The text of a manual · part 13 of 31
DX-9100 Configuration Guide: Software Configuration, pages 111 to 120
Pages 111 to 120 of 288, from DX-9100 Configuration Guide
The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Johnson Controls DX-9100
Page 111
Algorithm 13 Maximum Select
The Maximum Select algorithm selects the maximum values of up to eight input variables. Each input may be weighted with a constant K. If an input is not connected, the corresponding variable is automatically excluded from the calculation. If one of the inputs is required to be a constant, connect an analog constant (ACO). K0 + MAX. (I1*K1, I2*K2, ... , I8*K8)
Function
In@= Input Variable Connection n = 1-8
Kn = Constant n = 0-8
Via the GX Tool
Click on PM in the toolbar, select Numeric, then Maximum and position the module (box) on the screen. Make connections between source points and destination points In@, as applicable. Select the module (box) on screen and then Data to call up the Data Window. Under numbers 0 through 8, enter appropriate values to complete the calculation. Via the SX Tool
This algorithm is assigned to a programmable function module when the value 13 is configured in PM Item PMnTYP (RI.00). To connect to the Input Variable Connection, enter the source addresses at Alg. Item In@, (RI.10-RI.17). Enter the values for the constants at Alg. Item Kn, (RI.26-RI.34). High/Low Limits
The output of the module is limited by the high and low limits. Use these limits to keep the output within a reasonable range in case of the failure of an input. Via the GX Tool
Select the maximum module on screen and then Data to call up the Data Window. Then enter the appropriate values in the High Limit and Low Limit fields. If the calculation > high limit, then NCM = high limit If the calculation < low limit, then NCM = low limit Via the SX Tool
The module output can be limited by a low limit value entered at Alg. Item LOL (RI.37) and a high limit at Alg. Item HIL (RI.36).
Configuration Guides - DX-9100 Configuration Guide
111
Page 112
Notes
1.
On the SX Tool, the output of the algorithm can be seen under Program Modules at Alg. Item NCM (RI.60).
2.
The logical status of the algorithm can be seen on the SX Tool under Program Modules at PM Item PMnST (RI.72) with following bit structure: X1 = 1
NML
Calculated Output is at Low Limit.
X2 = 1
NMH
Calculated Output is at High Limit.
3.
The module can be put in Hold mode by entering the value 1 in PM Item PMnHDC (RI.70) bit X1. (This can only be done via the PLC or SX Tool.) Its numeric output (NCM) can be modified in the Hold mode by a BAS or SX Tool.
4.
As the maximum select output cannot be read at the DX front panel, it is recommended that this algorithm is used in the higher PM numbers, reserving the lower PM numbers for algorithms that can be displayed.
Status Items can be used as logic (digital) connections using the GX Tool or SX Tool. GX Labels
Source Points (Outputs)
PMnHLD
A 1 when the program module is in the Hold mode, being overridden by the SX Tool or a BAS.
PMnNCM
The calculation result of a numeric module.
PMnNMH
A 1 when the calculated output is equal to or greater than the numeric module high limit.
PMnNML
A 1 when the calculated output is less than or equal to the numeric module low limit.
Destination Points (Inputs)
In@
112
Analog input connections to a programmable module.
Configuration Guides - DX-9100 Configuration Guide
Page 113
Algorithm 14 Psychrometric Calculation °C
Note: Only one Programmable Module within a DX controller may be configured as Algorithm 14 or 15.
Function
Via the GX Tool
This Psychrometric algorithm provides two calculation channels, each with an output that is a function of two inputs, one representing humidity, and the other temperature.
