Page 41
3.11
Calib Group
Calibration data
3.12
Status Group
Status Test Data
1/01
The prompts used here are for field calibration purposes. Refer to Section 6 – Calibration in this manual for complete information and instructions.
The prompts used here are read only. They are used to determine the reason for a controller failure. Refer to Section 7 – Troubleshooting in this manual for complete information.
UDC3300 Limit Controller Product Manual
31
Page 42
3.13
Configuration Record Sheet
Keep a record
Enter the value or selection for each prompt on this sheet so you will have a record of how your controller was configured.
Group Prompt
Function Prompt
Value or Selection
Factory Setting
LOCKOUT
SECURITY LOCKOUT
__________ 0000 __________ None
LIMIT
LO or HI EXT RSET POWER UP SP HILIM SP LOLIM
__________ __________ __________ __________ __________
HI Disabl Normal 1000 0
INPUT 1
DECIMAL UNITS IN1 TYPE XMITTER IN1 HI IN1 LO BIAS IN1 FILTER 1 BURNOUT EMISSIV PWR FREQ
__________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________
XXXX None 0-10mV Linear 1000 0 0 0 None 0 60Hz
Group Prompt
Function Prompt
Value or Selection
Factory Setting
Com
ComSTATE Com ADDR SHEDTIME PARITY BAUD DUPLEX TX DELAY LOOPBACK UNITS
__________ __________ __________ __________ __________ __________ __________ __________ __________
Disabl 0 0 Odd 300 Half 1 Disabl Percent
ALARMS
A1S1 VAL A1S2 VAL A2S1 VAL A2S2 VAL A1S1TYPE A1S2TYPE A2S1TYPE A2S2TYPE A1S1 H L A1S2 H L A2S1 H L A2S2 H L AL HYST
__________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________
90 10 95 5 None None None None HI LO HI LO 0.1
Function Prompt
Value or Selection
Com
ComSTATE Com ADDR SHEDTIME PARITY BAUD DUPLEX TX DELAY LOOPBACK UNITS
__________ __________ __________ __________ __________ __________ __________ __________ __________
Disabl 0 0 Odd 300 Half 1 Disabl Percent
ALARMS
A1S1 VAL A1S2 VAL A2S1 VAL A2S2 VAL A1S1TYPE A1S2TYPE A2S1TYPE A2S2TYPE A1S1 H L A1S2 H L A2S1 H L A2S2 H L AL HYST
__________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________
90 10 95 5 None None None None HI LO HI LO 0.1
FM Models only Group Prompt
Function Prompt
LOCKOUT
SECURITY LOCKOUT
__________ 0000 __________ None
LIMIT
LO or HI EXT RSET POWER UP SP HILIM SP LOLIM
__________ __________ __________ __________ __________
HI Disabl Normal 1000 0
INPUT 1
DECIMAL UNITS IN1 TYPE IN1 HI IN1 LO BIAS IN1 FILTER 1 BURNOUT EMISSIV PWR FREQ
__________ __________ __________ __________ __________ __________ __________ __________ __________ __________
XXXX None K TC H 2400 0 0 0 Upscale 0 60Hz
32
Value or Selection
Factory Setting
Group Prompt
UDC3300 Limit Controller Product Manual
Factory Setting
1/01
Page 43
Section 4 – Configuration Prompt Definitions 4.1
Overview
Introduction
This section provides information for all the user configurable parameters listed in the configuration section. If you aren’t familiar with these parameters, this section gives you the parameter prompt, the selection or range of setting that you can make, and a definition of how each parameter setting affects controller performance. It will also refer you to any other prompts that might be affected by your selection.
What’s in this section?
The table below lists the topics that are covered in this section. They are listed in the order of their appearance in the controller. Contents
1/01
See Page
4.1
Overview
33
4.2
Lockout Data Set Up Group
34
4.3
Limit Data Set Up Group
35
4.4
Input 1 Set Up Group
36
4.5
Communications Set Up Group
40
4.6
Alarms Set Up Group
42
4.7
Calibration Data
44
4.8
Status Test Data
44
UDC3300 Limit Controller Product Manual
33
Page 44
4.2
Lockout Data Set Up Group
Introduction
The Lockout group provides three levels of keyboard security to protect configuration and calibration data. To further secure the data, there is a security code that can be entered which will permit changes to the lockout configuration.
