Page 101

7.8

Parts Replacement Procedures, Continued

MCU/output board

Follow the procedure listed in Table 7-19 to replace the following MCU/output boards: • Relay Output - P/N 51309401-506 Table 7-19

MCU/Output Board Replacement Procedure

Step

1/01

Action

1

Remove the chassis from the case. See Figure 7-1.

2

Remove the printed wiring boards from the chassis. See Figure 7-3.

3

Lay the boards flat and identify the MCU/Output board. See Figure 7-4.

4

Each option board is held onto the MCU/Output board with three posts. Locate these posts under the MCU/Output board.

5

Use small pliers and squeeze the ends of each post together and push it up through the board. Remove the option boards present.

6

Remove the transformer connections to the Digital Input board and the Communications board, if present.

7

Remove the Digital Input Board, if present. See Table 7-17.

8

Remove the Communications board, if present. See Table 7-18.

9

Replace the MCU/Output board.

10

Reinstall the Digital Input board, if present, onto the new MCU/Output board.

11

Reinstall the Communications board, if present, onto the new MCU/Output board.

12

Reinstall the transformer connectors to the Digital Input board and Communications board, if present.

13

Slide the printed wiring boards back into the chassis. Make sure the connections to the display/keyboard assembly are made and that the release points on the chassis snap into place on the printed wiring boards.

14

Reinstall the chassis into the case. Push in hard, then tighten the screw.

UDC3300 Limit Controller Product Manual

91

Page 102

7.9 Cleaning

92

Maintenance If you find it necessary to clean the elastomer bezel, use a 50% alcohol solution or mild soapy water.

UDC3300 Limit Controller Product Manual

1/01

Page 103

Section 8 – Parts List 8.1

Exploded View

Introduction

Figure 8-1

Figure 8-1 is an exploded view of the UDC3300 Limit Controller. Each part is labeled with a key number. The part numbers are listed by key number in Table 8-1. There is a list of parts not shown in Table 8-2. UDC3300 Exploded View 5

6

7

8

22650

1

2

3

4

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

93

Page 104

8.1

Exploded View, Continued

Parts identification

Table 8-1 lists the part numbers for the key numbers shown in the exploded view. Table 8-1 Parts Identification Key Numbe r

Part Number

1

30756667-502

Bezel Assembly - Gray

1

2

30756672-501

Display/Keyboard Printed Wiring Assembly

1

3

30756690-501 30756693-501

DMCS Communications PWB RS422/485 Communications PWB

1

Power/Input Printed Wiring Board

1

4

8.2

Description

51309404-502 51309404-501

90 to 264 Vac 24 Vac/dc

5

51309401-506

Limit Control MCU/Output Printed Wiring Board

1

6

30755306-501

Relay, Electromechanical

2

7

30756696-501

Digital Input Printed Wiring Board

1

8

30756721-501

Case Assembly

1

Parts Not Shown

Parts not shown

Table 8-2 lists the part numbers of the parts not show in the exploded view. Table 8-2 Parts Not Shown Part Number

94

Quantity

Description

Quantity

30731996-506

4-20 mA Resistor Assembly, 250 ohms

1

30754465-501

0-10 Volt Input Resistor Assembly, 100K Pair

1

30752481-501 30752481-502

Varistor, 120V Varistor, 240V

1

30755050-001

Mounting Kit

1

30756764-002

Rear Cover Kit

1

30755223-002 30755223-003

DIN Adapter Kit, Blue DIN Adapter Kit, Gray

1

30757088-501

Cold Junction Resistor

1

30756683-001

NEMA 3 Gasket (panel to case)

30757215-001

NEMA 4 Front Face Kit

1

30757069-001

Bezel Cover

1

UDC3300 Limit Controller Product Manual

1/01

Page 105

Section 9 - Appendix A How to Apply Digital Instrumentation in Severe Electrical Noise Environments

9.1

Overview

Guideline overview

Products that incorporate digital technology provide recognized performance advantages over conventional analog instrumentation used for process control. These advantages can result in better product uniformity and greater overall efficiency when used correctly. There are, however, certain guidelines regarding installation and wiring which must be carefully followed in order to achieve this performance. In addition to the traditional precaution of the separation of signal and power wiring in separate conduits, other measures must be taken to minimize the effects of electromagnetic interference (EMI) and radio frequency interference (RFI) on the operation of the equipment. Otherwise, if high level, short duration, noise spikes are permitted to enter the digital equipment, the noise can be transferred into the system’s logic networks and can be misinterpreted as signal data, resulting in erroneous system operation and other unpredictable responses.

What’s in this section

This section contains the following information: Topic

1/01

See Page

9.1

Overview

95

9.2

Potential Noise Sources

96

9.3

Prevention Methods

97

9.4

Recommended Wiring Practices

98

9.5

Power Source Considerations

100

9.6

Noise Suppression at the Source

101

UDC3300 Limit Controller Product Manual

95

Page 106

9.2

Potential Noise Sources

Overview

Noise can enter electronic equipment via three methods of coupling, namely: • Capacitive (or electrostatic) • Inductive (or magnetic) • Impedance.

Capacitive and inductive coupling

Capacitive and inductive coupling have the same essential effect, they couple current or voltage, without any actual connection of the two circuits. Impedance coupling requires a connection between the two circuits. Typical noise-generating sources that could affect electronic equipment through capacitive and inductive coupling include: • • • • • •

Impedance coupled noise

Relay coils Solenoids AC power wires, particularly at or above 100 Vac Current carrying cables Thyristor field exciters Radio frequency transmissions.

