Page 31
3.3
How To Get Started
Read the configuration tips
Read “Configuration Tips” shown on the next page. These tips will help you to easily and quickly accomplish the tasks at which you will be working when you configure your controller.
Read configuration procedure
Read “Configuration Procedure”. This procedure tells you how to access the Set Up groups, and the Function parameters within each of these groups that are shown in the Prompt Hierarchy in Figure 3-1.
Set Up groups
The Set Up groups and Function parameters are listed in the order of their appearance. The list includes the name of the prompt, the range of setting or selections available, and the factory setting.
Parameter explanations or definitions
If you need a detailed explanation of any prompt listed, refer to Section 4 Configuration Parameter Definitions. This section lists the Set Up and function prompts, the selection or range of settings that you can make for each, plus a detailed explanation or definition of each parameter.
Configuration record sheet
1/01
Located on the last page of this section is a “Configuration Record Sheet”. When you make your configuration selections, record them on this sheet. Then you will have a record of how the controller was configured.
UDC3300 Limit Controller Product Manual
21
Page 32
3.4
Configuration Tips
Introduction
Listed below in Table 3-1 are a few tips that will help you enter the configuration data more quickly. Table 3-1
Configuration Tips
Function
Tip
Displaying Groups
Use the [SET UP] key to display the Set Up groups. The group titles are listed in this section in the order that they appear in the controller.
Displaying Functions
Use the [FUNCTION] key to display the individual parameters under each group. The prompts are listed in the order of their appearance in each group.
Scrolling
To get to a Set Up group prompt more quickly, hold the [SET UP] key in. To get to a Function prompt more quickly, hold the [FUNCTION] key in. The display will scroll through the parameters.
ATTENTION The prompting scrolls at a rate of 2/3 seconds when the [SET UP] or [FUNCTION] key is held in. Also, [s] or [t] keys will move Group prompts forward and backward at a rate twice as fast.
22
Changing values quickly
When changing the value of a parameter, you can adjust a more significant digit in the upper display by holding in one key [s] or [t] , and pressing the other [s] or [t] at the same time. The adjustment will move one digit to the left. Press the key again and you will move one more digit to the left.
Restoring to the original value
When you change the value or selection of a parameter while in Set Up mode and decide not to enter it, press the lower blank key once, the original value or selection will be recalled.
Exiting SET UP mode
To exit Set Up mode, press the [LOWER DISPLAY] key. This returns the display to the same state it was in immediately preceding entry into the Set Up mode.
Timing out from Set Up mode
If you are in Set Up mode and do not press any keys for one minute, the controller will time out and revert to the mode and display that was being used prior to entry into Set Up mode.
Key Error
When a key is pressed and the prompt “KEY ERROR” appears in the lower display, it will be for one of the following reasons: • parameter not available • not in Set Up mode, press [SET UP] key first • key malfunction, do keyboard test (operation)
UDC3300 Limit Controller Product Manual
1/01
Page 33
3.5
Configuration Procedure
Introduction
Each of the Set Up groups and their functions are pre-configured at the factory. The factory settings are shown in the Set Up group tables that follow this procedure. If you want to change any of these selections or values, follow the procedure in Table 3-2. This procedure tells you the keys to press to get to any Set Up group and any associated Function parameter prompt.
Procedure
Follow the procedure listed in Table 3-2 to access the Set Up groups and Function prompts. ATTENTION
The prompting scrolls at a rate of 2/3 seconds when the [SET UP] or [FUNCTION] key is held in. Also, [s] [t] keys will move group prompts forward or backward at a rate of 1/3 seconds. Table 3-2 Step 1
Configuration Procedure Operation
Press
Select Set Up mode
SET UP
Result Upper Display SET UP
Lets you know you are in the configuration mode and a Set Up group title is being displayed in the lower display.
Lower Display LOCKOUT
2
Select any Set Up group
SET UP
This is the first Set Up group title.
Successive presses of the [SET UP ] key will sequentially display the other Set Up group titles shown in the prompt hierarchy in Figure 3-1. You can also use the [s] [t] keys to scan the Set Up groups in both directions. Stop at the Set Up group title which describes the group of parameters you want to configure. Then proceed to the next step.
3
Select a Function Parameter
Upper Display
FUNCTION
0
Lower Display SECURITY
Shows the first Function prompt within that Set Up group. Example displays show Set Up group “Lockout”, Function prompt “Security” and the code selected.