Lockout group prompts
Table 4-1 lists all the function prompts in the “LOCKOUT” Set Up group and their definitions.
Table 4-1
Lockout Group Prompt Definitions
Lower Display Prompt SECURITY
Upper Display Range of Setting or Selection 0-4095
Parameter Definition SECURITY CODE - A security code may or may not be used to protect configuration or keyboard Lockout selection. In order to enable this feature, a code (up to four-digits) between 1 and 4095 must be entered, then the keyboard level lockout cannot be changed until you select this number (or 1000 as an override). After selecting this number here, be sure to copy and keep it in a secure location. NOTE: The Security Code is for keyboard entry only and is not available via communications. Can only be changed if “LOCKOUT” selection is “NONE.”
LOCKOUT
34
LOCKOUT applies to one of the functional groups: Configuration or Calibration. DO NOT CONFIGURE UNTIL ALL CONFIGURATION IS COMPLETE. NONE
No Lockout - all groups read/write.
CALIB
CALIB - All are available for read/write except for the Calibration group.
+CONF
+CONF - All groups are read only.
MAX
MAX - Only Lockout group is available. No other parameters are viewable.
UDC3300 Limit Controller Product Manual
1/01
Page 45
4.3
Limit Data Set Up Group
Introduction
Limit control provides a latching output relay which is de-energized whenever the PV goes above (high limit) or below (low limit) a selected setpoint value. Reset is through the [RESET] key on the front of the controller or an optional external switch (Digital Input 1).
Limit group prompts
Table 4-2 lists all the function prompts in the “LIMIT” Set Up group and their definitions.
Table 4-2
Limit Group Prompt Definitions
Lower Display Prompt LO or HI
EXT RSET
Upper Display Range of Setting or Selection
Parameter Definition
LO LIM
LOW LIMIT CONTROL, The latching output relay deenergizes when the PV goes below the configured setpoint. It cannot be reset until the PV rises above the configured setpoint.
HI LIM
HIGH LIMIT CONTROL, The latching output relay deenergizes when the PV goes above the configured setpoint. It cannot be reset until the PV drops below the configured setpoint.
DISABL ENABLE EXoNLY
EXTERNAL RESET, Only available with the Digital Input option. Allows the controller to be reset from a remote location by contact closure of a momentary-type switch. DISABL = External reset is not active. ENABLE = Enables external reset when Digital Input option is included in the controller. EXoNLY = Enables external reset and disables the keyboard [RESET] key.
POWER UP
NORMAL RESET
POWER UP LOGIC - What condition do you want the controller to be in at power up. RESET = Latching relay will have to be reset. NORMAL = Controller will operate in the same mode as before power was removed.
1/01
SP HILIM
0 to 100% of span input in engineering units with decimal place
SETPOINT HIGH LIMIT, This selection prevents the setpoint from going above the value selected here. The setting must be equal or less than the upper range of input 1.
SP LOLIM
0 to 100% of span input in engineering units with decimal place
SETPOINT LOW LIMIT - This selection prevents the setpoint from going below the value selected here. The setting must be equal or greater than the lower range of input 1.
UDC3300 Limit Controller Product Manual
35
Page 46
4.4
Input 1 Parameters Set Up Group
Introduction
These are the parameters required for input 1; temperature units, decimal location, actuation, transmitter characterization, high and low range values in engineering units, filter, burnout, emissivity, and power line frequency.
Input 1 group prompts
Table 4-3 lists all the function prompts in the “INPUT 1” Set Up group and their definitions.
Table 4-3
Input 1 Group Definitions
Lower Display Prompt
Upper Display Range of Setting or Selection
DECIMAL
Parameter Definition DECIMAL POINT LOCATION - This selection determines where the decimal point appears in the display.
XXXX XXX.X XX.XX
None One Place Two Places NOTE: Auto-ranging will occur when one decimal position has been selected and the value increases above 999.9 but auto-ranging will not similarly occur when two decimal positions are selected.
UNITS DEG F DEG C NONE
TEMPERATURE UNITS - This selection will be indicated on the annunciator. What display of temperature do you want. Degrees Fahrenheit Degrees Celsius None
Continued on next page
36
UDC3300 Limit Controller Product Manual
1/01
Page 47
4.4
Input 1 Parameters Set Up Group, Continued
Input 1 group prompts, continued
Table 4-3
Input 1 Group Definitions, Continued
Lower Display Prompt
Upper Display Range of Setting or Selection
IN1 TYPE
Parameter Definition INPUT 1 ACTUATION TYPE - This selection determines what actuation you are going to use for input one.
