7800 SERIES RELAY MODULES

Table 10. Blinking Fault Codes and Recommended Troubleshooting (Continued). Blink Code

System Failure

Code 2-3 *Flame Signal Overrange*

Flame signal value is too high to be valid.

Code 3-1 Running or Lockout *Running/ Interlock fault during Interlock Switch Prepurge. Problem*

Code 3-2 *Running/ Interlock On During Standby*

Lockout Interlock powered at improper point in sequence or On in Standby.

Recommended Troubleshooting 1. Make sure the flame detector and flame amplifier are compatible. 2. Remove the flame amplifier and inspect its connections. Reset the flame amplifier. 3. Reset and sequence the relay module. 4. Check the flame detector sighting position; reset and recycle. Measure flame strength. Verify that it meets specifications. If not, refer to the flame detector and/or flame amplifier checkout procedures in the installation instructions. 5. If the code reappears, replace the flame amplifier and/or the flame detector. 6. If the fault persists, replace the relay module. 1. Check wiring; correct any errors. 2. Inspect the fan; make sure there is no air intake blockage and that it is supplying air. 3. Make sure the Lockout Interlock switches are functioning properly and the contacts are free from contaminants. 4. Reset and sequence the relay module to Prepurge (place the TEST/RUN Switch in the TEST position, if available). Measure the voltage between terminal 7 and G (ground); 120 Vac should be present. Switch TEST/RUN back to RUN. 5. If steps 1 through 4 are correct and the fault persists, replace the relay module. 1. Check wiring to make sure that the Lockout Interlocks are connected properly between terminals 6 and 7. Correct any errors. 2. Reset and sequence the relay module. 3. If the fault persists, measure the voltage between terminal 6 and G (ground), then between terminal 7 and G. If there is 120 Vac at terminal 6 when the controller is off, the controller switch may be bad or is jumpered. 4. If steps 1 through 3 are correct and there is 120 Vac at terminal 7 when the controller is closed and the fault persists, check for a welded or jumpered Running Interlock or Airflow Switch. Correct any errors. 5. If steps 1 through 4 are correct and the fault persists, replace the relay module.

VPS (Valve Proving Code 3-3 Switch) in wrong state *VPS in Improper State* during VPS Test.

1. Check wiring, making sure upstream valve is connected to terminal 9 and downstream valve is connected to terminal 17. 2. Conduct Valve Seat leakage test using a manometer. 3. Reset and sequence the relay module; if fault repeats, test VPS (connected to terminal 16) is functioning properly; replace if necessary. 4. Reset and sequence the relay module. 5. If fault persists, replace the relay module.

Code 4-1 *Purge Card Problem*

No purge card or the purge card timing has changed from the original configuration.

1. Make sure the purge card is seated properly. 2. Inspect the purge card and the connector on the relay module for any damage or contaminants. 3. Reset and sequence the relay module. 4. If the fault code reappears, replace the purge card. 5. Reset and sequence the relay module. 6. If the fault code persists, replace the relay module.

Code 4-2 *Wiring Problem/ Internal Fault*

Pilot (ignition) valve terminal, main valve, ignition or Main Valve 2 was on when it should be off.

Code 4-3 *Flame Amplifier Problem*

66-1150 - 02

Flame not sensed, or sensed when it should be off.

WARNING

Electrical Shock Hazard; Fire or Explosion Hazard. Can cause severe injury, death or property damage. Remove system power and turn off power supply.

1. 2. 3. 4. 5.

Remove system power and turn off fuel supply. Check wiring; correct any errors. inspect Pilot Fuel Valve(s), both places, and connections. Reset and sequence the relay module. If the fault persists, replace the relay module.

1. 2. 3. 4. 5. 6.

Check wiring; correct any errors. Make sure the flame amplifier and flame detector are compatible. Remove the flame amplifier and inspect the connections. Reseat the amplifier. Reset and sequence the relay module. If the code reappears, replace the flame amplifier and/or the flame detector. If the fault persists, replace the relay module.

22

Page 23

RM7890A1056, RM7890B1048 7800 SERIES RELAY MODULES

Table 10. Blinking Fault Codes and Recommended Troubleshooting (Continued). Blink Code

System Failure

Code 4-4 *Configuration Jumper Problem*

The configuration jumpers differ from the sample taken at startup.

1. Inspect the jumper connections. Make sure the clipped jumpers were completely removed. 2. Reset and sequence the relay module. 3. If the fault persists, replace the relay module.

Recommended Troubleshooting

Code 5-1 *Preignition Interlock*

Preignition Interlock fault.

1. 2. 3. 4. 5.

Code 5-2 *High Fire Sw. or Low Fire Sw.*

Either High Fire Switch or Low Fire Switch failure.

