Page 111

9.6

Noise Suppression at the Source

Introduction

Generally speaking, when good wiring practices are used with welldesigned digital electronic equipment, no further noise protection is necessary. However, in some severe electrical environments, the magnitude of the electrical noise is so great that it must be suppressed at the source. In most control cabinets, the main sources of noise are motor starters, contactors, relays, and switching gear. For this reason, many manufacturers of these devices supply “surge suppressors” which mount directly on the noise source, (for example, on the coil of a control relay or motor starter). For those devices that do not have accessory “surge suppressors,” resistance-capacitance (RC) circuits and/or voltage limiters such as metal varistors may be added when and where needed. This can be broken down into two categories, namely inductive loads (for example, a relay switch in series with a relay coil) and contacts.

Inductive coils

Metal Oxide Varistors (MOVs) are recommended for transient suppression in inductive coils. An MOV is connected in parallel with the coil and is as close as physically possible to the coil (see Figure 9-2). MOV devices (listed in Table 9-2) are recommended for general purpose applications. Table 9-2 lists part numbers for recommended MOV devices. Table 9-2

MOV Devices

Part Number

30732481-001

30732481-002

Maximum AC

130V

275V

Energy Pulse Rating

10 Joules

15 Joules

Supplier (General Electric)

V130LA10A

V275LA15A

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

101

Page 112

9.6

Noise Suppression at the Source, Continued

Inductive coils, continued

Figure 9-2 is an illustration of transient suppression in inductive coils. Figure 9-2

Transient Suppression in Inductive Coils MOV

R

C

A.C. supply

Inductive load

20781

Additional protection may be provided by adding an RC circuit in parallel with the MOV. This consists of a 220-ohm resistor in series with a 0.5 microfarad, 1000V capacitor. The power rating of the resistor will depend on the voltage rating of the coil (see Table 9-3). Table 9-3

Coil Voltage vs Resistor Voltage Rating Coil Voltage

Resistor Voltage Rating

115V

1/4 Watt

230V

1 Watt

460V

3 Watt

550V

5 Watt

Continued on next page

102

UDC3300 Limit Controller Product Manual

1/01

Page 113

9.6 Contacts

Noise Suppression at the Source, Continued When a contact interrupts an inductive load, a certain amount of energy is stored in the load. An MOV or RC circuit in parallel with the load provides a place where this energy may be dissipated. However, if there is no MOV or RC circuit, the energy may create a visible electrical arc across the open contacts. This, in turn, results in electrical noise as well as damage to the contacts. One way to eliminate this arc is to connect a resistor and capacitor across the contacts (see Figure 9-3). A combination of 47 ohms and 0.1 microfarads (1000 Vdc) is recommended for circuits up to 3 amps and 300 Vac. For voltages above 2000 Vac, an MOV across the contact may be added for extra protection. Figure 9-3 is an illustration of a resistor and capacitor connected across a contact to eliminate electrical noise. Figure 9-3

Contact Noise Suppression MOV

R

C

A.C. supply

Inductive load

For large load currents, a rule of thumb is to size the capacitor so that the number of microfarads equals the number of amperes in the load current, and the resistor has the same resistance value as the load. The objective is to eliminate the visible arc. Either discreet resistors and capacitors or packaged RC networks may be used. An RC network (47 ohms and 0.1 microfarad) is available as part number 30371852-001. Similar RC networks are available from Electrocube Inc. (part number RG1782-3) and from Industrial Condensor Corporation. Continued on next page

1/01

UDC3300 Limit Controller Product Manual

103

Page 114

9.6

Noise Suppression at the Source, Continued

Contacts, continued

In DC circuits, the power dissipation under steady state condition can be eliminated by placing a diode (in series with a resistor) in parallel with the load (see Figure 9-4). The value of R should be less than or equal to the DC resistance of the inductive load. Figure 9-4 is an illustration of DC load noise suppression. Figure 9-4

