Page 81
7.2
Troubleshooting Aids
Overall error messages
An error message can occur • at power-up • during continuous background tests while in normal operation • when the Status Tests are requested Table 7-1 lists all the error message prompts that you could see, the reason for the failure, and under what test group the prompt could appear. Refer to Tables 7-3 (Power-up), 7-5 (Status), and 7-6 (Background) for the particular test group indicated. Table 7-1 Error Message (lower display)
Error Message Prompts Reason for Failure
Test Group
Refer to Table
CAL TEST
Calibration test failure
Power-up or Status
7-3 7-5
CONFTEST
Configuration test failure
Power-up or Status
7-3 7-5
E E FAIL
Unable to write to non-volatile memory
Background
7-6
FACT CRC
Factory Calibration Cyclic Redundancy test
Status
7-5
FAILSAFE
Controller in Failsafe
Power-up, Background, or Status
7-3 7-5 7-6
INP1FAIL
Two consecutive failures of Input 1 integration
Background
7-6
INP1 RNG
Input 1 Out of Range
Background
7-6
PV LIMIT
PV Out of Range
Background
7-6
RAM TEST
RAM test failed
Power-up or Status
7-3 7-5
Continued on next page
1/01
UDC3300 Limit Controller Product Manual
71
Page 82
7.2
Troubleshooting Aids, Continued
Controller failure symptoms
Other failures may occur that deal with the Power, Latching Output Relay, or Non-Latching Alarm Relays. Refer to the controller failure symptom in Table 7-7 to determine what is wrong and the troubleshooting procedures to use to correct the problem.
Check Installation
If a set of symptoms still persists, refer to Section 2, Installation and ensure proper installation and proper use of the controller in the system.
Determining the software version
Table 7-2 lists the procedure for identifying the software version number. Table 7-2 Step 1
Procedure for Identifying the Software Version Operation
Press
Select STATUS Set Up Group
SET UP
Action Until you see: Upper Display READ Lower Display STATUS
2
Read the software version
Until you see: FUNCTION
Upper Display
Lower Display
Software version Number
VERSION
Please give this number to the Customer Support person. It will indicate which version of UDC3300 you have and help them determine a solution to your problem.
72
UDC3300 Limit Controller Product Manual
1/01
Page 83
7.3
Power-up Tests
What happens at power-up
When the controller is powered-up, three tests are run by the UDC3300 software to ensure memory integrity. As the tests are run, the displays will appear as shown in Table 7-3. Table 7-3
Power-up Tests Lower Display
Test failures
Upper Display
RAM TEST
PASS or FAIL
CONFTEST
PASS or FAIL
CAL TEST
PASS or FAIL
If any of these three tests fail, “FAILED” will appear momentarily in the upper display, then a display test is run, after which the controller will go into manual mode and you will see: Upper Display
PV value Lower Display FAILSAFE
(blinking)
Refer to “Status Tests” to determine which tests have failed and how to correct them.
1/01
UDC3300 Limit Controller Product Manual
73
Page 84
7.4
Status Tests
Introduction
When required, the results of these tests can be checked to determine the reason the controller has gone to “Failsafe”.
How to check the status tests
The procedure in Table 7-4 tells you how to display the results of the status tests. Table 7-5 lists the tests, the reason for the failure, and how to correct the problem. Table 7-4 Step 1
Procedure for Displaying the Status Tests Results Operation
Press
Select STATUS Set Up Group
SET UP
Action Until you see: Upper Display READ Lower Display STATUS
2
Read the status tests results
Until you see: FUNCTION
Upper Display NO or YES
YES indicates a failure
Lower Display FAILSAFE
Successive presses of the [FUNCTION] key will display the results of the status tests in the following order: RAM TEST CONF TEST CAL TEST FACT CRC Identify the problem and correct the failure as shown in Table 7-5.
Continued on next page
74
UDC3300 Limit Controller Product Manual
1/01
Page 85
7.4
Status Tests, Continued
Status Tests
Table 7-5 lists the Status tests, the reason for their failure, and how to correct the failure.
Table 7-5
Status Tests
Test (Lower Display)
Definition
Upper Display
FAILSAFE
Failsafe Fault
NO
No Failure
YES
Burnout configured for none and input fails. –RAM TEST failed –CONFTEST failed –CALTEST failed
1. Step through the rest of the STATUS check to identify the particular failure.
PASS
No Failure
RAM test passed.
