The text of a manual · part 7 of 12
UDC3300 Universal Digital Limit Controller, pages 61 to 70
Pages 61 to 70 of 120
The original document is the PDF (544 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Honeywell UDC3300
Page 61
5.4
How to Operate Your Limit Controller, Continued
Selecting a setpoint value
Use the procedure in Table 5-5 to change the setpoint value in the lower display. Table 5-5 Step 1
Change a Setpoint Value Procedure Press LOWER DISPLAY
2
Action until you have selected display mode #1 or #2.
This changes the value of the limit controller setpoint.
or
NOTE: To change setpoint values quickly, you can adjust a more significant digit in the lower display by holding in one key [s] or [t] and pressing the other [s] or [t] at the same time. The adjustment will move one digit to the left. Press the key again and you will move another digit to the left.
High or low limit indication
When the High or Low limit setpoint is exceeded the lower display alternately indicates “the limit control setpoint value” and the word “LIMIT.” This will continue until you reset the latching relay.
Non-latching relay alarm conditions
The alarm is active if alarm setpoint 1 or alarm setpoint 2 is exceeded. The alarm goes inactive when the value goes into the allowed region by more than the hysteresis.
Digital input option
The digital input option detects the state of external contacts. On contact closure, the limit controller will be reset if the option has been enabled at prompt “EXT RSET” in Set Up group “Limit.” (See Sections 3 and 4 for explanation.)
How to reset the latching relay
The latching relay cannot be reset until the PV input signal drops below the high limit setpoint or rises above the low limit setpoint. Press the [RESET] key or make contact closure of an external switch if the digital input option is present.
1/01
UDC3300 Limit Controller Product Manual
51
Page 62
5.5
How to Monitor Your Limit Controller
Diagnostic error messages
The UDC3300 performs background tests to verify data and memory integrity. If there is a malfunction, an error message will be displayed. In the case of more than one simultaneous malfunctions, only the one with the highest priority will appear on the lower display. A list of error messages is contained in Table 5-6. If any of these error messages occur, refer to Section 7, Troubleshooting for information to correct the failure. Table 5-6
Error Messages
Prompt
Description
EE FAIL
Unable to write to non-volatile memory
FAILSAFE
Failsafe
INP1FAIL
Two consecutive failures of input 1 integration
INP1 RNG
Input 1 out-of-range Linear: ±10% out-of-range Characterized: ±1% out-of-range
PV LIMIT
PV ±10% out-of-range
Continued on next page
52
UDC3300 Limit Controller Product Manual
1/01
Page 63
5.5
How to Monitor Your Limit Controller, Continued
RS422 communications
Refer to the separate manual shipped with this controller.
DMCS communications (also refer to Gateway manual, Section 10)
Changing Parameters from the Keyboard The following occurs when parameters are changed from the keyboard: LOCAL SETPOINT When the local setpoint is changed, its new value will be entered into nonvolatile memory as soon as another key is pressed (other than raise/lower). If no other key is pressed, the new setpoint is automatically entered into non-volatile memory ONE-HALF MINUTE following the last change. Obviously, if someone turns power off a unit within one-half minute following a setpoint change and during which there was no further keyboard activity, the new setpoint will not be remembered when power is restored. OTHER THAN SETPOINT When any parameter, other than setpoint, is changed, its new value will be entered into non-volatile memory as soon as another key (other than raise/lower) is pressed. If no other key is pressed, the new parameter is automatically entered into non-volatile memory at one minute following the last change. Obviously, if someone turns the power off a unit within one minute following a parameter change (other than setpoint) and during which there was no further keyboard activity, the new parameter value will not be remembered when power is restored. MONITORING DMCS COMMUNICATIONS When a Limit Controller (non-FM models only) goes into “slave” mode, the LED indicator for RSP goes “ON” indicating “SLAVE” mode. Also, the ▲▼ keys do not work. You cannot make any adjustments to the configurable parameters.
1/01
UDC3300 Limit Controller Product Manual
53
Page 64
5.6
Alarm Setpoints
Introduction
An alarm consists of a relay contact and an operator interface indication. The alarm is de-energized if Setpoint 1 or Setpoint 2 is exceeded. The alarm is energized when the monitored value goes into the allowed region by more than the hysteresis. The relay contacts can be wired for normally open (NO) or normally closed (NC) at the rear terminals. See Section 2, Installation for details. There are four alarm setpoints, two for each alarm. The type and state (High or Low) is selected during configuration. See Section 3, Configuration for details.