DC Load Noise Suppression

D.C. supply

+ –

R Inductive load Diode

20782

104

UDC3300 Limit Controller Product Manual

1/01

Page 115

Index

A

D

Alarm circuit wiring 11 Alarm relay 1 Alarm Relay Output failure 80 Alarm Setpoints 54 Alarms Set Up Group 30, 42 Application related problems 70

DC Load Noise Suppression 104 Decimal point location 36 Diagnostic error messages 52 Digital Input Board Replacement Procedure 89 Digital input connections 16 Dimensions 8 Display indications 55 Display/keyboard assembly 85 Displays and indicators 3 DMCS communications 53 DMCS Communications Board 90 Duplex 41

B Background Tests 76 Baud rate 40 Bias 39 Burnout protection 39

E

C Calib Group 31 Capacitive and inductive coupling 96 CE Conformity 2 Chassis Removal 84 Cleaning 92 Coil Voltage vs Resistor Voltage 102 Communication station address 40 Communication units 41 Communications Board Replacement Procedure 90 Communications failure 82 Communications option connections 17 Communications selection 40 Communications Set Up Group 29, 40 Composite wiring diagram 12 Configuration 19 Configuration Procedure 23 Configuration Prompt Definitions 33 Configuration Prompts 20 Configuration Record Sheet 32 Configuration Tips 22 Contact Noise Suppression 103 Controller failure symptoms 72, 78 Customer support 72

1/01

Electrical isolation 100 Electrical noise 10, 95 Emission limits 2 Emissivity 39 Error messages 71 External reset 35

F Filter 39 Function of keys 4

G Grounding 10

H Hardware and software related problems 70 High limit control 35

UDC 3300 Limit Controller Product Manual

105

Page 116

Index I, J

N

Impedance coupled noise 96 Inductive coils 101 Input 1 actuation type 37 Input 1 Calibration Procedure 67 Input 1 connections 14 Input 1 high range value 39 Input 1 low range value 39 Input 1 Parameters Set Up Group 27, 36 Input 1 Set Up Wiring 61 Input Calibration 57 Installation 5 CE Conformity 6 Operating limits 6 Pre-installation information 5 Installation related problems 70

Noise 95 Noise rejection 97 Noise Suppression at the Source 101

O Operating limits 6 Operating the limit controller 49 Operation 45 Operator Interface 3 Overview 1

P, Q K Keyboard failure 81 Keys 4

L Latching Output Relay Failure 80 Latching relays 1 Limit Set Up Group 26 Line voltage wiring 13 Lockout 34 Lockout Data Set Up Group 34 Lockout Set Up Group 25 Loopback 41 Low limit control 35

Parity 40 Parts List 93 Parts Replacement Procedures 83 Physical considerations 8 Power Failure Symptoms 79 Power Input Board Replacement Procedure 88 Power line frequency 39 Power Source Considerations 100 Power up 46 Power up logic 35 Power-up Tests 73 Precision Resistor 62 Printed wiring board identification 87 Printed wiring board removal 86 Prompt hierarchy 20 Protective bonding 10

R M

106

Recommended Wiring Practices 98 Reset of relay 1 Response-delay timer 41 RS422 communications 53 RS422/485 Communications Board 90

UDC3300 Limit Controller Product Manual

1/01

Page 117

Index

S Security code 34, 48 Setpoint high limit 35 Setpoint low limit 35 Shed time 40 Shock hazard warning 57, 69, 79 Signal and power line separation 97 Software version 72 Status Group 31 Status Tests 74 Suppression at the source 97 Surge suppressors 101

T, U, V Temperature units 36 Transformer for Digital Equipment 100 Transient Suppression in Inductive Coils 102 Transmitter characterization 38 Troubleshooting / Service 69 Troubleshooting Procedures 79

W, X, Y, Z WARNING - SHOCK HAZARD 57, 69, 79 Wire bundling 98 Wiring 10 electrical noise precautions 10 wire bundling 10 Wiring the controller 11 Wiring Diagrams 12 Output and alarm wiring diagram 15

1/01

UDC 3300 Limit Controller Product Manual

107