Manual · Honeywell
UDC3300 Universal Digital Limit Controller
Manual120 pagesPDF 544 KB
Product manual for the Honeywell UDC3300 Universal Digital Limit Controller: installation, configuration, operation, calibration and service.
Covers · 1 model
The models it covers
Summary
What is in it
Product manual for the UDC3300 Universal Digital Limit Controller, a 1/4 DIN stand-alone limit controller with a latching output relay and two alarm relays. It covers model number interpretation, mounting and wiring, the configuration groups and prompt definitions, operation and monitoring, input calibration for thermocouple, RTD, voltage and current inputs, troubleshooting and parts replacement, a parts list, and wiring practice in severe electrical noise environments.
Its parts
- Overview
- Installation
- Configuration
- Configuration Prompt Definitions
- Operation
- Input Calibration
- Troubleshooting / Service
- Parts List
- Appendix A: How to Apply Digital Instrumentation in Severe Electrical Noise Environments
From the manual
Key facts from this manual
Each line names its page in the PDF.
Product manual 51-52-25-101 (1/01) for the Honeywell UDC3300 Universal Digital Limit Controller, a 1/4 DIN high or low limit controller with a latching output relay. It covers installation, wiring, configuration, operation, input calibration, troubleshooting, replacement parts and wiring in electrically noisy plants.
- Device
- Microprocessor-based stand-alone 1/4 DIN limit controller p. 11
- Limit output
- Latching relay, de-energized when the PV goes above (high limit) or below (low limit) the setpoint p. 11
- Alarms
- Two non-latching alarm relays, two setpoints each p. 11
- PV inputs
- T/C, RTD, Radiamatic, mV, 0-5V, 1-5V; by model also 0-20 mA, 4-20 mA and 0-10V p. 17
- Accuracy
- Typical ±0.20% of span p. 11
- Power
- 90 to 264 Vac, 50/60 Hz (18 VA max) or 24 Vac/dc, 20 to 27 V (12 VA max) p. 16
- Ambient
- 0 to 55°C (32 to 131°F); 5 to 90 % RH at 40°C p. 16
- Display
- Vacuum fluorescent; upper six characters, lower eight characters p. 11, 13
- Communications
- Optional RS422/485 ASCII p. 17
- Digital input
- Optional one digital input, used for external reset p. 9, 17
- Model number
- DC330L plus option codes; first option digit 0 = 90 to 264 Vac, 1 = 24 Vac/dc p. 17
- Board part numbers
- MCU/output PWB 51309401-506; display/keyboard 30756672-501; digital input PWB 30756696-501; relay 30755306-501 p. 104
- Kit part numbers
- 4-20 mA resistor (250 ohms) 30731996-506; 0-10 V input resistor pair 30754465-501; mounting kit 30755050-001; NEMA 4 front face kit 30757215-001 p. 104
- Error messages
- EE FAIL, FAILSAFE, INP1FAIL, INP1 RNG, PV LIMIT p. 62
What this manual walks you through
- Using the keys and choosing display modes p. 13, 14
- Unpacking and checking the model number p. 15, 17
- Operating limits for installation p. 16
- Wiring line voltage, input, outputs, digital input and communications p. 4, 6
- Configuring the controller set up groups p. 4
- Calibrating input 1 p. 5
- Reading diagnostic error messages p. 62
- Troubleshooting and replacing boards p. 5, 7
- Ordering replacement parts p. 103, 104
- Wiring in severe electrical noise environments p. 5
Good to know
- The latching relay cannot be reset while a limit condition exists. p. 14
- The controller must be panel mounted with its wiring terminals enclosed. p. 12
- Use in a residential area may cause harmful interference. p. 12
- For CE conformity, shielded twisted pair cable is required for analog, PV, digital I/O and computer interface circuits. p. 16
- FM approved limit controllers are restricted to thermocouple and RTD inputs. p. 17
Questions this manual answers
How do I reset the UDC3300 limit relay?
Press the [RESET] key on the front, or use an external switch if that option is fitted. It will not reset while the limit condition still exists. p. 11, 14
What inputs does the UDC3300 accept?
Thermocouple, RTD, Radiamatic, mV, 0-5V and 1-5V, and by model also 0-20 mA, 4-20 mA and 0-10V. p. 17
What power supply does the UDC3300 need?
90 to 264 Vac at 50/60 Hz, or a 24 Vac/dc version that runs on 20 to 27 V. p. 16
What does INP1 RNG mean on a UDC3300?
Input 1 is out of range: ±10% for linear inputs or ±1% for characterized inputs. p. 62
How long was the UDC3300 in limit, and what was the peak?
During a limit condition, pressing [LOWER DISPLAY] shows the limit action duration in hours and minutes and the peak PV value. p. 14