The text of a spec sheet · part 1 of 2

UDC2000 Mini-Pro Universal Digital Controller Specification, pages 1 to 6

Pages 1 to 6 of 12

The original document is the PDF (128 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Honeywell UDC2000

Page 1

UDC2000 Mini-Pro Universal Digital Controller Overview The UDC2000 Mini-Pro is a low cost member of Honeywell’s Leaderline family of microprocessor-based, digital controllers. It monitors and controls temperatures and other variables in applications such as environmental chambers, plastic processing machines, furnaces and ovens and packaging machinery. The Mini-Pro is a low cost alternative to more expensive controllers without compromising quality or performance. It can be used to control variables such as temperature, pressure, flow, level, and rotation. A limit control model is also available. The Mini-Pro has a high degree of functionality. A dedicated configuration display provides multilanguage prompts providing unmatched operating simplicity. Programmed sequences of displays assure quick and accurate entry of all configurable parameters. Simple keystrokes let you change the operating parameters to meet your process control needs.

L L 51-52-03-08 2/97 Page 1 of 12

Specification

ALM 1 2 OUT 1 2

2000

SP

FUNCTION DISPLAY

MAN-AUTO RESET

AUTO TUNE

F C PV

RL

SET UP RUN HOLD

22063

Figure 1 - UDC2000 Mini-Pro Controller

Features, continued

Accutune II - This standard feature provides a new, truly plug and play tuning algorithm, which will, at the touch of a button, accurately identify and tune any process including deadtime and integrating processes . This speeds-up and Features simplifies startup plus allows retuning at any setpoint. Low-Cost - This Mini-Pro meets Honeywell’s high performance Fuzzy Logic- This new feature uses standards at a surprisingly fuzzy logic to suppress process affordable price. variable overshoot which can result from setpoint changes or externally Easy to Configure - A bright induced process disturbance. dedicated configuration display provides straightforward multiIt operates independently from language prompts that allow easy Accutune Tuning. It does not set-up with minimum time and effort. change the PID constants, but temporarily modifies the internal Universal Inputs - Accepts 10 controller response to suppress thermocouple types, RTDs, Radiamatics RH, mA, mV or voltage overshoot. This allows more aggressive tuning to co-exist with inputs through simple smooth process variable response. configuration. It can be enabled or disabled Thermocouple Failsafe Configurable upscale or downscale depending on the application or the control criteria. burnout or failsafe output level.

Features, continued UL Recognized Component - This is a standard feature for all models for regulatory use only. CE Mark- Conformity with 73/23/EEC, Low Voltage Directive and 89/336/EEC, the EMC Directive Dual Setpoints - Simple pushbutton selection allows quick switchover from primary to alternate setpoint with minimal operator confusion. Limit Control - This model provides a latching relay which is activated whenever the PV goes above (High Limit) or below (Low Limit) a preset setpoint value. An alarm message will be displayed when the output is activated. Reset is through a key on the front of the controller or an optional external switch. Normal display can be configured to indicate process variable or setpoint. Only T/C or RTD inputs are available on Limit models. FM approval is available.

Industrial Automation and Control, 1100 Virginia Drive, Fort Washington, PA 19034 Printed in U.S.A. ■ Copyright 1997 Honeywell Inc.

Page 2

51-52-03-08 Page 2

Features, continued Moisture Resistant Front Panel Capable of meeting NEMA 3 and IEC IP65 (i.e. hose down) requirements. Diagnostic/Failsafe Outputs Continuous diagnostic routines detect failure modes, trigger a failsafe output value and identify the failure to minimize troubleshooting time. Highly Secure - Non-volatile EEPROM memory assures data integrity during loss of power. Keyboard security prevents accidental or unauthorized changes to the display. High Noise Immunity - The Mini-Pro is designed to provide reliable, error- free performance in industrial environments that often affect highly noise-sensitive digital equipment. Quality/Support - The Mini-Pro conforms to Honeywell’s high quality standards in design, materials and workmanship. It is covered by a two year warranty and backed up by a toll-free phone number for technical assistance.

Optional Features, cont.

