Page 51
4.5
Communications Set Up Group, Continued
Communications group prompts, continued
Table 4-4
Communications Group Definitions, Continued
Lower Display Prompt
Upper Display Range of Setting or Selection
DUPLEX (RS422/485 only)
Parameter Definition DUPLEX, Transmission Type
HALF FULL
HALF DUPLEX - Two wires FULL DUPLEX - Four wires
1 to 500 milliseconds
(RS422/485 only)
TX DELAY - Configurable response-delay timer allows you to force the UDC to delay its response for a time period of from 1 to 500 milliseconds compatible with the host system hardware/software.
LOOPBACK
LOCAL LOOPBACK tests the communications hardware.
TX DELAY
ENABLE
ENABLE - Allows loopback test. The UDC goes into Loopback mode in which it sends and receives its own message. The UDC displays “PASS” or “FAIL” in the upper display and “LOOPTEST” in the lower display as long as the test is running. The UDC will go into manual mode. The test will run until the operator disables it here.
DISABL
DISABLE - disables the Loopback test.
UNITS
COMMUNICATION UNITS - This selection determines how the controller values are expressed during communications. PERCNT ENG
1/01
PERCENT OF SPAN ENGINEERING UNITS
UDC3300 Limit Controller Product Manual
41
Page 52
4.6
Alarms Set Up Group
Introduction
An alarm is an indication that an event that you have configured (for example - Process Variable) has exceeded one or more alarm limits. There are two alarms available. Each alarm has two setpoints. You can configure each of these two setpoints to alarm on various controller parameters. There are two alarm output selections, High and Low. You can configure each setpoint to alarm either High or Low. These are called single alarms. You can also configure the two setpoints to alarm on the same event and to alarm both high and low. A single adjustable Hysteresis of 0.0% to 5.0% is configurable for the alarm setpoint.
Alarms group prompts
Table 4-5 lists all the function prompts in the “ALARMS” Set Up group and their definitions.
Table 4-5
Alarms Group Definitions
Lower Display Prompt
Upper Display Range of Setting or Selection
Parameter Definition
A1S1 VAL
Value in Engineering Units
ALARM 1 SETPOINT 1 VALUE - This is the value at which you want the alarm type chosen in Prompt "A1S1TYPE" to actuate. The value depends on what the setpoint has been configured to represent. NO setpoint is required for Communications SHED.
A1S2 VAL
Value in Engineering Units
ALARM 1 SETPOINT 2 VALUE - This is the value at which you want the alarm type chosen in Prompt "A1S2TYPE" to actuate. The details are the same as “A1S1 VAL”.
A2S1 VAL
Value in Engineering Units
ALARM 2 SETPOINT 1 VALUE - This is the value at which you want the alarm type chosen in Prompt “A2S1TYPE” to actuate. The details are the same as “A1S1 VAL”.
A2S2 VAL
Value in Engineering Units
ALARM 2 SETPOINT 2 VALUE - This is the value at which you want the alarm type chosen in Prompt “A2S2TYPE” to actuate. The details are the same as “A1S1 VAL”.
A1S1TYPE
ALARM 1 SETPOINT 1 TYPE - Select what you want Setpoint 1 of Alarm 1 to represent. It can represent the Deviation or Input 1, and if you have a model with communications, you can configure the controller to alarm on SHED. NONE PV DEV SHED
NO ALARM INPUT 1 DEVIATION SHED FROM COMMUNICATIONS
Continued on next page
42
UDC3300 Limit Controller Product Manual
1/01
Page 53
4.6
Alarms Set Up Group, Continued
Alarms group prompts, continued
Table 4-5
Alarms Group Definitions, Continued
Lower Display Prompt
Upper Display Range of Setting or Selection
Parameter Definition
A1S2TYPE
Same as A1S1 TYPE
ALARM 1 SETPOINT 2 TYPE - Select what you want Setpoint 2 of Alarm 1 to represent. The selections are the same as A1S1TYPE.
A2S1TYPE
Same as A1S1 TYPE
ALARM 2 SETPOINT 1 TYPE - Select what you want Setpoint 1 of Alarm 2 to represent. The selections are the same as A1S1TYPE.
A2S2TYPE
Same as A1S1 TYPE
ALARM 2 SETPOINT 2 TYPE - Select what you want Setpoint 2 of Alarm 2 to represent. The selections are the same as A1S1TYPE. ALARM 1 SETPOINT 1 STATE - Select whether you want the alarm type chosen in Prompt "A1S1TYPE" to alarm High or Low .