FAIL
RAM Failure
1. Power cycle to see if the error clears.
PASS
No Failure
Configuration checksum passed.
FAIL
Configuration data is in error.
1. Step through STATUS tests – the controller will recalculate the checksum.
RAM TEST
CONF TEST
RAM Test Run at Power-up Configuration Checksum
Reason for Failure
How to Correct the Failure
Also see Table 7-6, Background tests.
2. Check all configuration prompts for accuracy. See Section 3 Configuration. CAL TEST
Working Calibration
PASS
No Failure
Working calibration checksum passed.
FAIL
The working calibration constants in the controller are in error.
1. If the controller has not been field calibrated, see Section 3 Configuration and change the input to a different type. Enter it, loop through the status tests, then return the input type to the original one. 2. If the controller has been field calibrated, recalibrate the controller.
FACT CRC
Factory Calibration Test
PASS
No Failure
Factory calibration cyclic redundancy test passed.
FAIL
Factory set input constants have been changed due to the change in input type.
1. Cycle through Status to clear the error. 2. Check the calibration. Make sure 0 and 100% are correct values. 3. Recalibrate if step 1 is unsatisfactory. Refer to Section 6 - Input Calibration.
1/01
UDC3300 Limit Controller Product Manual
75
Page 86
7.5
Background Tests
Introduction
The UDC3300 performs on-going background tests to verify data and memory integrity. If there is a malfunction, an error message will be displayed (blinking) in the lower display.
Background tests
Table 7-6 Lower Display EE FAIL
FAILSAFE
INP1FAIL
In the case of more than one simultaneous malfunction, only the one with the highest priority will appear in the lower display. Table 7-6 lists these background tests, the reason for their failure, and how to correct the problem. Background Tests Reason for Failure
How to Correct the Problem
Unable to write to non-volatile memory. Anytime you change a parameter and it is not accepted, you will see EE FAIL.
1. Check the accuracy of the parameter and re-enter.
This error message shows whenever the controller goes into a failsafe mode of operation. This will happen if: • RAM test failed • Configuration test failed • Calibration test failed • Burnout configured for none and the input failed.
1. Run through STATUS check to determine the reason for the failure.
Two consecutive failures of input 1 integration. i.e., cannot make analog to digital conversion.
1. Make sure the actuation is configured correctly. See Section 3, Configuration.
2. Try to change something in configuration. 3. Run through STATUS tests to re-write to EEPROM.
2. Press the [SET UP] key until STATUS appears in the lower display. 3. Press the [FUNCTION] key to see what tests pass or fail, then run through the STATUS codes a second time to see if the error cleared. Correct according to the recommendations given in Table 7-5.
2. Make sure the input is correct. 3. Check for gross overranging. 4. Restore the factory calibration: a. Disconnect the wiring from and place a jumper across terminals 26 and 27. The controller should read room temperature if it is configured for a thermocouple input. b. If it does not read room temperature, see Section 3 – Configuration and change the IN1TYP prompt in the INPUT 1 group to another type of thermocouple. c. After the change, press [FUNCTION] key, then the [LOWER DISPLAY] key. The limit controller should read the correct room temperature. If it does not, the unit has an input failure. d. Repeat step b. This time switch the IN1TYP back to the originally selected thermocouple. e. Repeat step c. The controller is restored with factory calibration. f. Remove the jumper and reconnect the thermocouple. 5. Replace the cold junction assembly.
Table continued on next page
76
UDC3300 Limit Controller Product Manual
1/01
Page 87
7.5
Background Tests, Continued
Background tests, continued
Table 7-6 Lower Display INP1 RNG
Background Tests, Continued Reason for Failure
How to Correct the Problem
Input 1 out of range. The process input is outside the range limits.
1. Make sure the range and actuation are configured properly.
If you have a linear input and the range goes outside the range limits, the controller will switch to Limit mode.
2. Check the input source. 3. Restore the factory calibration: a. Disconnect the wiring from and place a jumper across terminals 26 and 27. The controller should read room temperature if it is configured for a thermocouple input. b. If it does not read room temperature, see Section 3 – Configuration and change the IN1TYP prompt in the INPUT 1 group to another type of thermocouple. c. After the change, press [FUNCTION] key, then the [LOWER DISPLAY] key. The limit controller should read the correct room temperature. If it does not, the unit has an input failure. d. Repeat step b. This time switch the IN1TYP back to the originally selected thermocouple. e. Repeat step c. The controller is restored with factory calibration. f. Remove the jumper and reconnect the thermocouple. 4. Field calibrate. See Section 6, Input Calibration.