Procedure for displaying and changing the alarm setpoints
The procedure for displaying and changing the alarm setpoints is listed in Table 5-7. Table 5-7 Step 1
Procedure for Displaying or Changing the Alarm Setpoints Operation
Press
Access the Alarm Set Up group
SET UP
Action Until you see: Upper Display SET UP Lower Display ALARMS
2
Access the Alarm Setpoint Values
FUNCTION until you see the desired alarm setpoint and its value. The specific prompts are shown below. Upper Display
The alarm setpoint value Lower Display
A1S1 VAL = (Alarm 1, Setpoint 1 value) A1S2 VAL = (Alarm 1, Setpoint 2 value) A2S1 VAL = (Alarm 2, Setpoint 1 value) A2S2 VAL = (Alarm 2, Setpoint 2 value)
or
3
54
Return to normal operation to change any alarm setpoint value you select in the upper display.
LOWER DISPLAY
UDC3300 Limit Controller Product Manual
1/01
Page 65
5.7
Restarting After Power Loss
Power-up logic
Configurable power-up logic lets you select the latching output relay to require “reset” or to provide normal operation at power-up. If the power to the controller fails and power is reapplied, the controller goes through power-up tests then starts in one of the following configurable conditions:
Display indications
If you have configured: UPPER DISPLAY = RESET LOWER DISPLAY = POWER UP ■ The lower display will alternately blink the limit setpoint value and the word “LIMIT.” This will require reset via the [RESET] key or external switch to obtain normal operation. If you have configured: UPPER DISPLAY = NORMAL LOWER DISPLAY = POWER UP ■ The displays and controller will function normally; i.e., no reset of latching relay is required unless a limit has been exceeded. If the limit was latched when power went down, the unit will be in limit at power-up. Refer to the Configuration section under Set Up prompt “LIMIT” and make your selection at Function prompt “POWER UP.”
1/01
UDC3300 Limit Controller Product Manual
55
Page 66
56
UDC3300 Limit Controller Product Manual
1/01
Page 67
Section 6 – Input Calibration 6.1
Overview
Introduction
This section describes the field calibration procedures for Input 1. Every UDC3300 Limit controller contains all input actuation ranges fully factory calibrated and ready for configuration to range by the user. However, these procedures can be implemented if the factory calibration of the desired range is not within specifications. Note that the field calibration will be lost if a change in input type configuration is implemented at a later time. The original factory calibration data remains available for later use after a field calibration is done.
What’s in this section
This section contains the following topics: Topic
See Page
6.1
Overview
57
6.2
Minimum and maximum range values
58
6.3
Preliminary Information • Disconnect the field wiring • Equipment needed
59 59 60
6.4
Input 1 Set Up Wiring • Thermocouple inputs using an ice bath • Thermocouple inputs using a precision resistor • RTD (Resistance Thermometer Device) inputs • Radiamatic, Millivolts, or Volts except 0-10 Volts inputs • 0 to 10 Volts input • 4-20 Milliamps input
61 61 62 63 64 65 66
6.5
Input 1 Calibration Procedure
67
WARNING - SHOCK HAZARD
!
INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DEENERGIZE UNIT BEFORE CALIBRATION.