Click on PM in the toolbar, select Numeric, then Psychrometric and position the module (box) on the screen. Select the module and then Data to call up the Data Window. In the FUNCTION TYPE fields, enter a value describing the type of each of the two channels as follows: 0
= Disabled
1
= Enthalpy calculation
2
= Wet bulb calculation (Channel 1 only)
3
= Dew point calculation (Channel 1 only)
Via the SX Tool
This algorithm is assigned to a programmable function module when the value 14 is configured in PM Item PMnTYP (RI.00). You must first define the function of each channel of the algorithm. Select Alg. Items FUN1 (RI.02) or FUN2 (RI.03) and define them as follows:
Humidity and Temperature
X2X1 = 00
Disabled
X2X1 = 01
Enthalpy calculation KJ/Kg
X2X1 = 10
Wet Bulb calculation (Channel 1 only)
X2X1 = 11
Dew Point calculation (Channel 1 only)
Next, define the analog input variables: Via the GX Tool
Make connections between the source points and the destination points TEMP1@, HUMID1@, TEMP2@, and HUMID2@ as applicable for: Temperature Source Channel 1 Relative Humidity Source Channel 1 Temperature Source Channel 2 Relative Humidity Source Channel 2
Configuration Guides - DX-9100 Configuration Guide
113
Page 114
Via the SX Tool
TM1@ = Input variable connection for temperature value (T) - Channel 1 (RI.10) RH1@ = Input variable connection for relative humidity value (F) - Channel 1 (RI.11) TM2@ = Input variable connection for temperature value (T) - Channel 2 (RI.12) RH2@ = Input variable connection for relative humidity value (F) - Channel 2 (RI.13) Atmospheric Pressure
Via the GX Tool
Select the psychrometric module and then Data to call up the Data Window. At the Atm. Press. no. 1 (mbar) and Atm. Press no. 2 (mbar) fields, enter the atmospheric pressure (mbar) appropriate for your area. Via the SX Tool
The atmospheric pressure (in mbar) can be specified for each channel at Alg. Item ATP1 (RI.38) and ATP2 (RI.55). High/Low Limits
The output of the module is limited by the high and low limits. Use these limits to keep the output within a reasonable range in case of the failure of an input. Via the GX Tool
Select the psychrometric module and then Data to call up the Data Window. Enter values in the High Limit and Low Limit fields. If the calculation > high limit, then NCM = high limit If the calculation < low limit, then NCM = low limit Via the SX Tool
The module output can be limited by a low limit value entered at Alg. Item LOL (RI.37 and 54) and a high limit at Alg. Item HIL (RI.36 and 53).
114
Configuration Guides - DX-9100 Configuration Guide
Page 115
Notes
GX Labels
1.
On the SX Tool, the output of each channel can be seen under Program Modules at Alg. Item NCM1 (RI.60) and NCM2 (RI.61).
2.
The logic status of each channel can be seen on the SX Tool under Program Modules at PM Item PMnST (RI.72), with following bit structure: X1 = 1
NML1 Calculated Output is at Low Limit - Channel 1
X2 = 1
NMH1 Calculated Output is at High Limit - Channel 1
X3 = 1
NML2 Calculated Output is at Low Limit - Channel 2
X4 = 1
NMH2 Calculated Output is at High Limit - Channel 2
3.
Status Items can be used as logic (digital) connections using the GX Tool or SX Tool.
4.
Channel 2 is only available on DX-9100 Version 1.1 or later, and provides only an enthalpy calculation.
5.
The module channels can be put in Hold mode by entering the value 1 in PM Item PMnHDC (RI.70), HLD1 at bit X1 for Channel 1, HLD2 at bit X2 for Channel 2. (This can only be done via the SX Tool.) Its numeric outputs (NCM1 and NCM2) can be modified in the Hold mode.
6.
As the numeric output cannot be read at the DX front panel, it is recommended that this algorithm is used in the higher PM numbers, reserving the lower PM numbers for algorithms that can be displayed.
7.
Only one Programmable Module within a DX controller may be configured as Algorithm 14 or 15.
Source Points (Outputs)
PMnHLDm A 1 when the channel of the program module has been overridden (in hold) from an SX service module or a BAS. PMnNCMm The calculation result of a channel of a numeric module. PMnNMHm A 1 when the psychrometric numeric module output is equal to or greater than the high limit of the channel. PMnNMLm A 1 when the psychrometric numeric module output is less than or equal to the low limit of the channel. Destination Points (Inputs)
HUMIDn@ The relative humidity sensor connections for psychrometric calculations. TEMPn@
The temperature sensor connections for psychrometric calculations.
Configuration Guides - DX-9100 Configuration Guide
115
Page 116
Algorithm 15 Psychrometric Calculation °F
Note: Only one programmable module within a DX controller may be configured as Algorithm 14 or 15.
