For the Honeywell UDC3300

Page 71

6.4

Input #1 Set Up Wiring

Thermocouple inputs using an ice bath

Refer to Figure 6-2 and wire the controller according to the procedure given in Table 6-3. Table 6-3

Set Up Wiring Procedure for Thermocouple Inputs Using An Ice Bath

Step

Action

1

Connect the copper leads to the calibrator.

2

Connect a length of thermocouple extension wire to the end of each copper lead and insert the junction points into the ice bath.

3

Connect the thermocouple extension wires to the terminals for Input #1. See Figure 6-2.

4

Connect a cold junction resistor to terminals 25 and 27 for Input #1. See Figure 6-2.

Figure 6-2

Wiring Connections for Thermocouple Inputs Using an Ice Bath

+ –

10

1

L1

11

2

L2/N

12

3

22

13

4

23

14

5

24

15

6

25

16

7

26

17

8

27

9

T/C Extension Wire C/J Resistor

+ –

Millivolt Source

Copper Leads Ice Bath 24205

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

61

Page 72

6.4

Input #1 Set Up Wiring, Continued

Thermocouple inputs using a precision resistor

Refer to Figure 6-3 and wire the controller according to the procedure given in Table 6-4. Table 6-4

Set Up Wiring Procedure for Thermocouple Inputs Using a Precision Resistor

Step

Action

1

Connect the copper leads to the calibrator.

2

Disconnect the cold junction resistor.

3

Install a 500-ohm precision resistor across terminal 25 (R) and terminal 27 (–). See Figure 6-3.

4

Subtract the millivolt value for 77°F (25°C) from the zero and span value for your range (see Table 6-1 for zero and span values) and use the adjusted value when calibrating.

Figure 6-3

Wiring Connections for Thermocouple Inputs Using a Precision Resistor

R

+ –

10

1

L1

11

2

L2/N

12

3

22

13

4

23

14

5

24

15

6

25

16

7

26

17

8

27

Copper Leads

9 Precision 500 Ohm Resistor

– + 1

1

Millivolt Source

Caution: The accuracy of the controller is directly affected by the accuracy of this resistor. At a minimum, use a 0.1%, 25ppm resistor. 22628

Continued on next page

62

UDC3300 Limit Controller Product Manual

1/01

Page 73

6.4 RTD inputs

Input #1 Set Up Wiring, Continued Use the copper leads and connect the calibrator to the rear terminals of Input #1. See Figure 6-4. Figure 6-4

Wiring Connections for RTD (Resistance Thermometer Device)

R

+ –

10

1

L1

11

2

L2/N

12

3

22

13

4

23

14

5

24

15

6

25

16

7

26

17

8

27

9

Decade Resistance Box Copper Leads equal length

22629

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

63

Page 74

6.4

Input #1 Set Up Wiring, Continued

Radiamatic, millivolts, or volts (except 0 to 10 volts) inputs

Use the copper leads and connect the calibrator to the rear terminals of Input #1. See Figure 6-5. Figure 6-5

Wiring Connections for Radiamatic, Millivolts, or Volts (except 0 to 10 Volts)

+ –

10

1

L1

11

2

L2/N

12

3

22

13

4

23

14

5

24

15

6

25

16

7

26

17

8

27

9

– Millivolt/Volt + Source Copper Leads

22630

Continued on next page

64

UDC3300 Limit Controller Product Manual

1/01

Page 75

6.4

Input #1 Set Up Wiring, Continued

0 to 10 volt inputs

Use the copper leads and connect the calibrator to the rear terminals of Input #1. See Figure 6-6. Figure 6-6

Wiring Connections for 0 to 10 Volt Inputs

100K

10

1

L1

11

2

L2/N

12

3

22

13

4

23

14

5

24

15

6

25

16

7

26

17

8

100K

27

9

– Copper Leads

+

0 to 10 Volt Source

22631

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

65

Page 76

6.4

Input #1 Set Up Wiring, Continued

4 to 20 mA inputs

Use the copper leads and connect the calibrator to the rear terminals of Input #1. See Figure 6-7. Figure 6-7