B TC E TC H E TC L J TC H J TC L K TC H K TC L NNM H NNM L NM90 H NM90 L NIC TC R TC S TC T TC H T TC L W TC H W TC L 100 PT 100 LO 200 PT 500 PT RAD RH RAD RI 0-20mA 4-20mA 0-10mV 0-50mV 0-5 V 1-5 V 0-10 V
B thermocouple 0 to 3300°F E thermocouple high–454 to 1832°F E thermocouple low –200 to 1100°F J thermocouple high 0 to 1600°F J thermocouple low 20 to 770°F K thermocouple high 0 to 2400°F K thermocouple low –20 to 1000°F NNM NiNiMo thermocouple high 32 to 2500°F NNM NiNiMo thermocouple low 32 to 1260°F NiMo-NiCo thermocouple high 32 to 2500°F NiMo-NiCo thermocouple low 32 to 1260°F NIC Nicrosil-Nisil thermocouple 0 to 2372°F R thermocouple 0 to 3100°F S thermocouple 0 to 3100°F T thermocouple high–300 to 700°F T thermocouple low –200 to 500°F W5W26 thermocouple high 0 to 4200°F W5W26 thermocouple low 0 to 2240°F 100 Ohm–RTD –300 to 1200°F 100 Ohm RTD low –300 to 300°F 200 Ohm RTD –300 to 1200°F 500 Ohm–RTD –300 to 1200°F Radiamatic (Type RH) 0 to 3400°F Radiamatic (Type RI) 0 to 20 Milliamps* 4 to 20 Milliamps* 0 to 10 Millivolts* 0 to 50 Millivolts* 0 to 5 Volts* 1 to 5 Volts* 0 to 10 Volts*
–18 to 1816°C –270 to 1000°C –129 to 593°C –18 to 871°C –7 to 410°C –18 to 1316°C –29 to 538°C 0 to 1371°C 0 to 682°C 0 to 1371°C 0 to 682°C –18 to 1300°C –18 to 1704°C –18 to 1704°C –184 to 371°C –129 to 260°C –18 to 2315°C –18 to 1227°C –184 to 649°C –184 to 149°C –184 to 649°C –184 to 649°C –18 to 1871°C
*not available for FM models
Continued on next page
1/01
UDC3300 Limit Controller Product Manual
37
Page 48
4.4
Input 1 Parameters Set Up Group, Continued
Input 1 group prompts, continued
Table 4-3
Input 1 Group Definitions, Continued
Lower Display Prompt
Upper Display Range of Setting or Selection
XMITTER
Parameter Definition TRANSMITTER CHARACTERIZATION - This selection lets you instruct the controller to characterize a linear input to represent a non-linear one.
(not available for FM models)
NOTE: Prompt only appears when a linear actuation is selected at prompt ‘IN1 TYPE”. FOR EXAMPLE: If input 1 is a 4 to 20 mA signal, but the signal represents a type "K" thermocouple; select "K TC H" and the controller will characterize the 4 to 20 mA signal so that it is treated as a type "K" thermocouple input (high range). B TC E TC H E TC L J TC H J TC L K TC H K TC L NNM H NNM L NM90 H NM90 L NIC TC R TC S TC T TC H T TC L W TC H W TC L 100 PT 100 LO 200 PT 500 PT RAD RH RAD RI LINEAR SQROOT
B Type Thermocouple E Type Thermocouple High E Type Thermocouple Low J Type Thermocouple High J Type Thermocouple Low K Type Thermocouple High K Type Thermocouple Low NNM NiNiMo Type Thermocouple High NNM NiNiMo Type Thermocouple Low NiMo-NiCo Type Thermocouple High NiMo-NiCo Type Thermocouple Low NIC Nicrosil Nisil Thermocouple R Type Thermocouple S Type Thermocouple T Type Thermocouple High T Type Thermocouple Low W5W26 Type Thermocouple High W5W26 Type Thermocouple Low 100 Ohm–RTD 100 Ohm RTD low 200 Ohm–RTD 500 Ohm–RTD Radiamatic (Type RH) Radiamatic (Type RI) Linear Range Extracts Square Root
Continued on next page
38
UDC3300 Limit Controller Product Manual
1/01
Page 49
4.4
Input 1 Parameters Set Up Group, Continued
Input 1 group prompts, continued
Table 4-3
Input 1 Group Definitions, Continued
Lower Display Prompt IN1 HI
Upper Display Range of Setting or Selection –999. to 9999. in Engineering units
Parameter Definition INPUT 1 HIGH RANGE VALUE in engineering units is displayed for all inputs but can only be configured for Radiamatic RI, linear, or square root transmitter characterization. Scale the #1 input signal to the display value you want for 100%. EXAMPLE: Actuation (Input) = 4 to 20 mA Alarms Set Up Groupž XE "Alarms Set Up Group" \i ž TC "3.10 .ii.Alarms Set Up Group" \l 4 ; Introduction¨This The control setpoint will be limited by the range of units selected here.
