Page 101
7.8
Parts Replacement Procedures, Continued
MCU/output board
Follow the procedure listed in Table 7-19 to replace the following MCU/output boards: • Relay Output - P/N 51309401-506 Table 7-19
MCU/Output Board Replacement Procedure
Step
1/01
Action
1
Remove the chassis from the case. See Figure 7-1.
2
Remove the printed wiring boards from the chassis. See Figure 7-3.
3
Lay the boards flat and identify the MCU/Output board. See Figure 7-4.
4
Each option board is held onto the MCU/Output board with three posts. Locate these posts under the MCU/Output board.
5
Use small pliers and squeeze the ends of each post together and push it up through the board. Remove the option boards present.
6
Remove the transformer connections to the Digital Input board and the Communications board, if present.
7
Remove the Digital Input Board, if present. See Table 7-17.
8
Remove the Communications board, if present. See Table 7-18.
9
Replace the MCU/Output board.
10
Reinstall the Digital Input board, if present, onto the new MCU/Output board.
11
Reinstall the Communications board, if present, onto the new MCU/Output board.
12
Reinstall the transformer connectors to the Digital Input board and Communications board, if present.
13
Slide the printed wiring boards back into the chassis. Make sure the connections to the display/keyboard assembly are made and that the release points on the chassis snap into place on the printed wiring boards.
14
Reinstall the chassis into the case. Push in hard, then tighten the screw.
UDC3300 Limit Controller Product Manual
91
Page 102
7.9 Cleaning
92
Maintenance If you find it necessary to clean the elastomer bezel, use a 50% alcohol solution or mild soapy water.
UDC3300 Limit Controller Product Manual
1/01
Page 103
Section 8 – Parts List 8.1
Exploded View
Introduction
Figure 8-1
Figure 8-1 is an exploded view of the UDC3300 Limit Controller. Each part is labeled with a key number. The part numbers are listed by key number in Table 8-1. There is a list of parts not shown in Table 8-2. UDC3300 Exploded View 5
6
7
8
22650
1
2
3
4
Continued on next page
1/01
UDC3300 Limit Controller Product Manual
93
Page 104
8.1
Exploded View, Continued
Parts identification
Table 8-1 lists the part numbers for the key numbers shown in the exploded view. Table 8-1 Parts Identification Key Numbe r
Part Number
1
30756667-502
Bezel Assembly - Gray
1
2
30756672-501
Display/Keyboard Printed Wiring Assembly
1
3
30756690-501 30756693-501
DMCS Communications PWB RS422/485 Communications PWB
1
Power/Input Printed Wiring Board
1
4
8.2
Description
51309404-502 51309404-501
90 to 264 Vac 24 Vac/dc
5
51309401-506
Limit Control MCU/Output Printed Wiring Board
1
6
30755306-501
Relay, Electromechanical
2
7
30756696-501
Digital Input Printed Wiring Board
1
8
30756721-501
Case Assembly
1
Parts Not Shown
Parts not shown
Table 8-2 lists the part numbers of the parts not show in the exploded view. Table 8-2 Parts Not Shown Part Number
94
Quantity
Description
Quantity
30731996-506
4-20 mA Resistor Assembly, 250 ohms
1
30754465-501
0-10 Volt Input Resistor Assembly, 100K Pair
1
30752481-501 30752481-502
Varistor, 120V Varistor, 240V
1
30755050-001
Mounting Kit
1
30756764-002
Rear Cover Kit
1
30755223-002 30755223-003
DIN Adapter Kit, Blue DIN Adapter Kit, Gray
1
30757088-501
Cold Junction Resistor
1
30756683-001
NEMA 3 Gasket (panel to case)
30757215-001
NEMA 4 Front Face Kit
1
30757069-001
Bezel Cover
1
UDC3300 Limit Controller Product Manual
1/01
Page 105
Section 9 - Appendix A How to Apply Digital Instrumentation in Severe Electrical Noise Environments
9.1
Overview
Guideline overview
Products that incorporate digital technology provide recognized performance advantages over conventional analog instrumentation used for process control. These advantages can result in better product uniformity and greater overall efficiency when used correctly. There are, however, certain guidelines regarding installation and wiring which must be carefully followed in order to achieve this performance. In addition to the traditional precaution of the separation of signal and power wiring in separate conduits, other measures must be taken to minimize the effects of electromagnetic interference (EMI) and radio frequency interference (RFI) on the operation of the equipment. Otherwise, if high level, short duration, noise spikes are permitted to enter the digital equipment, the noise can be transferred into the system’s logic networks and can be misinterpreted as signal data, resulting in erroneous system operation and other unpredictable responses.
What’s in this section
This section contains the following information: Topic
1/01
See Page
9.1
Overview
95
9.2
Potential Noise Sources
96
9.3
Prevention Methods
97
9.4
Recommended Wiring Practices
98
9.5
Power Source Considerations
100
9.6
Noise Suppression at the Source
101
UDC3300 Limit Controller Product Manual
95
Page 106
9.2
Potential Noise Sources
Overview
Noise can enter electronic equipment via three methods of coupling, namely: • Capacitive (or electrostatic) • Inductive (or magnetic) • Impedance.
Capacitive and inductive coupling
Capacitive and inductive coupling have the same essential effect, they couple current or voltage, without any actual connection of the two circuits. Impedance coupling requires a connection between the two circuits. Typical noise-generating sources that could affect electronic equipment through capacitive and inductive coupling include: • • • • • •
Impedance coupled noise
Relay coils Solenoids AC power wires, particularly at or above 100 Vac Current carrying cables Thyristor field exciters Radio frequency transmissions.