A1S1 H L
HI ALARM LO ALARM
HI LO
ALARM 1 SETPOINT 2 STATE - Select whether you want the alarm type chosen in Prompt "A1S2TYPE" to alarm High or Low . A1S2 H L
HI ALARM LO ALARM
HI LO
ALARM 2 SETPOINT 1 STATE - Select whether you want the alarm type chosen in Prompt "A2S1TYPE" to alarm HIGH or LOW. A2S1 H L
HI ALARM LO ALARM
HI LO
ALARM 2 SET POINT 2 STATE - Select whether you want the alarm type chosen in Prompt "A2S2TYPE" to alarm HIGH or LOW. A2S2 H L
HI LO
HI ALARM LO ALARM
AL HYST
0.0 to 5.0% of span or full output as appropriate
ALARM HYSTERESIS - A single adjustable hysteresis is provided on alarms such that when the alarm is OFF it activates at exactly the alarm setpoint; when the alarm is ON, it will not deactivate until the variable is 0.0% to 5.0% away from the alarm setpoint. Configure the hysteresis of the alarms based on INPUT signals as a % of input range span.
1/01
UDC3300 Limit Controller Product Manual
43
Page 54
4.7
Calibration Data
Introduction
4.8
Status Test Data
Introduction
44
The prompts used here are for field calibration purposes. Refer to Section 6 – Calibration in this manual for complete information.
The prompts used here are for determining the reason for a controller failure. Refer to the Section 7 – Troubleshooting in this manual for complete information.
UDC3300 Limit Controller Product Manual
1/01
Page 55
Section 5 – Operation 5.1
Overview
Introduction
This section gives you all the information necessary to monitor and operate your controller. Review the Operator Interface shown in “Monitoring” to make sure you are familiar with the indicator definitions. The key functions are listed in Section 1, Overview.
What’s in this section?
This section contains the following topics: Topic
1/01
See Page
5.1
Overview
45
5.2
How to Power Up the Controller Diagnostic Tests Troubleshooting Display and Key Check
46 46 46 47
5.3
Enter a Security Code Procedure
48 48
5.4
How to Operate Your Limit Controller Operating Principles Setting a Display Mode Viewing Limit Action Duration or Peak PV Value Selecting a Setpoint Value High or Low Limit Indication Non-Latching Relay Alarm Conditions Digital Input Option How to Reset the Latching Relay
49 50 50 50 50 51 51 51 51
5.5
How to Monitor Your Limit Controller Diagnostic Error Messages RS422 Communications DMCS Communications
52 52 53 53
5.6
Alarm Setpoints Introduction Displaying or Changing the Alarm Setpoints
54 54 54
5.7
Restarting After a Power Loss
55
UDC3300 Limit Controller Product Manual
45
Page 56
5.2
How to Power Up the Controller
Apply power
When power is applied, the controller will run three diagnostic tests. All the displays will light and then the controller will go into automatic mode.
Diagnostic tests
Table 5-1 lists the three diagnostic tests. Table 5-1
Power Up Diagnostic Tests
Prompt on Lower Display
Condition
RAM TEST
Check RAM
CONFTEST
Check Non-volatile memory
CAL TEST
Check Calibration
Test failures
If one or more of these tests fail, the controller will go to the Failsafe Mode, and “FAILSAFE” will flash in the lower display.
Troubleshooting
Refer to “STATUS TESTS” in Section 7, Troubleshooting to identify and correct the problem. Continued on next page
46
UDC3300 Limit Controller Product Manual
1/01
Page 57
5.2
How to Power Up the Controller, Continued
Check the displays and keys
Use the procedure in Table 5-2 to run the display and key test. Table 5-2
Procedure for Testing the Displays and Keys
Press SET UP
Result The controller will run a display test. All the displays will light for 8 seconds, then the displays will look like this:
and hold in, then
Upper Display
FUNCTION
Lower Display keys try all at the same time Press each key to see if it When the key is pressed, the lower display will indicate the works name of the key pressed. Key Pressed FUNCTION LOWER DISPLAY SET UP
RESET + FUNCTION+SETUP UPPER BLANK KEY LOWER BLANK KEY
Lower Display FUNCTION LWR DISP SET UP INCRMENT DECRMENT RESET INCRDECR FUNC SU UNUSED RESTORE
If no key is pressed for 20 seconds, the test will time out and the controller will go into control mode. If any test fails, go to “Controller Failure Symptoms” in Section 7, Troubleshooting. Key error
1/01
When a key is pressed and the prompt “KEY ERROR” appears in the lower display, it will be for one of the following reasons: • parameter not available, • not in Set Up mode, press [SET UP] key first, • key malfunction, do keyboard test.
