Page 31

3.3

How To Get Started

Read the configuration tips

Read “Configuration Tips” shown on the next page. These tips will help you to easily and quickly accomplish the tasks at which you will be working when you configure your controller.

Read configuration procedure

Read “Configuration Procedure”. This procedure tells you how to access the Set Up groups, and the Function parameters within each of these groups that are shown in the Prompt Hierarchy in Figure 3-1.

Set Up groups

The Set Up groups and Function parameters are listed in the order of their appearance. The list includes the name of the prompt, the range of setting or selections available, and the factory setting.

Parameter explanations or definitions

If you need a detailed explanation of any prompt listed, refer to Section 4 Configuration Parameter Definitions. This section lists the Set Up and function prompts, the selection or range of settings that you can make for each, plus a detailed explanation or definition of each parameter.

Configuration record sheet

1/01

Located on the last page of this section is a “Configuration Record Sheet”. When you make your configuration selections, record them on this sheet. Then you will have a record of how the controller was configured.

UDC3300 Limit Controller Product Manual

21

Page 32

3.4

Configuration Tips

Introduction

Listed below in Table 3-1 are a few tips that will help you enter the configuration data more quickly. Table 3-1

Configuration Tips

Function

Tip

Displaying Groups

Use the [SET UP] key to display the Set Up groups. The group titles are listed in this section in the order that they appear in the controller.

Displaying Functions

Use the [FUNCTION] key to display the individual parameters under each group. The prompts are listed in the order of their appearance in each group.

Scrolling

To get to a Set Up group prompt more quickly, hold the [SET UP] key in. To get to a Function prompt more quickly, hold the [FUNCTION] key in. The display will scroll through the parameters.

ATTENTION The prompting scrolls at a rate of 2/3 seconds when the [SET UP] or [FUNCTION] key is held in. Also, [s] or [t] keys will move Group prompts forward and backward at a rate twice as fast.

22

Changing values quickly

When changing the value of a parameter, you can adjust a more significant digit in the upper display by holding in one key [s] or [t] , and pressing the other [s] or [t] at the same time. The adjustment will move one digit to the left. Press the key again and you will move one more digit to the left.

Restoring to the original value

When you change the value or selection of a parameter while in Set Up mode and decide not to enter it, press the lower blank key once, the original value or selection will be recalled.

Exiting SET UP mode

To exit Set Up mode, press the [LOWER DISPLAY] key. This returns the display to the same state it was in immediately preceding entry into the Set Up mode.

Timing out from Set Up mode

If you are in Set Up mode and do not press any keys for one minute, the controller will time out and revert to the mode and display that was being used prior to entry into Set Up mode.

Key Error

When a key is pressed and the prompt “KEY ERROR” appears in the lower display, it will be for one of the following reasons: • parameter not available • not in Set Up mode, press [SET UP] key first • key malfunction, do keyboard test (operation)

UDC3300 Limit Controller Product Manual

1/01

Page 33

3.5

Configuration Procedure

Introduction

Each of the Set Up groups and their functions are pre-configured at the factory. The factory settings are shown in the Set Up group tables that follow this procedure. If you want to change any of these selections or values, follow the procedure in Table 3-2. This procedure tells you the keys to press to get to any Set Up group and any associated Function parameter prompt.

Procedure

Follow the procedure listed in Table 3-2 to access the Set Up groups and Function prompts. ATTENTION

The prompting scrolls at a rate of 2/3 seconds when the [SET UP] or [FUNCTION] key is held in. Also, [s] [t] keys will move group prompts forward or backward at a rate of 1/3 seconds. Table 3-2 Step 1

Configuration Procedure Operation

Press

Select Set Up mode

SET UP

Result Upper Display SET UP

Lets you know you are in the configuration mode and a Set Up group title is being displayed in the lower display.

Lower Display LOCKOUT

2

Select any Set Up group

SET UP

This is the first Set Up group title.

Successive presses of the [SET UP ] key will sequentially display the other Set Up group titles shown in the prompt hierarchy in Figure 3-1. You can also use the [s] [t] keys to scan the Set Up groups in both directions. Stop at the Set Up group title which describes the group of parameters you want to configure. Then proceed to the next step.

3

Select a Function Parameter

Upper Display

FUNCTION

0

Lower Display SECURITY

Shows the first Function prompt within that Set Up group. Example displays show Set Up group “Lockout”, Function prompt “Security” and the code selected.

