The text of a spec sheet · part 2 of 2

UDC2000 Mini-Pro Universal Digital Controller Specification, pages 7 to 12

Pages 7 to 12 of 12

The original document is the PDF (128 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Honeywell UDC2000

Page 7

51-52-03-08 Page 7

Specifications, continued Design (continued) Controller Output Algorithms

On-Off or Time Proportional One SPST relay or open collector output. Control action can be set for direct or reverse. On/Off Control Hysteresis: Adjustable 0 to 100% of (PV) Input Span. On-Off Duplex, Three Position Step Control, or Time Proportional Duplex Two SPST relays. Control action can be set for direct or reverse. Current Proportional 4 to 20 mA dc maximum into a load of 0 to 750 ohms. Output range can be set direct or reverse action. Limit Control One SPST electromechanical latching relay. Control relay action Normally Open. (Normally Closed contact selectable by jumper.)

Auxiliary PV Output (Optional)*

The Process Variable Output can be scaled for any PV range from 0 to 5 Volts for 0 to 100%, with an overrange capability of 5.25 Volts at 105% output. The scale selection is configured through the operator interface. Voltage: 1 to 5 Volts (can be field calibrated to 0 to 5 Volts) Minimum Impedance: 2500 Ohms Resolution: 12 bits over 0 to 5.25 Volts Accuracy: 0.4% Full Scale at 2500 Ohm load Temperature Stability: 0.06% / ˚C

Digital Input (Optional)*

+20 Vdc source for external dry contact or isolated solid state contact. Contact closure selects one of the following actions: • Local setpoint 1 from Remote setpoint • Local setpoint 2 from Local setpoint 1 • Reset of Limit Controller • To Hold from Run (SP Ramp or SP Programming) • Disabled Keyboard • To Run - contact closure starts Setpoint Program or Single SP Ramp. Re-opening contact returns to Hold. The following Digital Input selections are available on models that contain the pertinent options: • Timer Start - momentary contact closure will start timer. • To Manual - contact closure switches to Manual mode. Re-opening contact switches back to Automatic mode. • To Manual /Failsafe Output - contact closures switches to Manual mode plus configured Failsafe Output value. Re-opening contact switches back to Automatic.

Setpoint Ramp/Soak Programming (Optional)

Lets you configure 6 ramp and 6 soak segments to be stored for use as one program or several small programs. You designate the beginning and end segments to determine where the program is to start and stop allowing several small programs. Each ramp segment can be configured to be run in Hours and Minutes or degrees per minute. Soak segments can have a guaranteed soak deviation which guarantees the time for each soak and will not start until the PV is reached.

Sampling Rate

Inputs sampled 3 times per second

Input Filter

Software: Single pole lowpass section with selectable time constants, off to 120 seconds for each input.

* Auxiliary Output and Digital Input are mutually exclusive.

Continued next page

Page 8

51-52-03-08 Page 8

Specifications, continued Design (continued) Digital Displays

Vacuum fluorescent, 9 segment and 14 segment, alphanumeric. A four digit display dedicated to the process variable, setpoints, deviation or output depending upon the model number. Alternate information displayed during configuration mode. A six character display primarily provides guidance during controller configuration.

Status Indicators

Alarm Relay Status (ALM 1 or 2) Temperature Units (F or C) Remote Setpoint or Local Setpoint 2 Active (R) Control Relay Status (OUT 1 or 2)

Dimensions

See Figure 5.

Mounting

Panel-mounted, 4.2 inch depth

Wiring Connections

Screw terminals on the rear of the case (6-32)

Power Consumption

6 VA

Weight

1 kg (2.2 lbs.)

Environmental and Operating Conditions Parameter

Reference

Rated

Operative Limits

Transportation and storage

Ambient Temperature

22 ± 3˚C 72 ± 5˚F

15 to 55˚C 58 to 131˚F

0 to 55˚C 32 to 131˚F

-40 to 66˚C -40 to 151˚F

Relative Humidity Vibration Frequency (Hz) Acceleration (g)

10 to 55*

10 to 90*

5 to 90*

5 to 95*

0 0

0 to 70 0.1

0 to 200 0.5

0 to 200 0.5

0 0

1 30

5 30

20 30

Voltage (Vac)

120 ± 1 240 ± 2

102 to 132 204 to 264

102 to 132 204 to 264

---

Frequency (Hz)

50 ± 0.2 60 ± 0.2

49 to 51 59 to 61

48 to 52 58 to 62

---

Mechanical Shock Acceleration (g) Duration (ms))

* The maximum rating only applies up to 40˚C (104 ˚F). For higher temperatures, the RH specification is derated to maintain constant moisture content.

Page 9

51-52-03-08 Page 9

General Reference Data Data Isolation (Functional)

No isolation between analog input and analog output circuits.

AC Power : is electrically isolated from all other inputs and outputs to withstand a HIPOT potential of 1900Vdc for 2 seconds per Annex K of EN61010-1. Radio Frequency Interference (RFI)

Immunity: No effect on performance from a 5 W walkie-talkie operated at 27, 151 or 450 MHz, one meter from the controller.

Surge Withstand Capability (SWC)

ANSI/IEEE C37.90.1, Surge Withstand Capability (SWC) (Formerly IEEE 472) Mains power input and relay contact outputs: 2.5 kV, Common Mode and Differential Mode. All other circuits: 1.0 kV, Common Mode and Differential Mode.