Auto/Manual Modes - Provides automatic or manual control with bumpless, balanceless switching between modes. This includes the Dual Display option as described above. Alarm Selection - None, one, or two relays to activate external equipment when preset high/low setpoints are reached. There is an indicator for each alarm on the operator interface. For Duplex or 3 Position Step operation, only one alarm is available. Timer - Provides a configurable time period of 0 to 99 hours, 59 minutes. Alarm 1 is dedicated to be active at the end of the time-out period. Timer “start” is selectable as either the RUN/HOLD key or Alarm 2. The optional Digital Input can also be configured to start the Timer in addition to either the keyboard or Alarm 2. The Timer display is selectable as either time remaining or elapsed time. Ramp Soak Programming - Lets you program and run 6 ramp and 6 soak segments for Setpoint Programming. Run or Hold of program is keyboard or remote Optional Features switch selectable. Dual Display - Provides the standard FM and CSA Approval - Are optional upper display dedicated to process features. variable, plus a lower display which Solid State External Control Relay can display output, setpoints or Outputs - Optional outputs rated at deviation as desired via the 2 Amps at 120/240V or 10 Amps at “DISPLAY” key. 120/240V. Minimum load 0.1 Amp. Second Input - 4-20 mA or 1 to 5 Volt input available for remote Physical Description setpoint signal. The controller is housed in a 4.2 *Auxiliary Output - This auxiliary inch deep, black metal case with an Process Variable output can be scaled from 1 to 5 Volt or 0 to 5 Volt elastomer bezel that can be for 0 to 100% for any range desired. mounted in a 1/4 DIN cutout. The modular construction of the plug-in OR chassis allows quick access to *Digital Input - Allows remote minimize down time. All power, switching via an external dry contact input, and output wiring are or isolated solid-state input to select connected to screw terminals on from a menu of discrete mode the rear terminal panel. Standard changes as described on page 6. bezel color is gray. Blue and tan colors are optional. * These options are mutually exclusive.

Inputs Each analog input is sampled 3 times a second. The sampled signal is amplified and then converted to a digital signal which is passed to the processor. The PV input can be one of various Thermocouple, RTD, Radiamatic or Linear actuations (Table 1). Cold Junction compensation is provided. You can select upscale or downscale sensor break protection. Any range can be field selected via internal switch positions and keyboard selections. A second input provides a remote setpoint function and accepts a 4 to 20 mA or a 1 to 5 Vdc linear signal that can be characterized. A configurable digital filter of 0 to 120 seconds provides signal smoothing for each input.

Outputs The following output types are available per the model selection guide: • Current Output • Electromechanical Relay • Solid State Relay • Open Collector Output

Output Algorithms The UDC2000 Mini-Pro is available with the following output algorithms: Time Proportional - provides On-Off or Time Proportional (relay) output. Electromechanical, solid-state or open collector outputs are standard; 2 amp or 10 amp externally mounted solid-state relay outputs are optional. Current Proportional - supplies proportional direct current output for final control elements that require a 4-20 mA signal. Time Proportional Duplex (Heat/Cool) - depending on which control algorithm you select, this duplex output type can provide onoff duplex, time proportional duplex or 3 Position Step control. The time proportional duplex output provides independent PID tuning constants and two time proportional outputs: one for heat zone above the 50% output, and one for cool zone below 50% output.

Page 3

51-52-03-08 Page 3

Control Algorithm

Configuration

Alarms

Depending on the output algorithm you select, the controller can be configured for the following control algorithms: On-Off - Whenever the controlled variable deviates a predetermined amount from the setpoint, the controller moves the final control element to either of two extreme positions. Hysteresis: 0 to 100% PID-A - The controller gives full response to Setpoint and Process Variable (PV) changes involving Gain (Proportional), Reset (Integral), and Rate (Derivative) effects. There is a fixed relationship between the value of the controlled variable and the position of the final control element. The adjustable Gain, Rate, and Reset Time tuning constants let you tailor the controller’s response to your process requirements. PD with Manual Reset - The action is similar to the PID-A algorithm except the reset (Integral) value is entered as Manual Reset tuning constant instead of Reset Time. The manual reset value eliminates offset by shifting the PD calculated output upscale or downscale to return the controller variable to the setpoint. Three Position Step Control - This is an extension of the On/Off Duplex control and includes internal feedback of the state of the relays. The effect of this control action is that the On and Off times of the output relay change in proportion to the error signal and the Gain and Reset time setting. The Deadband is adjustable in the same manner as the duplex output algorithm.