Impedance-coupled noise may enter by way of the lines used to power the digital equipment or by way of improper grounding. Most power lines, at typical industrial locations, are far from noise-free. The noise on them can be generated in many ways, but are nearly always associated with switching circuits of some nature. These include: • • • • • • •

96

Large relays Contactors Motor starters Business and industrial machines Power tools HID (high intensity discharge) lights Silicon controlled rectifiers (SCRs) that are phase-angled fired.

UDC3300 Limit Controller Product Manual

1/01

Page 107

9.3

Prevention Methods

Introduction

There are three ways to prevent electrical noise from interfering with the operation of the electronic digital equipment. • Built-in noise rejection • Separation of signal and power lines • Noise suppression at source

Built-in noise rejection

The first method is to design the digital equipment with a high degree of noise rejection built-in. This includes housing the equipment in a case that will provide shielding, liberal use of noise rejection filters and optoisolators, and the use of noise suppressors on potential noise sources within the equipment itself. This, of course, is the responsibility of the manufacturer who usually performs extensive laboratory and field testing of newly designed digital equipment to insure the adequacy of its immunity to noise. As a minimum requirement, the equipment should be able to pass the tests outlined in the IEEE Standard 472-1974 (Surge Withstand Capacity Tests).

Signal and power line separation

The second method is to prevent noise from getting on the signal and power lines that are connected to the equipment. This is achieved by proper separation and shielding of those lines. In some cases, separate power lines or special power line regulation or filtering may be required for satisfactory electronic digital equipment operation. It is the responsibility of the installer to follow good wiring practices.

Suppression at the source

The third prevention method is to suppress the noise at its source. This is the most effective but also the most difficult because it is not easy to identify all of the potential noise sources in a typical industrial installation. Therefore, “suppression” is usually a last resort for those extreme situations where the other methods are insufficient by themselves. See Noise Suppression at Source which follows.

1/01

UDC3300 Limit Controller Product Manual

97

Page 108

9.4

Recommended Wiring Practices

General rules

• All wiring must conform to local codes and practices. • Wires carrying similar types of signals (Table 9-1) may be bundled together, but bundles with different types of signals must be kept separated to prevent inductive or capacitive coupling.

Wire bundling

Table 9-1 shows what wiring should be bundled together to prevent inductive or capacitive coupling. Table 9-1

External Wiring Wire Function

No. 1 2 3

4

5

6 7

Bundle No.

Are Shielded Twisted Wires Recommended?

HIGH VOLTAGE Line Power Earth Ground Line Voltage Digital I/O

1

NO

ANALOG I/O Process Variable RTD Thermocouple dc Millivolts Low level (<100V) 4-20 mA dc 1-5 Vdc

2

YES

DIGITAL I/O Low Voltage (<100V) Computer Interface

3

YES

Type

Continued on next page

98

UDC3300 Limit Controller Product Manual

1/01

Page 109

9.4

Recommended Wiring Practices, Continued

Additional rules

Please observe these additional rules for wire bundling: • For distances over five (5) feet, and when shielding is recommended, use a separate metal tray or conduit for each bundle. Where conduits or trays are not practical, use twisted wires with a metal overbraid and provide physical separation of at least one foot. • Tray covers must be in continuous contact with the side rails of the trays. • When unlike signal levels must cross, either in trays or conduits, they should cross at a 90-degree angle and at a maximum spacing. Where it is not possible to provide spacing, a grounded steel barrier or grid should be placed between the unlike levels at the crossover points. • Trays containing low level wiring should have solid bottoms and sides. Tray covers must be used for complete shielding. Tray cover contact with side rails must be positive and continuous to avoid high reluctance air gaps, which impair shielding. Trays for low level cables should be metal and solidly grounded. • Wires containing low level signals should not be routed near any of the following: – Contactors – Motors – Generators – Radio transmitters – Wires carrying high current that is being switched on and off. • Use a 12-gage (or heavier) insulated stranded wire for the ground connection. Attach it firmly to a proven good earth ground such as a metal stake driven into the ground. • All shields should be grounded at one end only, preferably the instrument end.

1/01

UDC3300 Limit Controller Product Manual

99

Page 110

9.5

Power Source Considerations

Operate within limits

The AC power for the digital electronic equipment must be within the voltage and frequency limits specified for that equipment. Attempts to operate outside the specified limits will result in no performance. For those installations where the supply voltage will not stay within the specified limits, a ferroresonant transformer, for voltage resolution, should be used.

Independent AC source

For protection against noise, the AC source for the digital electronic equipment should be independent of all other loads especially when switching loads are involved. For example, it should not provide power for air-conditioning, convenience outlets, lighting, motors, or similar noise- generating devices. To obtain electrical isolation (see Figure 9-1) a separate transformer is required to supply power to the digital equipment. For additional noise and transient rejection, shielded primary and secondary windings may be required. And, if necessary, power line filters may be added to attenuate noise signals that have a higher frequency than the power line frequency.

Transformer for digital equipment

Figure 9-1 is an illustration of a separate transformer required to supply power to digital equipment. Figure 9-1

Transformer for Digital Equipment

H Power source 120/240 Vac single phase

N

H

N

To digital electronic equipment

G 20779

100

UDC3300 Limit Controller Product Manual

1/01