1/01
UDC3300 Limit Controller Product Manual
57
Page 68
6.2
Minimum and Maximum Range Values
Select the range values
You should calibrate the controller for the minimum (0%) and maximum (100%) range values of your particular sensor. Select the Voltage or Resistance equivalent for 0% and 100% range values from Table 6-1. Use these values when calibrating your controller. Voltage and Resistance Equivalents for 0% and 100% Range Values
Table 6-1
Sensor Type
PV Input Range °F
Thermocouples B
Range Values °C
0%
100%
0 to 3300
–18 to 1816
–0.100 mV
13.769 mV
E
-454 to 1832
–270 to 1000
–9.835 mV
76.373 mV
E (low)
-200 to 1100
–129 to 593
–6.472 mV
44.455 mV
J
0 to 1600
–18 to 871
–0.886 mV
50.060 mV
J (low)
20 to 770
–7 to 410
–0.334 mV
22.400 mV
K
0 to 2400
–18 to 1816
–0.692 mV
52.952 mV
K (low)
–20 to 1000
–29 to 538
–1.114 mV
22.255 mV
NiNiMoly (NNM68)
32 to 2500
0 to 1371
0.000 mV
71.330 mV
NiNiMoly (low)
32 to 1260
0 to 682
0.000 mV
31.820 mV
NiMo-NiCo (NM90)
32 to 2500
0 to 1371
0.000 mV
71.773 mV
NiMo-NiCo (low)
32 to 1260
0 to 682
0.000 mV
31.825 mV
Nicrosil Nisil (Nic)
0 to 2372
–18 to 1300
–0.461 mV
47.513 mV
R
0 to 3100
–18 to 1704
–0.090 mV
20.281 mV
S
0 to 3100
–18 to 1704
–0.092 mV
17.998 mV
T
-300 to 700
–184 to 371
–5.341 mV
19.097 mV
T (low)
-200 to 500
–129 to 260
–4.149 mV
12.574 mV
W5W26
0 to 4200
–18 to 2315
–0.234 mV
37.075 mV
W5W26 (low)
0 to 2240
–18 to 1227
–0.234 mV
22.283 mV
Honeywell Radiamatic Type RH Type RI
0 to 3400 0 to 3200
–18 to 1871 –18 to 1760
0.00 mV 0.00 mV
57.12 mV 60.08 mV
-300 to 1200 -300 to 300 -300 to 1200 -300 to 1200
–184 to 649 –184 to 149 –184 to 649 –184 to 649
25.18 ohms 25.18 ohms 50.36 ohms 125.90 ohms
274.96 ohms 156.90 ohms 549.92 ohms 1374.80 ohms
RTD (IEC Alpha=0.00385) 100 ohms 100 ohms (low) 200 ohms 500 ohms Linear Milliamps
4 to 20 mA* 0 to 20 mA*
4.00 mA 0.00 mA
20.00 mA 20.00 mA
Millivolts
0 to 10 mV* 0 to 50 mV*
0.00 mV 0.00 mV
10.00 mV 50.00 mV
Volts
1 to 5 Volts* 0 to 5 Volts* 0 to 10 Volts*
1.00 Volts 0.00 Volts 0.00 Volts
5.00 Volts 5.00 Volts 10.00 Volts
* not available for FM models
58
UDC3300 Limit Controller Product Manual
1/01
Page 69
6.3
Preliminary Information
Calibration steps
Use the following steps when calibrating an input. Step
Disconnect the field wiring
Action
1
Find the minimum and maximum range values for your PV input range from Table 6-1.
2
Disconnect the field wiring and find out what equipment you will need to calibrate. DO NOT remove external resistor assemblies (if present).
3
Wire the calibrating device to your controller according to the Set Up wiring instructions for your particular input.
4
Follow the calibration procedure given for Input #1 after the controller has warmed up for a minimum of 15 minutes.
Tag and disconnect any field wiring connected to the input terminals on the rear of the controller. Figure 6-1 shows the wiring terminal designations for Input #1. Figure 6-1
Input #1 Wiring Terminals
10
1
11
2
L2/N 12
3
22
13
4
23
14
5
24
15
6
25
16
7
26
17
8
L1
R Input 1 connections
+ –
27
9 22648
Continued on next page
1/01
UDC3300 Limit Controller Product Manual
59
Page 70
6.3
Preliminary Information, Continued
Equipment needed
Table 6-2 lists the equipment you will need to calibrate the specific types of inputs that are listed in the table. You will need a screwdriver to connect these devices to your controller. Table 6-2
Equipment Needed
Type of Input
Equipment Needed
Thermocouple Inputs (Ice Bath)
• A calibrating device with ±0.02% accuracy for use as a signal source such as a millivolt source. • Thermocouple extension wire that corresponds with the type of thermocouple that will be used with the controller input. • Two insulated copper leads for connecting the thermocouple extension wire from the ice baths to the precision calibrator. • Two containers of crushed ice.
Thermocouple Inputs (Precision Resistor)
• A calibrating device with ±0.02% accuracy for use as a signal source such as a millivolt source. • Two insulated copper leads for connecting the calibrator to the controller. • A precision 500 ohm resistor ±0.1% connected across input #1 terminals 25 (R) and 27 (–).
RTD (Resistance Thermometer • A decade box, with ±0.02% accuracy, capable of Device) providing stepped resistance values over a minimum range of 0 to 1400 ohms with a resolution of 0.1 ohm. • Three insulated copper leads for connecting the decade box to the controller. Milliampere, Millivolt, Volts, and • A calibrating device with ±0.02% accuracy for use Radiamatic as a signal source. • Two insulated copper leads for connecting the calibrator to the controller. • Place current source at zero before switching ON. • Do not switch current sources OFF/ON while connected to the UDC3300 input.
60
UDC3300 Limit Controller Product Manual
1/01