You decide how the controller is to interact with the process by selecting, through simple keystrokes, the functions you want. Multi-language prompts guide the operator through the configuration process assuring quick and accurate entry of all configurable parameters. Multi-language prompts including French, German, Italian, and Spanish are also available via configuration.

Alarm output terminals are located at the rear terminal panel. One or two alarm relays are available to activate external equipment when preset alarm setpoints are reached. Each of the two alarms can be set to monitor two independent setpoints. Each alarm setpoint can be either high or low alarm. The alarm type can be selected to be either the Process Variable, Deviation, or Setpoint Programming Events. Alarm 1 is dedicated to be activated by the Optional Timer, if enabled.

Control Modes The controller can operate in the following modes: Local Automatic Mode - The controller can operate from one or two local setpoints that can be selected and changed via the keyboard or optional external Contact Input. Remote Automatic Mode The controller operates from the setpoint value applied to the second input. This setpoint can have ratio and bias applied. Selection between local and remote setpoint is via the keyboard or optional Digital Input for remote mode switching. Manual/Automatic Switching (Optional) - The controller can be ordered with bumpless, balanceless transfer between modes using the RESET key. In the manual mode, the operator directly controls the controller output level. In the automatic mode, the controller will operate from a local setpoint, or a remote setpoint provided at the second input.

Diagnostics The controllers have built -in diagnostic tests to ensure reliable operation. Every time power is applied, the microprocessor initiates tests that check the integrity of the information held in various memory locations, and light all the display segments for a status check. These tests also can be operator initiated through the operator interface. Continuous checks are made to check that the inputs are being sampled, the stored constants are secure, and the measured inputs fall within the established range limits. Test failures are identified by various error indications so the source of the trouble can be easily identified.

Calibration The UDC2000 is factory calibrated for all ranges listed in Table 1. When desired, you can perform a field calibration by accessing the required calibration group via the SET UP key. To calibrate, you need only to enter the calibration mode, apply the reference signal and press the CAL key. The calibration is automatically established by the microprocessor, eliminating the need for any mechanical adjustment.

Page 4

51-52-03-08 Page 4

Operator Interface (Figure 2) Status Indicators - They provide the status of the alarm and control relays. There is also indication to show the temperature units and whether Remote setpoint or Local setpoint 2 is active. Displays - A 4 digit, 9 segment upper display is dedicated to the process variable or setpoint during normal operation, with alternate information displayed during configuration. A 6 digit, 14 segment lower display can be configured to indicate PV or SP for the normal display. It also provides guidance, through prompts, for the operator during configuration. Dual Displays - When Dual Display option is specified the upper display is dedicated to the Process Variable. The lower display shows various key selected parameters such as Setpoint 1, Setpoint 2, Deviation, and Output. Keyboard Lockout - For additional security against inadvertent changes or tampering, the following keys can be disabled by configuration: • Man-Auto/Reset • Auto Tune • Run/Hold • Setpoint Select (Function Key during operation)

L2000

F - °Fahrenheit being used C - °Centigrade being used R - Remote or Local SP2 setpoint active L - Local setpoint active

ALM - Alarm conditions exist OUT - Control Relay 1 or 2 on

ALM 1

2 OUT 1 2

SP 2000

FUNCTION

Keys See Figure 3

DISPLAY

AUTO TUNE

MAN-AUTO RESET

F C M A R L

PV

M or A Optional Manual/Auto Display Optional Dual Display

SET UP

RUN HOLD

22066

Figure 2 - Operator Interface

Five keys enable complete configuration and operation FUNCTION

Selects functions within each configuration group. Selects 2nd Setpoint or Remote Setpoint.

DISPLAY

Returns Controller to normal display from Set Up mode. Toggles various operating parameters for display.

MAN-AUTO RESET

In Set Up mode, used to restore original value or selection. Also resets the latching Limit Controller relay. (For Manual/Auto model: selects Manual or Auto mode).

SET UP

Scrolls through the configuration groups.

AUTO TUNE

Initiates Autotune. Increases setpoint or output value. Increases the configuration values or changes functions in Set Up groups. Decreases setpoint or output value. Decreases the configuration values or changes functions in Set Up groups.

RUN HOLD

Enables Run/Hold of the SP Ramp or Program plus Timer start.

Figure 3 - Key Functions

22350

Page 5

51-52-03-08 Page 5

Specifications Design CE Conformity (Europe)

This product is in conformity with the protection requirements of the following European Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMC Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be assumed.