1. Check wiring and correct any errors. 2. Reset and sequence the relay module. 3. Use manual motor potentiometer to drive the motor open and closed. Verify at motor switch that the end switches are operating properly. Use RUN/TEST switch if manual potentiometer is not available. 4. Reset and sequence the relay module. 5. If the fault persists, replace the relay module.

Code 5-3 *Man-Open Sw.; Start Sw. or Control On*

Man-Open Switch, Start Switch or Control On in the wrong operational state.

1. Check wiring and correct any errors. 2. Make sure that the Manual Open Valve Switch, Start Switch and Control are operating properly. 3. Stat Switch held “On” too long. 4. Reset and sequence the relay module. 5. Reset and sequence the relay module. If the fault persists, replace the relay module (RM7838A1014; RM7838B1013 or RM7838C1004 only).

Code 6-1 Relay Module self-test *Internal Faults* failure.

1. Reset and sequence the relay module. 2. If fault reappears, remove power from the device, reapply power, then reset and sequence the relay module. 3. If the fault persists, replace the relay module.

Code 6-2 Relay Module Self-Test *Internal Faults* failure.

1. Reset and sequence the relay module. 2. If fault reappears, remove power from the device, reapply power, then reset and sequence the relay module. 3. If fault does not repeat on the next cycle, check for electrical noise being copied into the relay module through the external loads or possibly an electrical grounding issue. 4. If the fault persists, replace the relay module.

Code 6-3 *Device Specific*

Fault with special OEM input circuits.

1. Check wiring and operation of special OEM inputs. 2. Reset and sequence the relay module. 3. If fault reappears, remove power from the device, reapply power, then reset and sequence the relay module. 4. If the fault does not repeat on the next cycle, check for electrical noise being copied into the relay module through the external loads or possibly an electrical grounding issue. 5. If the fault persists, replace the relay module.

Code 6-4 *Accessory Fault*

Unused at this time., Code 7-7 *Unused*

Unused at this time., Check wiring and correct any errors. Check Preignition Interlock switches to assure proper functioning. Check fuel valve operation. Reset and sequence the relay module; monitor the Preignition Interlock status. If the fault persists, replace the relay module.

23

66-1150 - 02

Page 24

RM7890A1056, RM7890B1048 7800 SERIES RELAY MODULES

APPENDIX A Valve Proving Test The Valve Proving System feature offers a systematic way of testing the valve seat integrity to assure the valves are in the closed position when the system is off-line, in STANDBY.

WARNING

Explosion Hazard. Can cause severe injury, death or property damage. Be sure to select adequate testing times when the Valve Proving feature is selected. A shorter time can result in inadequate leak testing of the valves.

The following steps are to determine the test time for the relay module to verify the valve seats are not leaking at a rate of greater than/equal to 0.1% of the burner capacity. The following diagram shows a typical valve train. The legend identifies information that will be used to fill out the worksheet that appears at the end of this appendix.

V1

V2 VP SW.

D

P INLET

OUTLET L

C

X

LEGEND V1 UPSTREAM VALVE V2 DOWNSTREAM VALVE D PIPE DIAMETER (IN INCHES.) USED TO DETERMINE A; ARE FOUND IN TABLE III L PIPE LENGTH (IN FEET) P VALVE INLET PRESSURE (PSIG) C BURNER MAX. FIRING (CFH) X CALCULATED TEST VALVE TRAIN VOLUME M22778

Fig. 20. Typical valve train layout. 1. 2.

Identify items of your system and fill in the “Information” portion of the worksheet. Go to the Lookup Tables noted (13, 14, or 15) to get the results for your system.

IMPORTANT The tables show information on Honeywell Valves only. Contact other valve manufacturers to obtain data on their specific valves. 3. 4. 5.

Use appropriate Results column items to fill in the Valve Train Volume Formula and the Calculation of Valve Proving Test Time. Round up the time to the nearest second. The test time calculated is the time you will enter into the VPS Setup.

Calculation of Valve Train Volume X = V1 + V2 + (A X L/144)

Symbol

Unit

Description

X ft

3

Volume between the two valves to be tested.

V1 ft3

Volume of upstream valve outlet cavity.

V2 ft3

Volume of downstream valve inlet cavity.

L ft

Length of pipe between valves.

D npt

Pipe Size - used to define A

A in.2

Pipe Cross Section Area (from Table III)

Test Time

Seconds Minimum VPS test period.

P psi

Gas inlet pressure to upstream valve.

C ft3/hr

Burner Capacity.

NOTE: V1 is the outlet cavity of the upstream valve and V2 is the inlet cavity of the downstream valve.

Calculation of Valve Proving Test Time

NOTE: 10 seconds is the minimum test time allowed. If your calculations are less than 10 seconds, enter 10 seconds.

Test Time = 187,000 x (P x X)/C

66-1150 - 02

Table 11. Valve Proving Test Time Symbols and Descriptions.

