Spec sheet · Honeywell
UDC2000 Mini-Pro Universal Digital Controller Specification
Spec sheet12 pagesPDF 128 KB
Specification sheet for the Honeywell UDC2000 Mini-Pro universal digital controller for temperature and other process variables.
Covers · 1 model
The models it covers
Summary
What is in it
The specification sheet for the Honeywell UDC2000 Mini-Pro universal digital controller, a 1/4 DIN microprocessor-based controller for temperature and other process variables. It describes the standard and optional features, inputs, output types and algorithms, control algorithms, configuration, alarms, control modes, diagnostics and the operator interface, followed by detailed specifications, general reference data, model number interpretation, dimensions and ordering information.
Its parts
- Overview
- Features
- Optional Features
- Physical Description
- Inputs
- Outputs
- Output Algorithms
- Control Algorithm
- Configuration
- Alarms
- Control Modes
- Operator Interface
- Specifications
- Model Number Interpretation
- Ordering Information
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Honeywell specification 51-52-03-08 (2/97) for the UDC2000 Mini-Pro Universal Digital Controller, a 1/4 DIN panel-mount controller for temperature and other process variables, with a limit control model. It describes the features, inputs, outputs, control algorithms and operator keys, and gives the specifications, the model number key and the dimensions.
- What it is
- Microprocessor-based digital controller for temperature, pressure, flow, level and rotation; a limit control model is available p. 1
- Output types
- Current output, electromechanical relay, solid state relay or open collector output p. 2
- Power
- 120Vac or 240Vac (50/60 Hz), set by a factory jumper the user can change; 6 VA p. 8, 10
- Mounting
- 1/4 DIN cutout; 4.2 inch deep black metal case; screw terminals (6-32) on the rear p. 2, 8
- Accuracy
- ±0.3% of span typical (± 1 digit for display); 14 bit resolution typical p. 5
- Relay output
- SPST, N.O. or N.C. by jumper; resistive 5 amps @ 120 Vac, 30 Vdc; 2.5 amps @ 240 Vac; motor 1/6 H.P. p. 6
- Current output
- 4 to 20 mA, direct or reverse; load 0 to 750 ohms; accuracy 0.5% full scale p. 6
- Displays
- Vacuum fluorescent: 4 digit, 9 segment upper display; 6 digit, 14 segment lower display p. 4, 8
- Alarms
- Optional one or two SPST alarm relays, 5 amps @ 120 Vac or 30 Vdc, 2.5 amps @ 240 Vac p. 3, 6
- Weight
- 1 kg (2.2 lbs.) p. 8
- Front panel
- IP 65 (IEC 529); NEMA 3 p. 2, 5
- Sampling and filter
- Inputs sampled 3 times per second; filter off to 120 seconds per input p. 7
- Timer and ramp/soak
- Optional timer 0 to 99 hours, 59 minutes; optional 6 ramp and 6 soak segments p. 2, 7
What this sheet walks you through
- Configuring and operating the controller with its five keys p. 4
- Field calibration from the front keys p. 3
- Choosing output and control algorithms p. 2, 3, 7
- Setting high and low alarms p. 3, 6
- Using the optional digital input actions p. 7
- Locking keys against tampering p. 4
- Reading the model number p. 10
- Panel cutout and dimensions p. 11
- Input ranges for each thermocouple, RTD and linear input p. 9
Good to know
- The controller must be panel mounted with its terminals enclosed in the panel (IP 00 behind the panel). p. 5
- The auxiliary output and the digital input cannot both be fitted. p. 7
- There is no isolation between the analog input and analog output circuits. p. 9
- Limit models take only thermocouple or RTD inputs. p. 1
- With Duplex or 3 Position Step operation, only one alarm is available. p. 2
Questions this sheet answers
What power supply does the UDC2000 need?
120Vac or 240Vac at 50/60 Hz, chosen by a jumper; it uses 6 VA. p. 8, 10
What size panel cutout does the UDC2000 fit?
A 1/4 DIN cutout; the case is 4.2 inches deep. p. 2
How much current can the UDC2000 relay output switch?
The electromechanical relay is rated 5 amps resistive at 120 Vac or 30 Vdc, and 2.5 amps at 240 Vac. p. 6
Can the UDC2000 run a ramp and soak program?
Yes, as an option: 6 ramp and 6 soak segments, as one program or several small ones. p. 7
The whole text · 2 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.