For the Honeywell UDC3300

Page 11

Section 1 – Overview 1.1

Introduction

Function

The UDC3300 Universal Digital Limit Controller is a microprocessorbased stand-alone controller. It combines the highest degree of functionality and operating simplicity offered in a 1/4 DIN size controller. With a typical accuracy of ±0.20% of span, the UDC3300 is an ideal controller for limiting temperature and other process variables in numerous heating and cooling applications, in metal working, food, and pharmaceuticals, and testing and environmental work.

Easy to read displays

The dedicated vacuum fluorescent displays with English prompts make the operator interface easy to read, understand and operate. Programmed sequences of displays assure quick and accurate entry of all configurable parameters.

Easy to operate

Simple keystrokes let you select input and range configuration, set the operating parameters that meet your process control needs now, and change them later to meet new ones. The tactile keyboard provides positive operator feedback. Self diagnostics, fault tolerant design and keyboard security provide maximum assurance of trouble-free operation.

Latching relays

This limit controller has a latching output relay which is de-energized whenever the PV goes above (high limit) or below (low limit) a selected setpoint value. When the limit is exceeded (high or low), the lower display alternately indicates “the limit control setpoint value” and the word “limit.”

Reset of relay

Reset of the latching output relay is made through a [RESET] key on the front of the controller or an external switch (if the option is present).

Alarm relay

Two additional non-latching alarm relays with two setpoints each alert you to critical process conditions. Continued on next page

1/01

UDC3300 Limit Controller Product Manual

1

Page 12

1.1

Introduction, Continued

Mount anywhere

The UDC is industrial control equipment that must be panel mounted. The wiring terminals must be enclosed within the panel. The UDC is environmentally hardened and, when suitably enclosed, can be mounted virtually anywhere in plant or factory; on the wall, in a panel, or even on the process machine. It withstands ambient temperatures up to 55 °C (133 °F) and resists the effects of vibration and mechanical shock.

CE Conformity (Europe)

This product is in conformity with the protection requirements of the following European Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMC Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be assumed. Deviation from the installation conditions specified in this manual, and the special conditions for CE conformity in Section 2.1, may invalidate this product’s conformity with the Low Voltage and EMC Directives. ATTENTION

The emission limits of EN 50081-2 are designed to provide reasonable protection against harmful interference when this equipment is operated in an industrial environment. Operation of this equipment in a residential area may cause harmful interference. This equipment generates, uses, and can radiate radio frequency energy and may cause interference to radio and television reception when the equipment is used closer than 30 meters (98 feet) to the antenna(e). In special cases, when highly susceptible apparatus is used in close proximity, the user may have to employ additional mitigating measures to further reduce the electromagnetic emissions of this equipment.

2

UDC3300 Limit Controller Product Manual

1/01

Page 13

1.2

Operator Interface

Displays and indicators

Figure 1-1

Figure 1-1 shows the operator interface and defines the displays and indicators. The function of the keys is shown in Table 1-1. Operator Interface Displays and Indicators

Upper Display - Six Characters

• Normal Operation - four digits dedicated to display the process variable, or blank • Configuration Mode - displays parameter value or selection Lower Display - Eight characters

• Normal Operation - displays the value of limit control setpoint, or indicates "LIMIT OK". When alarm condition exists, it alternates between the setpoint value and the word "LIMIT". • Configuration Mode - displays function group and parameters F - °Fahrenheit being used C - °Centigrade being used

Indicator definition when lit ALM - Alarm conditions exist

ALM

12

DI - Digital Input active

DI

1

FC

RSP OUT

1

FUNCTION

LOWER DISPLAY

RESET

Keys - See Table 1-1 SET UP

22642

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

3

Page 14

1.2

Operator Interface, Continued

Function of keys

Table 1-1 shows each key on the operator interface and defines its function. Table 1-1 Key SET UP

FUNCTION

Function of Keys Function • Places the controller in the Configuration Set Up group select mode. Sequentially displays Set Up groups and allows the [FUNCTION] key to display individual functions in each Set Up group. • Used in conjunction with the [SET UP] key to select the individual functions of a selected Configuration Set Up group. • Used during field calibration procedure.

LOWER DISPLAY

• Selects one of the following display modes when no limit conditions exist: #1 Upper Display = the value of the process variable Lower Display = the value of the Limit Control Setpoint #2 Upper Display = (blank) except during Limit conditions Lower Display = the value of the Limit Control Setpoint #3 Upper Display = (blank)except during Limit conditions Lower Display = LIMIT OK • Pressing [LOWER DISPLAY] key while a limit condition exists, shows the following in the lower display: TIME XX.YY = Limit action duration in hours and minutes PK_XXXXX = Peak PV Value - The highest PV value reached for a High Limit Controller, or the lowest PV value reached for a Low Limit Controller.