UDC3300 Limit Controller Product Manual
47
Page 58
5.3
Enter a Security Code
Introduction
The LOCKOUT feature in the UDC3300 is used to inhibit changes (via keyboard) of certain functions or parameters by unauthorized personnel. There are different levels of LOCKOUT depending on the level of security required. These levels are: NONE CALIB +CONF MAX See Section 4, Configuration Definitions for details.
Security code numbers
The level of keyboard lockout may be changed in the Set Up mode. However, knowledge of a security code number (1 to 4095) may be required to change from one level of lockout to another. When a controller leaves the factory, it has a security code of 0 which permits changing from one lockout level to another without entering any other code number.
Procedure
If you require the use of a security code, select a number from 1 to 4095 and enter it when the lockout level is configured as “NONE”. Thereafter, that selected number must be used to change the lockout level from something other than “NONE”. CAUTION Write the number on the Configuration Record Sheet in the configuration section so you will have a permanent record; or, in case of a problem, refer to the keyboard failure troubleshooting section. Use the procedure in Table 5-3 to enter a security code. Table 5-3 Step
Procedure for Entering a Security Code Press
1
Action Until you see
SET UP
Upper Display SET UP Lower Display LOCKOUT
2
Until you see
FUNCTION
Upper Display 0 Lower Display SECURITY
3 or to enter a four digit number in the upper display (1 to 4095) This will be your security code.
48
UDC3300 Limit Controller Product Manual
1/01
Page 59
5.4
How to Operate Your Limit Controller
Overview
The indicators and displays on the operator interface let you see what is happening to your process and how the controller is responding. Figure 5-1 is a view of the operator interface. A description of the displays and indicators is included.
Figure 5-1
Operator Interface Upper Display - Six Characters
• Normal Operation - four digits dedicated to display the process variable, or blank • Configuration Mode - displays parameter value or selection Lower Display - Eight characters
• Normal Operation - displays the value of limit control setpoint, or indicates "LIMIT OK". When alarm condition exists, it alternates between the setpoint value and the word "LIMIT". • Configuration Mode - displays function group and parameters F - °Fahrenheit being used C - °Centigrade being used
Indicator definition when lit ALM - Alarm conditions exist DI - Digital Input active
ALM
12
DI
1
FC
RSP OUT
1
FUNCTION
LOWER DISPLAY
RESET
Keys - See Table 1-1 SET UP
22642
Decimal point position
In each display, when no decimal place is configured, the right-most character is blank. When a single decimal position has been configured and values greater than 1000 are displayed, the right-most character is blank but the decimal point will be lit. Continued on next page
1/01
UDC3300 Limit Controller Product Manual
49
Page 60
5.4
How to Operate Your Limit Controller, Continued
Operating principles
The UDC3300 Limit Controller accepts signals from such sources as thermocouples (T/Cs), Resistance Temperature Detectors (RTDs), milliamps, millivolts, and volts dc. The equivalent PV signal is compared with the limit setpoint and any error (difference) de-energizes a limit output relay. When de-energized, the output relay locks out and remains in this state until the PV input signal drops below the high limit setpoint or rises above the low limit setpoint, and the controller is reset manually from the front of the controller or through an optional external switch.
Setting a display mode
When an alarm condition exists, there are three display modes from which to choose: Press [LOWER DISPLAY] key to successively select one of the following three modes. DISPLAY MODE #1 Upper Display = the value of the PV Lower Display = the limit control setpoint value DISPLAY MODE #2 Upper Display = (blank) Lower Display = the limit control setpoint value DISPLAY MODE #3 Upper Display = (blank) Lower Display = LIMIT OK
Viewing limit action duration or peak PV value
When an alarm condition exists, you can view the parameters listed in Table 5-4. Table 5-4 To View Limit Action Duration Peak PV Value
Limit Action Duration or Peak PV Value Press LOWER DISPLAY
LOWER DISPLAY
Lower Display Shows the limit action duration in hours:minutes as “TIME XX.XX”. the highest PV value reached for a high limit controller, or the lowest PV value reached for a low limit controller as “PK XXXX”.
Continued on next page
50
UDC3300 Limit Controller Product Manual