Impedance-coupled noise may enter by way of the lines used to power the digital equipment or by way of improper grounding. Most power lines, at typical industrial locations, are far from noise-free. The noise on them can be generated in many ways, but are nearly always associated with switching circuits of some nature. These include: • • • • • • •
96
Large relays Contactors Motor starters Business and industrial machines Power tools HID (high intensity discharge) lights Silicon controlled rectifiers (SCRs) that are phase-angled fired.
UDC3300 Limit Controller Product Manual
1/01
Page 107
9.3
Prevention Methods
Introduction
There are three ways to prevent electrical noise from interfering with the operation of the electronic digital equipment. • Built-in noise rejection • Separation of signal and power lines • Noise suppression at source
Built-in noise rejection
The first method is to design the digital equipment with a high degree of noise rejection built-in. This includes housing the equipment in a case that will provide shielding, liberal use of noise rejection filters and optoisolators, and the use of noise suppressors on potential noise sources within the equipment itself. This, of course, is the responsibility of the manufacturer who usually performs extensive laboratory and field testing of newly designed digital equipment to insure the adequacy of its immunity to noise. As a minimum requirement, the equipment should be able to pass the tests outlined in the IEEE Standard 472-1974 (Surge Withstand Capacity Tests).
Signal and power line separation
The second method is to prevent noise from getting on the signal and power lines that are connected to the equipment. This is achieved by proper separation and shielding of those lines. In some cases, separate power lines or special power line regulation or filtering may be required for satisfactory electronic digital equipment operation. It is the responsibility of the installer to follow good wiring practices.
Suppression at the source
The third prevention method is to suppress the noise at its source. This is the most effective but also the most difficult because it is not easy to identify all of the potential noise sources in a typical industrial installation. Therefore, “suppression” is usually a last resort for those extreme situations where the other methods are insufficient by themselves. See Noise Suppression at Source which follows.
1/01
UDC3300 Limit Controller Product Manual
97
Page 108
9.4
Recommended Wiring Practices
General rules
• All wiring must conform to local codes and practices. • Wires carrying similar types of signals (Table 9-1) may be bundled together, but bundles with different types of signals must be kept separated to prevent inductive or capacitive coupling.
Wire bundling
Table 9-1 shows what wiring should be bundled together to prevent inductive or capacitive coupling. Table 9-1
External Wiring Wire Function
No. 1 2 3
4
5
6 7
Bundle No.
Are Shielded Twisted Wires Recommended?
HIGH VOLTAGE Line Power Earth Ground Line Voltage Digital I/O
1
NO
ANALOG I/O Process Variable RTD Thermocouple dc Millivolts Low level (<100V) 4-20 mA dc 1-5 Vdc
2
YES
DIGITAL I/O Low Voltage (<100V) Computer Interface
3
YES
Type
Continued on next page
98
UDC3300 Limit Controller Product Manual
1/01
Page 109
9.4
Recommended Wiring Practices, Continued
Additional rules
Please observe these additional rules for wire bundling: • For distances over five (5) feet, and when shielding is recommended, use a separate metal tray or conduit for each bundle. Where conduits or trays are not practical, use twisted wires with a metal overbraid and provide physical separation of at least one foot. • Tray covers must be in continuous contact with the side rails of the trays. • When unlike signal levels must cross, either in trays or conduits, they should cross at a 90-degree angle and at a maximum spacing. Where it is not possible to provide spacing, a grounded steel barrier or grid should be placed between the unlike levels at the crossover points. • Trays containing low level wiring should have solid bottoms and sides. Tray covers must be used for complete shielding. Tray cover contact with side rails must be positive and continuous to avoid high reluctance air gaps, which impair shielding. Trays for low level cables should be metal and solidly grounded. • Wires containing low level signals should not be routed near any of the following: – Contactors – Motors – Generators – Radio transmitters – Wires carrying high current that is being switched on and off. • Use a 12-gage (or heavier) insulated stranded wire for the ground connection. Attach it firmly to a proven good earth ground such as a metal stake driven into the ground. • All shields should be grounded at one end only, preferably the instrument end.
1/01
UDC3300 Limit Controller Product Manual
99
Page 110
9.5
Power Source Considerations
Operate within limits
The AC power for the digital electronic equipment must be within the voltage and frequency limits specified for that equipment. Attempts to operate outside the specified limits will result in no performance. For those installations where the supply voltage will not stay within the specified limits, a ferroresonant transformer, for voltage resolution, should be used.
Independent AC source
For protection against noise, the AC source for the digital electronic equipment should be independent of all other loads especially when switching loads are involved. For example, it should not provide power for air-conditioning, convenience outlets, lighting, motors, or similar noise- generating devices. To obtain electrical isolation (see Figure 9-1) a separate transformer is required to supply power to the digital equipment. For additional noise and transient rejection, shielded primary and secondary windings may be required. And, if necessary, power line filters may be added to attenuate noise signals that have a higher frequency than the power line frequency.
Transformer for digital equipment
Figure 9-1 is an illustration of a separate transformer required to supply power to digital equipment. Figure 9-1
Transformer for Digital Equipment
H Power source 120/240 Vac single phase
N
H
N
To digital electronic equipment
G 20779
100
UDC3300 Limit Controller Product Manual
1/01