RESET

• Resets the latching output relay. Relay cannot be reset while a limit condition exists.

The upper blank key is not used.

The lower blank key restores an original value. – When you are using the [FUNCTION] key and [s] [t] keys to change a parameter value of selection and you decide you want to keep the original value that was displayed, press the lower blank key, before entry, to recall the original value. • Increases the setpoint, output, or configuration values displayed.

• Decreases the setpoint, output, or configuration values displayed.

4

UDC3300 Limit Controller Product Manual

1/01

Page 15

Section 2 – Installation 2.1

Overview

Introduction

Installation of the UDC3300 Limit Controller consists of mounting and wiring the controller according to the instructions given in this section. Read the pre-installation information, check the model number interpretation and become familiar with your model selections, then proceed with installation.

What’s in this section?

This section contains the following information: Topic 2.1 2.2 2.3

2.4

2.5

Pre-installation information

Overview Model Number Interpretation Mounting Physical Considerations Overall Dimensions Mounting Procedure Wiring Taking Electrical Noise Precautions Permissible Wire Bundling Identify Your Wiring Requirements Control Alarm Circuit Wiring Wiring the Controller Wiring Diagrams Composite Wiring Diagram AC Line Voltage Input #1 Output and Alarm Wiring Digital Inputs Communications RS422/485 DMCS

See Page 5 7 8 8 8 9 10 10 10 11 11 11 12 12 13 14 15 16 17 17 18

If the controller has not been removed from its shipping carton, inspect the carton for damage and remove the controller. Inspect the unit for any obvious shipping damage and report any damage due to transit to the carrier. Make sure the carton with the controller includes • a bag containing mounting hardware and • a bag containing input resistors. Check that the model number shown on the inside of the case agrees with what you have ordered. Continued on next page

1/01

UDC3300 Limit Controller Product Manual

5

Page 16

2.1

Overview, Continued

CE Conformity special conditions (Europe)

Shielded twisted pair cables are required for all Analog I/O, Process Variable, RTD, Thermocouple, dc millivolt, low level signal, 4-20 mA, Digital I/O, and computer interface circuits.

Operating limits

We recommend that you review and adhere to the operating limits listed in Table 2-1 when you install your controller. Table 2-1

Operating Limits

Condition

Specifications

Ambient Temperature

32 to 131°F (0 to 55°C)

Relative Humidity

5 to 90 % RH at 40°C (104°F)

Vibration Frequency Acceleration

0 to 200 Hz 0.6 g

Mechanical Shock Acceleration Duration

5g 30 ms

Power

6

90 to 264 Vac

90 to 264 Vac 50/60 Hz (CSA models rated to 250 V maximum)

24 Vac/dc

20 to 27 Vac 20 to 27 Vdc

50/60 Hz 0 Hz

Power Consumption

18 VA maximum (90 to 264 Vac) 12 VA maximum (24 Vac/dc)

Frequency (For Vac)

48 to 52 Hz 58 to 62 Hz

UDC3300 Limit Controller Product Manual

1/01

Page 17

2.2

Model Number Interpretation

Model number

Figure 2-1

The model number interpretation is shown in Figure 2-1. Write the model number into the spaces provided and compare it to the model number interpretation. This information will also be useful when you wire your controller. Model Number Interpretation Key Number

Table I

DC 3 3 0 L

Table II

0

Table III

Table IV

0

Table V

0

Limit Control Model

Table VI

0

Certificate – 0 = None – C = Certificate of Conformance

Output #1 E – = Relay, Electromechanical Output #2 or Alarm #2 – 0 = None – E = Relay, Electromechanical

Options 0 – – – – – = 90 to 264 Vac Power 1 – – – – – = 24 Vac/dc Power – 0 – – – – = None – A – – – – = CSA, FM and UL* – F – – – – = FM and UL* – – 0 – – – = Gray Elastomer Bezel – – B – – – = Blue Elastomer Bezel – – T – – – = Tan Elastomer Bezel – – – 0 – – = None – – – P – – = Rear Terminal Cover – – – T – – = Customer ID Tag – – – U – – = Rear Terminal Cover and Tag – – – – 0 – = None – – – – D – = DIN Cutout Adapter – – – – – 0 = None

External Interface 0 – – = None 1 – – = RS422/485 ASCII Digital Inputs – – 0 = None – – 3 = One Digital Input

PV Input 1 – = T/C, RTD, Radiamatic, mV, 0-5V, 1-5V 2 – = T/C, RTD, Radiamatic, mV, 0-5V, 1-5V, 0-20 mA, 4-20 mA 3 – = T/C, RTD, Radiamatic, mV, 0-5V, 1-5V, 0-20 mA, 4-20 mA, 0-10V

*FM approved Limit Controllers are restricted to thermocouple and RTD PV inputs. Limit Controllers are UL recognized for regulatory use only.