24

Page 25

RM7890A1056, RM7890B1048 7800 SERIES RELAY MODULES

Example: We have a 2.5 MBTU burner with 2 psi valve train inlet pressure. The upstream valve is a proof-of-closure V5044 with a solenoid V4295 valve downstream. We have a 2 in. NPT pipe, 1-3/4 ft long, between the valves. Table 12. VPS Worksheet Example. Item

Description

V1

Upstream Valve Volume

Information V5055

Lookup Table 13

Results 0.0218

Formula Item V1

V2

Downstream Valve Volume

V4295

14

0.0267

V2

D

Pipe Size (in.)

2 in. NPT

15

3.356

A

L

Pipe Length (ft)

1.75 ft, 1.75

L, 2

P, 2500

C

P

Valve Inlet Pressure (psig)

2

C

Burner Maximum Firing (cf/hr)b

2.5 mbtu a a Divide inches w.c. by 27.7 to get psi. b Divide Btuh by 1000 to get cf/hr for natural gas or by 2550 to get cf/hr for LP gas.

Calculation of Valve Train Volume:

Test Time = 187,000 x (P x X ÷ C)

X = V1 + V2 + (A x L ÷ 144)

Test Time = 187,000 x (2 x 0.0893 ÷ 2500) = 13.4 seconds.

X = 0.0218 + 0.0267 + (3.356 x 1.75 ÷ 144) = 0.0893.

Round up to 14 seconds; enter 14 seconds into the VPS Setup.

Calculation of Valve Proving Test Time:

Table 13. V1 Upstream Valve Volumes for Honeywell Valves. Pipe Size NPT (inches) 3/8

V4295 0.0002

V4297A1013

V4297A1005, - - V48

V5055, V5097A1004

V5097A1012, - 1/2

0.0002, - - - - - 3/4

0.0008

0.0093

0.0090

0.0010

0.0046

0.0066, 1

0.0009

0.0093

0.0090

0.0010

0.0046

0.0066, 1-1/4

0.0045

0.0093

0.0090

0.0035

0.0046

0.0066, 1-1/2

0.0045

0.0093, 0.0035

0.0218

0.0066, 2

0.0089

0.0093, 0.0048

0.0218

0.0066

0.0285

2-1/2

0.0441, - 0.0048

0.0227, 0.0285

3

0.0441, - 0.0048

0.0227, 0.0285

4, - - - 0.0779, - Table 14. V2 Downstream Valve Volumes for Honeywell Valves. Pipe Size NPT (inches) 3/8

V4295 0.0011

V4297A1013

V4297A1005, - - V48

V5055, V5097A1004

V5097A1012, - 1/2

0.0011, - - - - - 3/4

0.0026

0.0282

0.0232

0.0048

0.0067

0.0093, 1

0.0036

0.0282

0.0232

0.0048

0.0067

0.0093, 1-1/4

0.0148

0.0282

0.0232

0.0110

0.0067

0.0093, 1-1/2

0.0148

0.0282, 0.0110

0.0238

0.0093, 2

0.0267

0.0282, 0.0184

0.0238

0.0093

0.0303

2-1/2

0.0554, - 0.0184

0.0245, 0.0303

3

0.0554, - 0.0184

0.0245, 0.0303

4, - - - 0.0801, - 25

66-1150 - 02

Page 26

RM7890A1056, RM7890B1048 7800 SERIES RELAY MODULES

Table 15. Schedule 40 Pipe Internal Cross-Sectional Area. Pipe Size NPT (Inches)

Cross-Sectional Area (Sq. In.) “A”

3/8

0.191

1/2

0.304

3/4

0.533

1

0.864

1-1/4

1.498

1-1/2

2.036

2

3.356

2-1/2

4.788

3

7.393

4

12.730 Table 16. VPS Worksheet. Item

Description

Information

Lookup Table

Results

Formula Item

V1

Upstream Valve Volumes

13

V1

V2

Downstream Valve Volumes

14

V2

D

Pipe Size (in.)

15

A

L

Pipe Length (ft), L

P

Valve Inlet Pressure (psig)a, P

C

Burner Maximum Firing (cf/hr)b, C a Divide inches w.c. by 27.7 to get psi. b Divide Btuh by 1000 to get cf/hr for natural gas or by 2550 to get cf/hr for LP gas.

66-1150 - 02

26

Page 27 read from a scan by OCR; it may hold reading errors

27

RM7890A 1056, RM7890B1048 7800 SERIES RELAY MODULES

66-1150 - 02

Page 28

RM7890A1056, RM7890B1048 7800 SERIES RELAY MODULES

Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Toronto, Ontario M1V 4Z9 customer.honeywell.com

® U.S. Registered Trademark © 2010 Honeywell International Inc. 66-1150 - 02 M.S. Rev. 08-10 Printed in U.S.A.