Continued on next page
1/01
UDC3300 Limit Controller Product Manual
23
Page 34
3.5
Configuration Procedure, Continued
Procedure, continued
Table 3-2 Step 4
Configuration Procedure, Continued Operation
Press
Select other Function Parameters
FUNCTION
Result Successive presses of the [FUNCTION] key will sequentially display the other function prompts of the Set Up group you have selected. Stop at the function prompt that you want to change, then proceed to the next step.
5
Change the value or selection
These keys will increment or decrement the value or selection that appears for the function prompt you have selected. or
See “Configuration Tips” for instructions to increase or decrease value quickly. Change the value or selection to meet your needs. If the display flashes, you are trying to make an unacceptable entry.
6
Enter the value or selection
This key selects another Function prompt.
FUNCTION or This key selects another Set Up group.
SET UP
7
Exit Configuration
LOWER DISPLAY
24
The value or selection you have made will be entered into memory after another key is pressed. This exits configuration mode and returns the controller to the same state it was in immediately preceding entry into the Set Up mode. It stores any changes you have made.
UDC3300 Limit Controller Product Manual
1/01
Page 35
3.6
Lockout Set Up Group
Introduction
The Lockout group provides three levels of keyboard security to protect configuration and calibration data. To further secure this data, there is a security code that can be entered which will permit changes to the lockout configuration.
Set this group last
DO NOT configure this group until all other configuration is complete.
Function prompts
Table 3-3 lists the function prompts in the “LOCKOUT” Set Up group.
Table 3-3
Lockout Group Function Prompts
Function Prompt Lower Display
Function Name
Selections or Range of Setting
Factory Setting
Upper Display
1/01
SECURITY
Security Code
0 to 4095
0
LOCKOUT
Configuration Lockout
NONE CALIB +CONF MAX
NONE
UDC3300 Limit Controller Product Manual
25
Page 36
3.7
Limit Set Up Group
Introduction
Limit control provides a latching output relay which is de-energized whenever the PV goes above (high limit) or below (low limit) a selected setpoint value. Reset is through the [RESET] key on the front of the controller or an optional external switch (Digital Input #1).
Function prompts
Table 3-4 lists the function prompts in the “LIMIT” Set Up group.
Table 3-4
Limit Group Function Prompts
Function Prompt Lower Display
Function Name
Selections or Range of Setting
Factory Setting
Upper Display
LO or HI
Type of Limit Control
LO LIM HI LIM
HI LIM
EXT RSET
External Reset (Digital Input 1)
DISABL ENABLE EXoNLY
DISABL
POWER UP
Power-up Logic
NORMAL RESET
NORMAL
SP HILIM
High Setpoint Limit
0 to 100% of Span in engineering units
1000
ATTENTION This value should never be set higher than the temperature limit of the oven or furnace being controlled. SP LOLIM
26
Low Setpoint Limit
0 to 100% of Span in engineering units
UDC3300 Limit Controller Product Manual
0
1/01
Page 37
3.8
Input 1 Parameters Set Up Group
Introduction
This data deals with various parameters required to configure Input 1.
Function prompts
Table 3-5 lists all the function prompts in the “INPUT 1” Set Up group.
Table 3-5
Input 1 Group Function Prompts
Function Prompt Lower Display
Function Name
Selections or Range of Setting
Factory Setting
Upper Display
DECIMAL
UNITS
IN1 TYPE
Decimal Point Location
XXXX XXX.X XX.XX
Temperature Units
DEG F DEG C NONE
Input 1 Actuation Type
B TC E TC H E TC L J TC H J TC L K TC H K TC L NNM H NNM L NM90 H NM90 L NIC TC R TC S TC T TC H
XXXX
None One Two
NONE
T TC L W TC H W TC L 100 PT 100 LO 200 PT 500 PT RAD RH RAD RI 0-20mA* 4-20mA* 0-10mV* 0-50mV* 0-5 V* 1-5 V* 0-10V*
0-10mV (K TC H for FM only)
*not available for FM models XMITTER
B TC E TC H E TC L J TC H J TC L K TC H K TC L NNM H NNM L NM90 H NM90 L NIC TC R TC
IN1 HI
Input 1 High Range Value (Linear Inputs and Radiamatic RI only)
–999. to 9999. in engineering units
1000 (2400 for FM only)
IN1 LO
Input 1 Low Range Value (Linear Inputs and Radiamatic RI only)
–999. to 9999. in engineering units
0
(not available for FM models)
S TC T TC H T TC L W TC H W TC L 100 PT 100 LO 200 PT 500 PT RAD RH RAD RI LINEAR SQROOT
LINEAR
Transmitter Characterization
Continued on next page
1/01
UDC3300 Limit Controller Product Manual
27
Page 38
3.8
Input 1 Group, Continued
Function prompts, continued
Table 3-5
Table 3-5 lists all the function prompts in the “INPUT 1” Set Up group.