IN1 LO
–999. to 9999. in Engineering units
INPUT 1 LOW RANGE VALUE in engineering units is displayed for all inputs but can only be configured for Radiamatic RI, linear, or square root transmitter characterization. Scale the #1 input signal to the display value you want for 0%. See example given in IN1 HI. The control setpoint for Input 1 will be limited by the range of units selected here.
BIAS IN1
Non-FM: –999. to 9999.
BIAS ON INPUT 1 - Bias is used to compensate the input for drift of an input value due to deterioration of a sensor, or some other cause.
FM: –10.0 to +10.0
Select the bias value you want on input one. FILTER 1
0 to 120 seconds No filter = 0
FILTER FOR INPUT ONE - A software digital filter is provided for input 1 to smooth the input signal. You can configure the first order lag time constant from 1 to 120 seconds. If you do not want filtering, enter 0.
BURNOUT
Burnout is preset based on the type of model.
BURNOUT PROTECTION (SENSOR BREAK) provides most input types with upscale or downscale protection if the input fails. NO BURNOUT applies to linear inputs. HIGH LIMIT CONTROLLERS have upscale burnout. LOW LIMIT CONTROLLERS have downscale burnout.
EMISSIV
0.01 to 1.00
PWR FREQ
POWER LINE FREQUENCY - select whether your controller is operating at 60 Hz or 50 Hz. 60 Hz 50 Hz
1/01
EMISSIVITY is a correction factor applied to the Radiamatic input signal that is the ratio of the actual energy emitted from the target to the energy which would be emitted if the target were a perfect radiator. Available only for “Radiamatic” inputs.
60 HERTZ 50 HERTZ
UDC3300 Limit Controller Product Manual
39
Page 50
4.5
Communications Set Up Group
Introduction
This option allows the controller to be connected to a host computer via a RS422/485 or DMCS bus. Fifteen units can be configured over this link. The controller looks for messages from the computer at regular intervals. If these messages are not received within the configured shed time, the controller will SHED from the communications link and return to stand alone operation. The device address, parity, and baud rate are configurable. ATTENTION
FM-approved Limit controllers with Communications option are limited to READ ONLY (monitoring only) functionality. Communications group prompts
Table 4-4
Table 4-4 lists all the function prompts in the “COMMUNICATIONS” Set Up group and their definitions.
Communications Group Definitions
Lower Display Prompt
Upper Display Range of Setting or Selection
ComSTATE
Parameter Definition COMMUNICATIONS SELECTION RS422 - Allows RS422/485 communication prompts. DMCS - Allows DMCS communication prompts. DISABL - Disables the communications option.
RS422 DMCS DISABL Com ADDR
1 to 99 (RS422) 1 to 99 (DMCS)
COMMUNICATION STATION ADDRESS - This is a number that is assigned to a controller that is to be used with the communications option.
SHEDTIME
0 to 255
SHED TIME - The number that represents how many sample periods there will be before the controller sheds from communications. Each period equals 1/3 seconds or 0 = No shed.
PARITY
PARITY pertains to the use of a self-checking code employing binary digits in which the total number of ONE's (or ZERO's) in each permissible code expression is either ODD or EVEN.
(RS422/485 only)
ODD EVEN BAUD (RS422/485 only)
ODD PARITY EVEN PARITY BAUD RATE is the transmission speed in bits per second.
300 600 1200 2400 4800 9600 19200
300 BAUD 600 BAUD 1200 BAUD 2400 BAUD 4800 BAUD 9600 BAUD 19200 BAUD
Continued on next page
40
UDC3300 Limit Controller Product Manual
1/01