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

23

Page 34

3.5

Configuration Procedure, Continued

Procedure, continued

Table 3-2 Step 4

Configuration Procedure, Continued Operation

Press

Select other Function Parameters

FUNCTION

Result Successive presses of the [FUNCTION] key will sequentially display the other function prompts of the Set Up group you have selected. Stop at the function prompt that you want to change, then proceed to the next step.

5

Change the value or selection

These keys will increment or decrement the value or selection that appears for the function prompt you have selected. or

See “Configuration Tips” for instructions to increase or decrease value quickly. Change the value or selection to meet your needs. If the display flashes, you are trying to make an unacceptable entry.

6

Enter the value or selection

This key selects another Function prompt.

FUNCTION or This key selects another Set Up group.

SET UP

7

Exit Configuration

LOWER DISPLAY

24

The value or selection you have made will be entered into memory after another key is pressed. This exits configuration mode and returns the controller to the same state it was in immediately preceding entry into the Set Up mode. It stores any changes you have made.

UDC3300 Limit Controller Product Manual

1/01

Page 35

3.6

Lockout Set Up Group

Introduction

The Lockout group provides three levels of keyboard security to protect configuration and calibration data. To further secure this data, there is a security code that can be entered which will permit changes to the lockout configuration.

Set this group last

DO NOT configure this group until all other configuration is complete.

Function prompts

Table 3-3 lists the function prompts in the “LOCKOUT” Set Up group.

Table 3-3

Lockout Group Function Prompts

Function Prompt Lower Display

Function Name

Selections or Range of Setting

Factory Setting

Upper Display

1/01

SECURITY

Security Code

0 to 4095

0

LOCKOUT

Configuration Lockout

NONE CALIB +CONF MAX

NONE

UDC3300 Limit Controller Product Manual

25

Page 36

3.7

Limit Set Up Group

Introduction

Limit control provides a latching output relay which is de-energized whenever the PV goes above (high limit) or below (low limit) a selected setpoint value. Reset is through the [RESET] key on the front of the controller or an optional external switch (Digital Input #1).

Function prompts

Table 3-4 lists the function prompts in the “LIMIT” Set Up group.

Table 3-4

Limit Group Function Prompts

Function Prompt Lower Display

Function Name

Selections or Range of Setting

Factory Setting

Upper Display

LO or HI

Type of Limit Control

LO LIM HI LIM

HI LIM

EXT RSET

External Reset (Digital Input 1)

DISABL ENABLE EXoNLY

DISABL

POWER UP

Power-up Logic

NORMAL RESET

NORMAL

SP HILIM

High Setpoint Limit

0 to 100% of Span in engineering units

1000

ATTENTION This value should never be set higher than the temperature limit of the oven or furnace being controlled. SP LOLIM

26

Low Setpoint Limit

0 to 100% of Span in engineering units

UDC3300 Limit Controller Product Manual

0

1/01

Page 37

3.8

Input 1 Parameters Set Up Group

Introduction

This data deals with various parameters required to configure Input 1.

Function prompts

Table 3-5 lists all the function prompts in the “INPUT 1” Set Up group.

Table 3-5

Input 1 Group Function Prompts

Function Prompt Lower Display

Function Name

Selections or Range of Setting

Factory Setting

Upper Display

DECIMAL

UNITS

IN1 TYPE

Decimal Point Location

XXXX XXX.X XX.XX

Temperature Units

DEG F DEG C NONE

Input 1 Actuation Type

B TC E TC H E TC L J TC H J TC L K TC H K TC L NNM H NNM L NM90 H NM90 L NIC TC R TC S TC T TC H

XXXX

None One Two

NONE

T TC L W TC H W TC L 100 PT 100 LO 200 PT 500 PT RAD RH RAD RI 0-20mA* 4-20mA* 0-10mV* 0-50mV* 0-5 V* 1-5 V* 0-10V*

0-10mV (K TC H for FM only)

*not available for FM models XMITTER

B TC E TC H E TC L J TC H J TC L K TC H K TC L NNM H NNM L NM90 H NM90 L NIC TC R TC

IN1 HI

Input 1 High Range Value (Linear Inputs and Radiamatic RI only)

–999. to 9999. in engineering units

1000 (2400 for FM only)

IN1 LO

Input 1 Low Range Value (Linear Inputs and Radiamatic RI only)

–999. to 9999. in engineering units

0

(not available for FM models)

S TC T TC H T TC L W TC H W TC L 100 PT 100 LO 200 PT 500 PT RAD RH RAD RI LINEAR SQROOT

LINEAR

Transmitter Characterization

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

27

Page 38

3.8

Input 1 Group, Continued

Function prompts, continued

Table 3-5

Table 3-5 lists all the function prompts in the “INPUT 1” Set Up group.