PV LIMIT
PV out of range. PV = INP1 + INP1 BIAS
1. Make sure the input signal is correct. 2. Make sure the Bias setting is correct 3. Recheck the calibration. Use Bias of 0.0.
1/01
UDC3300 Limit Controller Product Manual
77
Page 88
7.6
Controller Failure Symptoms
Introduction
In addition to the error message prompts, there are failure symptoms that can be identified by noting how the controller displays and indicators are reacting.
Symptoms
Compare your symptoms with those shown in Table 7-7 and refer to the troubleshooting procedure indicated to correct the problem.
Table 7-7
Controller Failure Symptoms
Upper Display
Lower Display
Controller Output
Probable Cause
Troubleshooting Procedure
Blank
Blank
None
Power Failure
1
OK
Lower Display disagrees with Latching Output Relay function
Latching Output Relay function disagrees with Lower Display
Latching Output Relay
2
OK
OK
External Alarm function does not operate properly
Malfunction in alarm output
3
Display does not function when a key is pressed
Keyboard Malfunction
4
Controller fails to go into “Slave” operation during communications
Communications Failure
5
Other symptoms
If a set of symptoms or prompts other than the one you started with appears while troubleshooting, re-evaluate the symptoms. This may lead to a different troubleshooting procedure. If the symptom still persists, refer to the installation section in this manual to ensure proper installation and proper use of the controller in your system.
78
UDC3300 Limit Controller Product Manual
1/01
Page 89
7.7
Troubleshooting Procedures
Introduction
The troubleshooting procedures are listed in numerical order as they appear in Table 7-7. Each procedure lists what to do if you have that particular failure and how to do it or where to find the data needed to accomplish the task.
WARNING - SHOCK HAZARD
!
TROUBLESHOOTING MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DEENERGIZE UNIT BEFORE SERVICING.
Equipment needed
You will need the following equipment in order to troubleshoot the symptoms listed in the tables that follow: • DC Milliammeter – mAdc • Calibration sources – T/c, mV, Volt, etc. • Voltmeter
Procedure #1
Table 7-8 explains how to troubleshoot power failure symptoms. Table 7-8 Step 1
Troubleshooting Power Failure Symptoms What to do Check the AC line voltage.
How to do it Use a Voltmeter to measure the AC voltage across terminals L1 and L2 on the rear terminal panel of the controller. Check the earth ground connection.
2
Make sure the chassis plugs into the rear of the case properly.
Withdraw the chassis and visually inspect the controller board and the inside of the case.
3
Check the system for Brown-outs, heavy load switching, etc., and conformance to installation instructions.
Refer to Section 2 - Installation.
Continued on next page
1/01
UDC3300 Limit Controller Product Manual
79
Page 90
7.7
Troubleshooting Procedures, Continued
Procedure #2
Table 7-9 explains how to troubleshoot Latching Output Relay failure symptoms. Table 7-9
Procedure #3
Troubleshooting Latching Output Relay Failure
Step
What to do
How to do it
1
Make sure all the configurable data for the Limit controller is correct.
See the Configuration section in this manual to check the configuration data and to reconfigure, if necessary.
2
Check that the latching relay actuates properly.
Move the setpoint above or below the PV value, depending on the type of limit control. Listen for the click of the relay as the setpoint moves above or below the PV.
Table 7-10 explains how to troubleshoot Alarm Relay Output failure. Table 7-10
Troubleshooting Alarm Relay Output Failure
Step
What to do
How to do it
1
Check the alarm configuration data. If it is correct, check the field wiring.
Reconfigure if necessary.
2
Check that the applicable alarm relay actuates properly depending on what you have set at prompt “ALARM TYPE”. If it does, check the field wiring.
Place the controller in manual mode. Vary the input to raise and lower the PV around the setpoint. Listen for a click from the relay as the PV moves in either direction and note that the proper ALM1 or ALM2 is lit.
3
Check the field wiring.
Make sure the NO or NC contact wiring is correct on the alarm output terminals.
Refer to Section 3 – Configuration for details.
Refer to Section 2 – Installation for details.
Continued on next page
80
UDC3300 Limit Controller Product Manual
1/01