Wiring Connections for 4 to 20 mA Inputs

250Ω resistor assy

Copper Leads

66

+ –

10

1

L1

11

2

L2/N

12

3

22

13

4

23

14

5

24

15

6

25

16

7

26

17

8

27

9

– 4 to 20 mA + Source

UDC3300 Limit Controller Product Manual

22632

1/01

Page 77

6.5

Input #1 Calibration Procedure

Introduction

Apply power and allow the controller to warm up for 15 minutes before you calibrate. Read “Set Up Wiring” before beginning the procedure. Make sure you have “LOCKOUT” set to “NONE.” See Section 3 – Configuration. CAUTION For linear inputs, avoid step changes in inputs. Vary smoothly from initial value to final 100% value. Procedure

Table 6-5 Step 1

The Calibration procedure for Input #1 is listed in Table 6-5. Input #1 Calibration Procedure Description

Press

Enter Calibration Mode

Action Upper Display

SET UP until you see

CALIB Lower Display INPUT 1

You will see:

FUNCTION

Upper Display DISABL Lower Display CAL IN1

The calibration sequence is enabled and you will see: Upper Display BEGIN Lower Display CAL IN1

At the completion of the sequence, the selection automatically reverts to disable. 2

Calibrate 0%

You will see:

FUNCTION

Upper Display APPLY Lower Display IN1 ZERO

Adjust your calibration device to an output signal equal to the 0% range value for your particular input sensor. See Table 6-1 for Voltage or Resistance equivalents. Wait 15 seconds, then go to the next step.

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

67

Page 78

6.5

Input #1 Calibration Procedure, Continued

Procedure, continued

Table 6-5 Step 3

Input #1 Calibration Procedure, Continued Description

Press

Calibrate 100%

Action You will see:

FUNCTION

Upper Display APPLY Lower Display IN1 SPAN

Adjust your calibration device to an output signal equal to the 100% range value for your particular input sensor. See Table 6-1 for Voltage or Resistance equivalents. Wait 15 seconds, and If… you are calibrating a Thermocouple input you are calibrating other than a Thermocouple input

4

Check the Cold Junction Temperature

FUNCTION

Go to step 5

The calculations for zero and span are now stored and you will see: Upper Display

ATTENTION The accuracy of the controller is directly affected by the accuracy of this value. Change this value only if the zero and span calibration procedures did not bring the controller within the specified accuracy requirements.

Then… Go to step 4

Lower Display

The cold junction temperature at the rear terminals

C-J TEMP

The value in the upper display is in the tenths of a degree. It is the current reading of the temperature as measured at the thermocouple terminals and recognized by the controller. You can change this value, if it is in error, using the s or t key.

ATTENTION When calibrating T/C inputs using a precision resistor, calibrate the cold junction as 77°F(25°C). 5

Exit the Calibration Mode

FUNCTION

68

The controller will store the calibration constants and exit calibration mode.

UDC3300 Limit Controller Product Manual

1/01

Page 79

Section 7 – Troubleshooting / Service 7.1

Overview

Introduction

Instrument performance can be adversely affected by installation and application problems as well as hardware problems. We recommend that you investigate the problems in the following order: • Installation related problems • Application related problems • Hardware and software related problems and use the information presented in this section to solve them. If a replacement of any part is required, follow the procedures listed under “Replacement Procedures”.

!

WARNING - SHOCK HAZARD INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DEENERGIZE UNIT BEFORE CALIBRATION.

What’s in this section?

The following topics are covered in this section. Topic

See Page

7.1

Overview

69

7.2

Troubleshooting Aids

71

7.3

Power-up Tests

73

7.4

Status Tests

74

7.5

Background Tests

76

7.6

Controller Failure Symptoms

78

7.7

Troubleshooting Procedures

79

7.8

Parts Replacement Procedures

83

7.9

Maintenance (Cleaning)

92

Continued on next page

1/01

UDC3300 Limit Controller Product Manual

69

Page 80

7.1

Overview, Continued

Installation related problems

Read the Installation section in this manual to make sure the UDC3300 has been properly installed. The installation section provides information on protection against electrical noise, connecting external equipment to the controller, and shielding and routing external wiring. ATTENTION

System noise induced into the controller will result in diagnostic error messages recurring. If the diagnostic error messages can be cleared, it indicates a “soft” failure and is probably noise related. If system noise is suspected, completely isolate the controller from all field wiring. Use calibration sources to simulate PV and check all controller functions; i.e. Inputs, Alarms, etc. Application related problems

Review the application of the controller; then, if necessary, direct your questions to the local sales office.

Hardware and software related problems

Use the troubleshooting error message prompts and controller failure symptoms to identify typical failures which may occur in the controller. Follow the troubleshooting procedures to correct them.

70

UDC3300 Limit Controller Product Manual

1/01