The text of a spec sheet · part 2 of 2
UDC2000 Mini-Pro Universal Digital Controller Specification, pages 7 to 12
Pages 7 to 12 of 12
The original document is the PDF (128 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Honeywell UDC2000
Page 7
51-52-03-08 Page 7
Specifications, continued Design (continued) Controller Output Algorithms
On-Off or Time Proportional One SPST relay or open collector output. Control action can be set for direct or reverse. On/Off Control Hysteresis: Adjustable 0 to 100% of (PV) Input Span. On-Off Duplex, Three Position Step Control, or Time Proportional Duplex Two SPST relays. Control action can be set for direct or reverse. Current Proportional 4 to 20 mA dc maximum into a load of 0 to 750 ohms. Output range can be set direct or reverse action. Limit Control One SPST electromechanical latching relay. Control relay action Normally Open. (Normally Closed contact selectable by jumper.)
Auxiliary PV Output (Optional)*
The Process Variable Output can be scaled for any PV range from 0 to 5 Volts for 0 to 100%, with an overrange capability of 5.25 Volts at 105% output. The scale selection is configured through the operator interface. Voltage: 1 to 5 Volts (can be field calibrated to 0 to 5 Volts) Minimum Impedance: 2500 Ohms Resolution: 12 bits over 0 to 5.25 Volts Accuracy: 0.4% Full Scale at 2500 Ohm load Temperature Stability: 0.06% / ˚C
Digital Input (Optional)*
+20 Vdc source for external dry contact or isolated solid state contact. Contact closure selects one of the following actions: • Local setpoint 1 from Remote setpoint • Local setpoint 2 from Local setpoint 1 • Reset of Limit Controller • To Hold from Run (SP Ramp or SP Programming) • Disabled Keyboard • To Run - contact closure starts Setpoint Program or Single SP Ramp. Re-opening contact returns to Hold. The following Digital Input selections are available on models that contain the pertinent options: • Timer Start - momentary contact closure will start timer. • To Manual - contact closure switches to Manual mode. Re-opening contact switches back to Automatic mode. • To Manual /Failsafe Output - contact closures switches to Manual mode plus configured Failsafe Output value. Re-opening contact switches back to Automatic.
Setpoint Ramp/Soak Programming (Optional)
Lets you configure 6 ramp and 6 soak segments to be stored for use as one program or several small programs. You designate the beginning and end segments to determine where the program is to start and stop allowing several small programs. Each ramp segment can be configured to be run in Hours and Minutes or degrees per minute. Soak segments can have a guaranteed soak deviation which guarantees the time for each soak and will not start until the PV is reached.
Sampling Rate
Inputs sampled 3 times per second
Input Filter
Software: Single pole lowpass section with selectable time constants, off to 120 seconds for each input.
* Auxiliary Output and Digital Input are mutually exclusive.
Continued next page
Page 8
51-52-03-08 Page 8
Specifications, continued Design (continued) Digital Displays
Vacuum fluorescent, 9 segment and 14 segment, alphanumeric. A four digit display dedicated to the process variable, setpoints, deviation or output depending upon the model number. Alternate information displayed during configuration mode. A six character display primarily provides guidance during controller configuration.
Status Indicators
Alarm Relay Status (ALM 1 or 2) Temperature Units (F or C) Remote Setpoint or Local Setpoint 2 Active (R) Control Relay Status (OUT 1 or 2)
Dimensions
See Figure 5.
Mounting
Panel-mounted, 4.2 inch depth
Wiring Connections
Screw terminals on the rear of the case (6-32)
Power Consumption
6 VA
Weight
1 kg (2.2 lbs.)
Environmental and Operating Conditions Parameter
Reference
Rated
Operative Limits
Transportation and storage
Ambient Temperature
22 ± 3˚C 72 ± 5˚F
15 to 55˚C 58 to 131˚F
0 to 55˚C 32 to 131˚F
-40 to 66˚C -40 to 151˚F
Relative Humidity Vibration Frequency (Hz) Acceleration (g)
10 to 55*
10 to 90*
5 to 90*
5 to 95*
0 0
0 to 70 0.1
0 to 200 0.5
0 to 200 0.5
0 0
1 30
5 30
20 30
Voltage (Vac)
120 ± 1 240 ± 2
102 to 132 204 to 264
102 to 132 204 to 264
---
Frequency (Hz)
50 ± 0.2 60 ± 0.2
49 to 51 59 to 61
48 to 52 58 to 62
---
Mechanical Shock Acceleration (g) Duration (ms))
* The maximum rating only applies up to 40˚C (104 ˚F). For higher temperatures, the RH specification is derated to maintain constant moisture content.
Page 9
51-52-03-08 Page 9
General Reference Data Data Isolation (Functional)
No isolation between analog input and analog output circuits.
AC Power : is electrically isolated from all other inputs and outputs to withstand a HIPOT potential of 1900Vdc for 2 seconds per Annex K of EN61010-1. Radio Frequency Interference (RFI)
Immunity: No effect on performance from a 5 W walkie-talkie operated at 27, 151 or 450 MHz, one meter from the controller.
Surge Withstand Capability (SWC)
ANSI/IEEE C37.90.1, Surge Withstand Capability (SWC) (Formerly IEEE 472) Mains power input and relay contact outputs: 2.5 kV, Common Mode and Differential Mode. All other circuits: 1.0 kV, Common Mode and Differential Mode.