Input 1 Group Function Prompts, Continued

Function Prompt Lower Display

Function Name

Selections or Range of Setting

Factory Setting

Upper Display

BIAS IN1

Input 1 Bias

FM: –10.0 to +10.0 Non-FM: –999. to 9999.

0

FILTER 1

Input 1 Filter

0 to 120 seconds

0

BURNOUT

Burnout Protection

Burnout is fixed.

UPSCALE for FM

For non-linear inputs: High Limit Control = Upscale Low Limit Control = Downscale

28

EMISSIV

Emissivity

0.01 to 1.00

0

PWR FREQ

Power Line Frequency

60 Hz 50 Hz

60 Hz

UDC3300 Limit Controller Product Manual

1/01

Page 39

3.9

Communications Set Up Group

Introduction

This data deals with the Communications option that is available with your controller. This option allows the controller to be connected to a host computer via a RS422/485 or DMCS bus. ATTENTION

FM-approved Limit controllers with Communications option are limited to READ ONLY (monitoring only) functionality. If your controller does not have the Communications option, the prompts will not appear. Function prompts

Table 3-6

Table 3-6 lists all the function prompts in the “Com” Set Up group.

Com Group Function Prompts

Function Prompt

Function Name

Lower Display

Selections or Range of Setting

Factory Setting

Upper Display

ComSTATE

Communications Option State

DISABL DMCS RS422

DISABL

Com ADDR

Communications Station Address

1 to 99

0

SHEDTIME

Shed Time

1 to 255 sample periods

0

Parity

ODD EVEN

ODD

Baud Rate

300 600 1200 2400

Duplex Operation

HALF FULL

HALF

Transmission Delay

1 to 500 milliseconds

1

Local Loop Back

DISABL ENABLE

DISABL

Communication Units

PERCNT ENG

ENG

PARITY (RS422/485 Only) BAUD (RS422/485 Only)

DUPLEX (RS422/485 Only) TX DELAY

4800 9600 19200

300

(RS422/485 Only) LOOPBACK

UNITS

1/01

UDC3300 Limit Controller Product Manual

29

Page 40

3.10

Alarms Set Up Group

Introduction

This data deals with the Alarms function that is available with your controller. There are two alarms available. Each alarm has two setpoints. You can configure each of these two setpoints to alarm on one of nine events and you can configure each setpoint to alarm High or Low. You can also configure the two setpoints to alarm on the same event and to alarm both high and low, if desired.

Function prompts

Table 3-7

Table 3-7 lists all the function prompts in the “ALARMS” Set Up group.

Alarms Group Function Prompts

Function Prompt Lower Display

Function Name

Selections or Range of Setting

Factory Setting

Upper Display

30

A1S1 VAL

Alarm 1, Setpoint 1 Value

Value in Engineering Units

90

A1S2 VAL

Alarm 1, Setpoint 2 Value

Value in Engineering Units

10

A2S1 VAL

Alarm 2, Setpoint 1 Value

Value in Engineering Units

95

A2S2 VAL

Alarm 2, Setpoint 2 Value

Value in Engineering Units

5

A1S1TYPE

Alarm 1, Setpoint 1 Type NONE PV (Input 1) DEV (Deviation) SHED (Communications)

NONE

A1S2TYPE

Alarm 1, Setpoint 2 Type Same as A1S1TYPE

NONE

A2S1TYPE

Alarm 2, Setpoint 1 Type Same as A1S1TYPE

NONE

A2S2TYPE

Alarm 2, Setpoint 2 Type Same as A1S1TYPE

NONE

A1S1 H L

Alarm 1, Setpoint 1 State

LO HI

HI

A1S2 H L

Alarm 1, Setpoint 2 State

LO HI

LO

A2S1 H L

Alarm 2, Setpoint 1 State

LO HI

HI

A2S2 H L

Alarm 2, Setpoint 2 State

LO HI

LO

AL HYST

Alarm Hysteresis

0.0 to 5.0% of Span or 100% Output, as appropriate

0.1

UDC3300 Limit Controller Product Manual

1/01