The text of a manual · part 3 of 12

UDC3300 Universal Digital Limit Controller, pages 21 to 30

Pages 21 to 30 of 120

The original document is the PDF (544 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Honeywell UDC3300

Page 21

2.4

Wiring, Continued

Alarm circuit wiring

The insulation of wires connected to the Alarm terminals shall be rated for the highest voltage involved. Extra Low Voltage (ELV) wiring (input, current output, and low voltage Alarm circuits) shall be separated from HAZARDOUS LIVE (>30 Vac, 42.4 Vpeak, or 60 Vdc) wiring per Table 2-2.

Identify your wiring requirements

To determine the appropriate diagrams for wiring your controller, refer to the model number interpretation in this section. The model number of the controller can be found on the inside of the case.

Wiring the controller

Using the information contained in the model number, select the appropriate wiring diagrams from the figures listed below and wire the controller accordingly. Wiring Requirements

1/01

Figure

Composite Wiring Diagram

2-4

Line Power 90–264 Vac or 24 Vac/dc

2–5

Input #1 Wiring

2–6

Output and Alarm Wiring

2-7

Digital Inputs Wiring

2–8

Communications Wiring • RS422 • DMCS

2–9 2–10

UDC3300 Limit Controller Product Manual

11

Page 22

2.5

Wiring Diagrams

Composite wiring diagram

Figure 2-4

Figure 2-4 is a composite wiring diagram of the UDC3300 Limit controller. It identifies the terminal designations and their functions. Refer to the individual diagrams listed to wire the controller according to your requirements.

Composite Wiring Diagram Digital Input Terminals See Figure 2-8

AC Line Voltage Terminals See Figure 2-5

Input #1 Terminals See Figure 2-6

10

1

L1

11

2

L2/N

12

3

22

13

4

23

14

5

24

15

6

25

16

7

26

17

8

27

Communications Terminals See Figures 2-9 and 2-10

Outputs and Alarms Terminals See Figure 2-7

9 I/O Shield Ground (Do Not use for communication shield)

Continued on next page

12

UDC3300 Limit Controller Product Manual

1/01

Page 23

2.5

Wiring Diagrams, Continued

Line voltage wiring

This equipment is suitable for connection to 90-264 Vac or 24 Vac/dc, 50/60 Hz, power supply mains. It is the user’s responsibility to provide a switch and non-time delay (North America), quick-acting, high breaking capacity, Type F, (Europe) 1/2 A, 250 V fuse(s) or circuit-breaker for 90264 V; or 1 A, 125 V fuse or circuit breaker for 24Vac/dc operation, as part of the installation. The switch or circuit-breaker should be located close to the controller, within easy reach of the operator. The switch or circuit-breaker should be marked as the disconnecting device for the controller. (4mm2). CAUTION Applying 90-264 Vac to a controller rated for 24Vac/dc will severely damage the controller and is a fire and smoke hazard. When applying power to multiple instruments, make sure that sufficient current is supplied. Otherwise, the instruments may not start up normally due to the voltage drop caused by the in-rush current. Figure 2-5 shows the wiring connections for line voltage. Figure 2-5

Line Voltage Wiring 1

Ground

10

1

L1

11

2

L2/N

12

3

22

13

4

23

14

5

24

15

6

25

16

7

26

17

8

2

AC/DC Line Voltage

Hot Neutral

27

9 22607

1

PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is installed, shall be in accordance with National and local electrical codes. To minimize electrical noise and transients that may adversly affect the system, supplementary bonding of the controller enclosure to a local ground, 2 using a No. 12 (4 mm ) copper conductor, is recommended.

2 Provide a switch and non-time delay (North America), quick-acting, high breaking capacity, Type F, (Europe) 1/2 A, 250 V fuse(s) or circuit-breaker for 90-264 V; or 1 A, 125 V fuse or circuit breaker for 24 Vac/dc operation, as part of the installation.

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

13

Page 24

2.5

Wiring Diagrams, Continued

Input #1 connections

Figure 2-6

Figure 2-6 shows the wiring connections for Input #1.

Input #1 Connections

Thermocouple Use Thermocouple extension wire only 1

R

25 R

+ –

26 + 27

1

L1

11

2

L2/N

12

3

22

13

4

23

14

5

24

15

6

25

16

7

26

17

8

27

9

–

Remove screw and install C/J on the "R" terminal, connect tang to "–" terminals. 2

RTD

25 R 26

+

27

–

I N P U T 1

0 –10 Volts

0–10 Volt source

+

25 R

100K 1 2

1

26 +

– 100K 3

MV or Volts except 0 –10 Volts MV or Volt source

10

27 –

4–20 milliamps

25 R

25 R

–

Xmitter

+

26 +

–

27 –

+

1

26 +

250 Ω Power

+

27 –

–

Supply 22608

1 The 250Ω load resistor for 4-20mA or the Voltage divider for 0–10 Volts or the 500 Ohm C/J compensation resistor are supplied with the controller when the input is specified. These items must be installed when you wire the controller before startup. 2 When installing the cold junction (Part number 30757088-001) for a T/C input, remove the screws from terminals 25 and 27, and install the assembly into place.

Continued on next page 14

UDC3300 Limit Controller Product Manual

1/01

Page 25

2.5

Wiring Diagrams, Continued

Output and alarm wiring diagram

Figure 2-7

Figure 2-7 shows the Output and Alarm wiring connections for Limit controllers.

Output and Alarm Wiring

Output Relay #1 Latching

L1 L2/N 22 23

Alarm Relay #2 Non-Latching

24 25 26 27

1

N.C.

2

N.O.

3 4

To terminal 1 or 3

N.C.

5

N.O.