Input 1 Group Function Prompts, Continued
Function Prompt Lower Display
Function Name
Selections or Range of Setting
Factory Setting
Upper Display
BIAS IN1
Input 1 Bias
FM: –10.0 to +10.0 Non-FM: –999. to 9999.
0
FILTER 1
Input 1 Filter
0 to 120 seconds
0
BURNOUT
Burnout Protection
Burnout is fixed.
UPSCALE for FM
For non-linear inputs: High Limit Control = Upscale Low Limit Control = Downscale
28
EMISSIV
Emissivity
0.01 to 1.00
0
PWR FREQ
Power Line Frequency
60 Hz 50 Hz
60 Hz
UDC3300 Limit Controller Product Manual
1/01
Page 39
3.9
Communications Set Up Group
Introduction
This data deals with the Communications option that is available with your controller. This option allows the controller to be connected to a host computer via a RS422/485 or DMCS bus. ATTENTION
FM-approved Limit controllers with Communications option are limited to READ ONLY (monitoring only) functionality. If your controller does not have the Communications option, the prompts will not appear. Function prompts
Table 3-6
Table 3-6 lists all the function prompts in the “Com” Set Up group.
Com Group Function Prompts
Function Prompt
Function Name
Lower Display
Selections or Range of Setting
Factory Setting
Upper Display
ComSTATE
Communications Option State
DISABL DMCS RS422
DISABL
Com ADDR
Communications Station Address
1 to 99
0
SHEDTIME
Shed Time
1 to 255 sample periods
0
Parity
ODD EVEN
ODD
Baud Rate
300 600 1200 2400
Duplex Operation
HALF FULL
HALF
Transmission Delay
1 to 500 milliseconds
1
Local Loop Back
DISABL ENABLE
DISABL
Communication Units
PERCNT ENG
ENG
PARITY (RS422/485 Only) BAUD (RS422/485 Only)
DUPLEX (RS422/485 Only) TX DELAY
4800 9600 19200
300
(RS422/485 Only) LOOPBACK
UNITS
1/01
UDC3300 Limit Controller Product Manual
29
Page 40
3.10
Alarms Set Up Group
Introduction
This data deals with the Alarms function that is available with your controller. There are two alarms available. Each alarm has two setpoints. You can configure each of these two setpoints to alarm on one of nine events and you can configure each setpoint to alarm High or Low. You can also configure the two setpoints to alarm on the same event and to alarm both high and low, if desired.
Function prompts
Table 3-7
Table 3-7 lists all the function prompts in the “ALARMS” Set Up group.
Alarms Group Function Prompts
Function Prompt Lower Display
Function Name
Selections or Range of Setting
Factory Setting
Upper Display
30
A1S1 VAL
Alarm 1, Setpoint 1 Value
Value in Engineering Units
90
A1S2 VAL
Alarm 1, Setpoint 2 Value
Value in Engineering Units
10
A2S1 VAL
Alarm 2, Setpoint 1 Value
Value in Engineering Units
95
A2S2 VAL
Alarm 2, Setpoint 2 Value
Value in Engineering Units
5
A1S1TYPE
Alarm 1, Setpoint 1 Type NONE PV (Input 1) DEV (Deviation) SHED (Communications)
NONE
A1S2TYPE
Alarm 1, Setpoint 2 Type Same as A1S1TYPE
NONE
A2S1TYPE
Alarm 2, Setpoint 1 Type Same as A1S1TYPE
NONE
A2S2TYPE
Alarm 2, Setpoint 2 Type Same as A1S1TYPE
NONE
A1S1 H L
Alarm 1, Setpoint 1 State
LO HI
HI
A1S2 H L
Alarm 1, Setpoint 2 State
LO HI
LO
A2S1 H L
Alarm 2, Setpoint 1 State
LO HI
HI
A2S2 H L
Alarm 2, Setpoint 2 State
LO HI
LO
AL HYST
Alarm Hysteresis
0.0 to 5.0% of Span or 100% Output, as appropriate
0.1
UDC3300 Limit Controller Product Manual
1/01