Table 1 - Field Selectable Input Actuations Range PV Input
˚F
˚C
Thermocouples B E E (low) J J (low) K K (low) Nicrosil Nisil NiNiMoly (N) R S T T (low) W5W26
150 -100 -100 0 0 0 -20 0 32 0 0 -300 -80 0 to 3300 to 1832 to 1100 to 1600 to 900 to 2400 to 1000 to 2372 to 2500 to 3100 to 3100 to 700 to 500 to 4200
66 -73 -73 -18 -18 -18 -29 -17.8 0 -18 -18 -184 -63 -18 to to to to to to to to to to to to to to
1815 1000 593 871 482 1316 538 1300 1371 1704 1704 371 260 2316
-300 to 900 0 to 300
-184 to -18 to
482 149
1400 to 3400
760
RTD (IEC) 100 Ohm Pt. 100 Ohm Pt. (low) Radiamatic RH to 1871
Linear Milliamps dc Millivolts dc Volts dc
4 0 0 0 0 1 0 to 20 to 10 to 100 to 1 to 5 to 5 to 10
Linear Ranges not available on Limit Control Models
Page 10
51-52-03-08 Page 10
Model Number Interpretation
Key Number
Table 1
D C 2 0 0 Controller Output #1 C = Current 4 – 20mA E = Relay, Electromechanical – 5AMP A = Relay, Solid State AC – 1AMP T = Open Collector Output – 20mA Limit Control Output H = High Limit (T/C and RTD inputs only) L = Low Limit (T/C and RTD inputs only) Digital Indicator I = Digital Indicator Only Additional Relays O = None 1 = Second relay for Duplex Output or 3 Position Step plus One Alarm Relay 2 = Two Alarm Relays (only 1 Alarm on Limit Models) 3 = Timer (or Alarm 1) plus Second Relay for Duplex Output or 3 Pos Step 4 = Timer (or Alarm 1) plus Second Alarm Relay External Interface O – – = None 2 – – = Auxiliary Output or Digital Input Optional Input – O – = None – 1 – = 4 -20 mA or 1- 5V
Table 2
Table 3
Table 4
0 Custom Configuration – – – – OO = None – – – – BO = Blue Elastomer Bezel – – – – TO = Tan Elastomer Bezel Custom ID Tag – – – O – –= None – – – T – – = Tag (1 line 30 characters Max.) Solid State Relay Kits (Externally Mounted) – – O – – – = None – – 1 – – – = 10 Amps – – 2 – – – = 2 Amps Approval Bodies – O – – – – = None – F – – – – = FM approved – C – – – – = CSA certification – D – – – – = FM and CSA – T – – – – = TUV and VDE – A – – – – = FM, CSA, TUV and VDE Instrument Power Configuration * 1 – – – – –= 120Vac (50/60 Hz) 2 – – – – –= 240Vac (50/60 Hz) * Power jumper is set at factory, but can be changed by user. 20748
Software Options – – O = None – – A = Autotune – – B = Autotune and Setpoint Programming – – D = Dual Display and Autotune – – E = Dual Display, Autotune and SP Prog – – F = Manual/Auto Modes (includes Dual Display and Autotune) – – G = Manual/Auto Modes and SP Prog (includes Dual Display and Autotune)
Figure 4 - Model Selection Guide
Page 11
51-52-03-08 Page 11
L
Dimensions +0.8 +0.008 90 92 =0.0 -0.0 +0.03 3.5906 3.622 +0.031 -0.0
96 3.780
ALM
OUT
12
FC
12
MA
PV
RL
96 3.780
Panel Cutout FUNCTION
DISPLAY
MAN-AUTO RESET
+0.008 92 -0.0 3.622 +0.031 -0.0
SET UP RUN HOLD
AUTO TUNE
24 Max Panel .945 Thickness
10 Max (2) .394
2.62 with optional .103 rear cover
90.7 3.57
21.0 .826
105.4 4.19
Figure 5 - UDC2000 Mini-Pro Controller dimensions - not to scale
Dimensions: Millimeters Inches 20751
Page 12
51-52-03-08 Page 12
Ordering Information For the complete ordering information, request Model Selection Guide: 51-51-16-33 for UDC2000 Controller. Honeywell offers a full line of Sensors, Transmitters, and Final Control Devices for use with the UDC2000 Controller. These devices include: Thermocouples, RTDs Digital Panel Indicator, Pressure Transmitters, Flow Transmitters, Liquid Level Transmitters. Valve, Actuators, and Electric Motors.
Specifications are subject to change without notice.
Distributor :
For more information, contact your nearest Honeywell Response Center listed below.
Industrial Automation and Control Honeywell Inc. In the U.S.A.: Honeywell Industrial Automation and Control, 1100 Virginia Drive., Ft. Washington, PA 19114, (800) 343-0228 In Europe: Honeywell S.A., 80084 Amiens Cedex 2, (33) 22.54.56.56 Honeywell Control System Ltd., Honeywell House, Bracknell, UK-RG 12 1 EB, (44) 1344 826000 In Japan: Yamatake-Honeywell Co. Ltd., Nagai Int’l Bldg., 2 - 12 - 19 Shibuya-Ku, Tokyo 150 Japan, 81-3-3486-2051 In Asia: Honeywell Asia Pacific Inc., Room 3213-3225, Sun Hung kai Centre, No. 30 Harbor Road, Wanchai, Hong Kong, (852) 829-8298 In the Mediterranean: Africa and Middle East Region, Honeywell SpA, Via Vittor Pisani 13, 20124 Milano, Italy (39-2) 67731 Honeywell Pacific Division: Honeywell Pty Ltd., 5 Thomas Holt Drive, North Ryde Sydney, NSW Australia 2113, (61-2) 353 7000 In Canada: The Honeywell centre, 155 Gordon Baker Road., Ontario M2H 3N7, 1-800-461-0013 In Latin America: Honeywell Inc.,14505 Commerce Way, Suite 500, Miami Lakes, Florida 33016-1556, (305) 364-2300