1/01

UDC3300 Limit Controller Product Manual

7

Page 18

2.3

Mounting

Physical considerations

The controller can be mounted on either a vertical or tilted panel using the mounting kit supplied. Adequate access space must be available at the back of the panel for installation and servicing activities. The overall dimensions and panel cutout requirements for mounting the controller are shown in Figure 2-2.

Overall dimensions

Figure 2-2

Figure 2-2 shows the overall dimensions for mounting the controller.

Dimensions +0.8

-0.0 92 3.622 +0.03

96 3.780

-0.0

LL ALM 1 2 1 2 ALM

FC F ALDI 1 PV 1 2 13 4 MDI 1 C 2

96 3.780

FC

RSP

2 OUT 11 2 2

FUNCTION

M A N

MAN %%

%

+0.8

92 -0.0 3.622 +0.03

Panel Cutout

LOWER DISPLAY

-0.0

RESET

SET UP

24 Max Panel .945 Thickness

10 Max (2) .394

2.4 with optional .093 rear cover

90.7 3.57

21.6 .850

147.3 5.82

22716

Continued on next page

8

UDC3300 Limit Controller Product Manual

1/01

Page 19

2.3

Mounting, Continued

Mounting method

Before mounting the controller, refer to the nameplate on the inside of the case and make a note of the model number. It will help later when selecting the proper wiring configuration. Figure 2-3 shows you the mounting method for the UDC3300 Limit controller. Figure 2-3 Mounting Method

Panel

22605

Mounting procedure

1/01

Refer to Figure 2-3 and follow the procedure below to mount the controller. Step

Action

1

Mark and cut out the controller hole in the panel according to the dimension information in Figure 2-2.

2

Remove the screw cover and loosen the screw on the front of the controller. Pull the chassis out of the case.

3

Orient the case properly and slide it through the panel hole from the front.

4

Remove the mounting kit from the shipping container, and install the kit as follows: • Install the screws into the threaded holes of the clips. • Insert the prongs of the clips into the two holes in the top and bottom of the case. • Tighten both screws to secure the case against the panel. • Carefully slide the chassis assembly into the case, press to close and tighten the screw. Replace the screw cover.

UDC3300 Limit Controller Product Manual

9

Page 20

2.4

Wiring

Electrical considerations

The controller is considered “rack and panel mounted equipment” per EN 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements. Conformity with 72/23/EEC, the Low Voltage Directive requires the user to provide adequate protection against a shock hazard. The user shall install this controller in an enclosure that limits OPERATOR access to the rear terminals.

Controller grounding

PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is installed shall be in accordance with National and local electrical codes. To minimize electrical noise and transients that may adversely affect the system, supplementary bonding of the controller enclosure to a local ground, using a No. 12 (4 mm2) copper conductor, is recommended.

Taking electrical noise precautions

Electrical noise is composed of unabated electrical signals which produce undesirable effects in measurements and control circuits. Digital equipment is especially sensitive to the effects of electrical noise. Your controller has built-in circuits to reduce the effect of electrical noise from various sources. If there is a need to further reduce these effects: • Separate External Wiring - separate connecting wires into bundles (see Table 2-2) and route the individual bundles through separate conduits or metal trays. • Use Suppression Devices - for additional noise protection, you may want to add suppression devices at the external source. Appropriate suppression devices are commercially available. NOTE

Permissible wire bundling

For additional noise information, refer to Section 9.

Table 2-2 shows which wire functions should be bundled together. NOTE

For installation where high EMI/RFI noise cannot be avoided, we recommend you use shielded twisted pair wires for the signals in bundle 2.

Table 2-2

Permissible Wiring Bundling

Bundle No.

Wire Functions

1

• Line power wiring • Earth ground wiring • Control relay output wiring • Line voltage alarm wiring

2

Analog signal wire, such as: • Input signal wire (thermocouple, 4 to 20 mA, etc.) • Digital input signals • Communications

3

• Low voltage alarm relay output wiring • Low voltage wiring to solid state type control circuits

Continued on next page

10

UDC3300 Limit Controller Product Manual

1/01