Table 1 - Field Selectable Input Actuations Range PV Input

˚F

˚C

Thermocouples B E E (low) J J (low) K K (low) Nicrosil Nisil NiNiMoly (N) R S T T (low) W5W26

150 -100 -100 0 0 0 -20 0 32 0 0 -300 -80 0 to 3300 to 1832 to 1100 to 1600 to 900 to 2400 to 1000 to 2372 to 2500 to 3100 to 3100 to 700 to 500 to 4200

66 -73 -73 -18 -18 -18 -29 -17.8 0 -18 -18 -184 -63 -18 to to to to to to to to to to to to to to

1815 1000 593 871 482 1316 538 1300 1371 1704 1704 371 260 2316

-300 to 900 0 to 300

-184 to -18 to

482 149

1400 to 3400

760

RTD (IEC) 100 Ohm Pt. 100 Ohm Pt. (low) Radiamatic RH to 1871

Linear Milliamps dc Millivolts dc Volts dc

4 0 0 0 0 1 0 to 20 to 10 to 100 to 1 to 5 to 5 to 10

Linear Ranges not available on Limit Control Models

Page 10

51-52-03-08 Page 10

Model Number Interpretation

Key Number

Table 1

D C 2 0 0 Controller Output #1 C = Current 4 – 20mA E = Relay, Electromechanical – 5AMP A = Relay, Solid State AC – 1AMP T = Open Collector Output – 20mA Limit Control Output H = High Limit (T/C and RTD inputs only) L = Low Limit (T/C and RTD inputs only) Digital Indicator I = Digital Indicator Only Additional Relays O = None 1 = Second relay for Duplex Output or 3 Position Step plus One Alarm Relay 2 = Two Alarm Relays (only 1 Alarm on Limit Models) 3 = Timer (or Alarm 1) plus Second Relay for Duplex Output or 3 Pos Step 4 = Timer (or Alarm 1) plus Second Alarm Relay External Interface O – – = None 2 – – = Auxiliary Output or Digital Input Optional Input – O – = None – 1 – = 4 -20 mA or 1- 5V

Table 2

Table 3

Table 4

0 Custom Configuration – – – – OO = None – – – – BO = Blue Elastomer Bezel – – – – TO = Tan Elastomer Bezel Custom ID Tag – – – O – –= None – – – T – – = Tag (1 line 30 characters Max.) Solid State Relay Kits (Externally Mounted) – – O – – – = None – – 1 – – – = 10 Amps – – 2 – – – = 2 Amps Approval Bodies – O – – – – = None – F – – – – = FM approved – C – – – – = CSA certification – D – – – – = FM and CSA – T – – – – = TUV and VDE – A – – – – = FM, CSA, TUV and VDE Instrument Power Configuration * 1 – – – – –= 120Vac (50/60 Hz) 2 – – – – –= 240Vac (50/60 Hz) * Power jumper is set at factory, but can be changed by user. 20748

Software Options – – O = None – – A = Autotune – – B = Autotune and Setpoint Programming – – D = Dual Display and Autotune – – E = Dual Display, Autotune and SP Prog – – F = Manual/Auto Modes (includes Dual Display and Autotune) – – G = Manual/Auto Modes and SP Prog (includes Dual Display and Autotune)

Figure 4 - Model Selection Guide

Page 11

51-52-03-08 Page 11

L

Dimensions +0.8 +0.008 90 92 =0.0 -0.0 +0.03 3.5906 3.622 +0.031 -0.0

96 3.780

ALM

OUT

12

FC

12

MA

PV

RL

96 3.780

Panel Cutout FUNCTION

DISPLAY

MAN-AUTO RESET

+0.008 92 -0.0 3.622 +0.031 -0.0

SET UP RUN HOLD

AUTO TUNE

24 Max Panel .945 Thickness

10 Max (2) .394

2.62 with optional .103 rear cover

90.7 3.57

21.0 .826

105.4 4.19

Figure 5 - UDC2000 Mini-Pro Controller dimensions - not to scale

Dimensions: Millimeters Inches 20751

Page 12

51-52-03-08 Page 12

Ordering Information For the complete ordering information, request Model Selection Guide: 51-51-16-33 for UDC2000 Controller. Honeywell offers a full line of Sensors, Transmitters, and Final Control Devices for use with the UDC2000 Controller. These devices include: Thermocouples, RTDs Digital Panel Indicator, Pressure Transmitters, Flow Transmitters, Liquid Level Transmitters. Valve, Actuators, and Electric Motors.

Specifications are subject to change without notice.

Distributor :

For more information, contact your nearest Honeywell Response Center listed below.

Industrial Automation and Control Honeywell Inc. In the U.S.A.: Honeywell Industrial Automation and Control, 1100 Virginia Drive., Ft. Washington, PA 19114, (800) 343-0228 In Europe: Honeywell S.A., 80084 Amiens Cedex 2, (33) 22.54.56.56 Honeywell Control System Ltd., Honeywell House, Bracknell, UK-RG 12 1 EB, (44) 1344 826000 In Japan: Yamatake-Honeywell Co. Ltd., Nagai Int’l Bldg., 2 - 12 - 19 Shibuya-Ku, Tokyo 150 Japan, 81-3-3486-2051 In Asia: Honeywell Asia Pacific Inc., Room 3213-3225, Sun Hung kai Centre, No. 30 Harbor Road, Wanchai, Hong Kong, (852) 829-8298 In the Mediterranean: Africa and Middle East Region, Honeywell SpA, Via Vittor Pisani 13, 20124 Milano, Italy (39-2) 67731 Honeywell Pacific Division: Honeywell Pty Ltd., 5 Thomas Holt Drive, North Ryde Sydney, NSW Australia 2113, (61-2) 353 7000 In Canada: The Honeywell centre, 155 Gordon Baker Road., Ontario M2H 3N7, 1-800-461-0013 In Latin America: Honeywell Inc.,14505 Commerce Way, Suite 500, Miami Lakes, Florida 33016-1556, (305) 364-2300