6 Alarm Relay #1 Non-Latching

1

Limit Relay Load

7

Alarm Relay #2 Load To terminal 4 or 6

N.C.

8

Alarm Relay #1 Load

N.O.

9

To terminal 7 or 9

Load Supply Power Load Supply Power Load Supply Power

1 Electromechanical relays are rated at 5 Amps @ 120 Vac or 2.5 Amps at 240 Vac.

Customer should size fuses accordingly. 22645

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

15

Page 26

2.5

Wiring Diagrams, Continued

Digital input connections

Figure 2-8

Figure 2-8 shows the wiring connections for the Digital Input option. This input is used for external reset of the latching relay. Digital Input Connections Digital Input Switch #1

10 L1

11

L2/N

12

22

13

Connect shield to ground at one end only

Switch Common

23 24 25 26 27

22646

Continued on next page

16

UDC3300 Limit Controller Product Manual

1/01

Page 27

2.5

Wiring Diagrams, Continued

Communications option connections

There are two types of Communications option available: • RS422/485 - Figure 2-9 • DMCS - Figure 2-10. Figure 2-9 shows the wiring connections for the RS422/485 Communications Option. RS422/485 Communications Option Connections

Figure 2-9

RS422/485 HALF DUPLEX

L1 L2/N

Master

12

22

13

23

14

24

15

25

16

26

17

SHD

1

SHD

TX+/RX+

TX+/RX+

TX–/RX–

TX–/RX–

120 Ohm Resistor

27 To Other Communication Instruments (maximum 15) CAUTION Do not mix half and full duplex wiring.

Do not run these lines in the same conduit as AC power

120 Ohm Resistor on Last Leg

RS422/485 FULL DUPLEX L1 L2/N

12

22

13

23

14

24

15

25

16

26

17

Master SHD

1

SHD

RX+

TX+

RX–

TX–

TX+

RX+

TX–

RX–

120 Ohm Resistor 120 Ohm Resistor

27 Do not run these

1

Use shielded twisted pair cables (Belden 9271 Twinax or equivalent)

To Other lines in the same Communication conduit as AC power Instruments (maximum 15) 120 Ohm Resistor on Last Leg

22621

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

17

Page 28

2.5

Wiring Diagrams, Continued

Communications option connections (continued)

Figure 2-10

Figure 2-10 shows the wiring connections for the DMCS Communications Option.

DMCS Communications Option Connections DMCS Communications Master Honeywell Gateway 500 or LPM Series 9000

L1 L2/N

12

22

13

23

14

24

15

25

16

26

17

SHD

1

SHD

D+

D+

D–

D– 120 Ohm Resistor

27

1

18

Do not run these lines in the same conduit as AC power

Use shielded twisted pair cables (Belden 9271 Twinax or equivalent)

To Other Communication Instruments (Maximum 31)

120 Ohm Resistor on Last Leg

UDC3300 Limit Controller Product Manual

22622

1/01

Page 29

Section 3 – Configuration 3.1

Overview

Introduction

Configuration is a dedicated operation where you use straightforward keystroke sequences to select and establish (configure) pertinent control data best suited for your application.

What’s in this section?

The table below lists the topics that are covered in this section. Topic

Prompts

See Page

3.1

Overview

19

3.2

Prompt Hierarchy

20

3.3

How to Get Started

21

3.4

Configuration Tips

22

3.5

Configuration Procedure

23

3.6

Lockout Setup Groups

25

3.7

Limit Set up Group

26

3.8

Input 1 Setup Group

27

3.9

Communications Setup Group

29

3.10

Alarms Setup Group

30

3.11

Calibration Setup Group

31

3.12

Status Set up Group

31

3.13

Configuration Record Sheet

32

To assist you in the configuration process, there are prompts that appear in the upper and lower displays. These prompts let you know what group of configuration data (Set Up prompts) you are working with and also, the specific parameters (Function prompts) associated with each group. Figure 3-1 shows you an overview of the prompt hierarchy. As you will see, the configuration data is divided into 5 main Set Up groups plus prompts for calibration and prompts that show the status of the continuous background tests that are being performed.

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

19

Page 30

3.2

Configuration Prompts

Diagram: prompt hierarchy

Figure 3-1 Set Up

Figure 3-1 shows an overview of the UDC3300 Set Up prompts and their associated Function prompts. Read from left to right.

Overview of UDC3300 Prompt Hierarchy • Press [SET UP] key to access the Set Up prompts. Function • Press [FUNCTION] key to access Function prompts within each Set Up group.

tuto change the value or selection of the Function prompt.

• Press

LOCKOUT

SECURITY

LOCKOUT

LIMIT

LO or HI

EXT RSET

POWER UP

SP HILIM

SP LOLIM

INPUT 1

DECIMAL

UNITS

IN1 TYPE

XMITTER

IN1 HI

BIAS IN1

FILTER 1

BURNOUT

EMISSIV

PWR FREQ

ComSTATE

Com ADDR

SHEDTIME

PARITY

TX DELAY

LOOPBACK

UNITS

A1S1 VAL

A1S2 VAL

A2S1 VAL

A2S1TYPE

A2S2TYPE

A1S1 H L

Com

ALARMS

IN1 LO

Continued next line

BAUD

DUPLEX

Continued next line

A2S2 VAL

A1S1TYPE

A1S2TYPE

Continued next line

A1S2 H L

A2S1 H L

A2S2 H L

Continued next line

AL HYST

CALIB

Used for Field Calibration (Refer to the Calibration section for prompts.)

STATUS

VERSION

FAILSAFE

RAM TEST

CONFTEST

CAL TEST

FAC CRC 24181

Read Only

20

UDC3300 Limit Controller Product Manual

1/01