Product Classification:

Class I: Permanently Connected, Panel Mounted Industrial Control Equipment with protective earthing (grounding). (EN 61010-1)

Enclosure Rating:

Panel Mounted Equipment, IP 00, this controller must be panel mounted. Terminals must be enclosed within the panel. Front panel IP 65 (IEC 529).

Installation Category (Overvoltage Category):

Category II: Energy-consuming equipment supplied from the fixed installation. Local level appliances, and Industrial Control Equipment. (EN 61010-1)

Pollution Degree:

Pollution Degree 2: Normally non-conductive pollution with occasional conductivity caused by condensation. (Ref. IEC 664-1)

EMC Classification:

Group 1, Class A, ISM Equipment (EN 55011, emissions), Industrial Equipment (EN 50082-2, immunity)

Method of EMC Assessment:

Technical File (TF)

Declaration of Conformity:

513093000-000.

Accuracy

±0.3% of span typical (± 1 digit for display) 14 bit resolution typical

Temperature Stability

±0.8% for 50˚F (28˚C) change

Input Signal Failure Protection

Thermocouple Inputs: Upscale or downscale burnout Burnout Current: 0.2 microamps Failsafe Output Level: Configurable 0-100%

Input Impedance

4-20 Milliampere Input: 250 Ohms All Voltage Inputs: 200K Ohms Thermocouples: 10 Megohms Resistance Temperature Detector: 10K Ohms

Stray Rejection

Common Mode: AC (50 or 60 Hz): 120dB (with maximum source impedance of 100 Ohms) or ± 1 LSB (least significant bit) whichever is greater.

Normal Mode AC (50 or 60 Hz): 60 dB (with 100% span peak-to-peak maximum)

Continued next page

Page 6

51-52-03-08 Page 6

Specifications, continued Design (continued) Controller Output Types

Current Output Range can be set between 4 to 20 mA, and as direct or reverse action. Minimum output level is 3.2 mA dc. Resolution: 11 bits for 4 to 20 mA Accuracy: 0.5% full scale Temperature Stability: 0.03% / ˚C Load Resistance: 0 to 750 ohms (ungrounded) Electromechanical Relay SPST contacts. Normally Open or Normally Closed contacts selectable by jumper. Internally socketed (Control Output #1) Resistive Load: 5 amps @ 120 Vac, 30 Vdc, 2.5 amps @ or 240 Vac Inductive Load: 50 VA @ 120 Vac, or 240 Vac Motor: 1/6 H.P. Solid State Relay SPST solid state contact consisting of a triac N.O. output. Internally socketed Resistive Load: 1.0 amp @ 25 ˚C and 120 or 240 Vac 0.5 amp @ 55 ˚C and 120 or 240 Vac Inductive Load: 50 VA @ 120 Vac or 240 Vac Open Collector Outputs Maximum Sink Current: 20 mA Overload Protection: 100 mA Internally powered @ 34 Vdc Opto-isolated from all other circuits but not from each other. Socketed jumper assembly replaces relay. Solid State Relays (2 amps or 10 amps) Externally mounted triac N.O. output for use with open collector output. 2 amp Relay Resistive Load: 3 amps @ 25 ˚C and 120 or 240 Vac 2 amps @ 55 ˚C and 120 or 240 Vac 10 amp relay Resistive Load: 15 amps @ 25 ˚C and 120 or 240 Vac 10 amps @ 55 ˚C and 120 or 240 Vac Inductive Load: 50 VA @ 120 Vac or 240 Vac Motor Rating: 1 HP @ 25 ˚C 0.75 HP @ 55 ˚C

Alarm Output (Optional)

One SPST electromechanical relay. Normally Open or Normally Closed contact is selectable by jumper. A second alarm is available except with Time Proportional Relay Duplex, Three Position Step and Limit Control Models. Alarm 2 can start the optional timer. Up to four setpoints are independently set as high or low alarm, two for each relay. Setpoint can be either Process Variable, Deviation, or Setpoint Programming Events. Timer Output: Alarm 1.

Alarm Relay Contacts Resistive Load: 5 amps @ 120 Vac or 30 Vdc, 2.5 amps @ 240 Vac Hysteresis: Adjustable: 0 to 100% of (PV) Input Span

Continued next page