Function
Via the GX Tool
This Psychrometric algorithm provides two calculation channels, each with an output that is a function of two inputs, one representing humidity, and the other temperature.
Click on PM in the toolbar, select Numeric, then Psychrometric, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. In the Function Type fields, enter a value describing the type of each of the two channels as follows: 0
= Disabled
1
= Enthalpy calculation
2
= Wet bulb calculation (Channel 1 only)
3
= Dew point calculation (Channel 1 only)
Via the SX Tool
This algorithm is assigned to a programmable function module when the value 15 is configured in PM Item PMnTYP (RI.00). You must first define the function of each channel of the algorithm. Select Alg. Items FUN1 (RI.02) or FUN2 (RI.03) and define them as follows:
Humidity and Temperature
X2X1 = 00
Disabled
X2X1 = 01
Enthalpy calculation Btu/lb
X2X1 = 10
Wet Bulb calculation °F (Channel 1 only)
X2X1 = 11
Dew Point calculation °F (Channel 1 only)
Next, define the analog input variables: Via the GX Tool
Make connections between the source points and the destination points TEMP1@, HUMID1@, TEMP2@, and HUMID2@ as applicable for:
116
•
Temperature Source Channel 1
•
Relative Humidity Source Channel 1
•
Temperature Source Channel 2
•
Relative Humidity Source Channel 2
Configuration Guides - DX-9100 Configuration Guide
Page 117
Via the SX Tool
Atmospheric Pressure
TM1@
= Input variable connection for temperature value Channel 1 (RI.10)
RH1@
= Input variable connection for relative humidity value Channel 1 (RI.11)
TM2@
= Input variable connection for temperature value Channel 2 (RI.12)
RH2@
= Input variable connection for relative humidity value Channel 2 (RI.13)
Via the GX Tool
Select the psychrometric module and then Data to call up the Data Window. At the Atm. Press. no. 1 (mbar) and Atm. Press no. 2 (mbar) fields, enter the atmospheric pressure (mbar) appropriate for your area. Via the SX Tool
The atmospheric pressure (in mbar) can be specified for each channel at Alg. Item ATP1 (RI.38) and ATP2 (RI.55). Notes: Standard Sea Level barometric pressure is 1000 mbar or 29.92 in. HG. To convert barometric pressure from inches of mercury (in. HG) to mbar, use this formula: Pressure (mbar) = 33.42 x Pressure (in. HG) High/Low Limits
The output of the module is limited by the high and low limits. Use these limits to keep the output within a reasonable range in case of the failure of an input. Via the GX Tool
Select the psychrometric module and then Data to call up the Data Window. Enter values in the High Limit and Low Limit fields. If the calculation > high limit, then NCM = high limit. If the calculation < low limit, then NCM = low limit. Via the SX Tool
The module output can be limited by a low limit value entered at Alg. Item LOL (RI.37 and 54) and a high limit at Alg. Item HIL (RI.36 and 53).
Configuration Guides - DX-9100 Configuration Guide
117
Page 118
Notes
GX Labels
1.
On the SX Tool, the output of each channel can be seen under Program Modules at Alg. Item NCM1 (RI.60) and NCM2 (RI.61).
2.
The logic status of each channel can be seen on the SX Tool under Program Modules at PM Item PMnST (RI.72), with the following bit structure: X1 = 1
NML1 Calculated Output is at Low Limit - Channel 1
X2 = 1
NMH1 Calculated Output is at High Limit - Channel 1
X3 = 1
NML2 Calculated Output is at Low Limit - Channel 2
X4 = 1
NMH2 Calculated Output is at High Limit - Channel 2
3.
Status Items can be used as logic (digital) connections using the GX Tool or SX Tool.
4.
Channel 2 is only available on DX-9100 Version 1.1 or later, and provides only an enthalpy calculation.
5.
The module channels can be put in Hold mode by entering the value 1 in PM Item PMnHDC (RI.70), HLD1 at bit X1 for Channel 1, HLD2 at bit X2 for Channel 2. (This can only be done via the PLC or SX Tool.) Its numeric output (NCM) can be modified in the Hold mode by a BAS or SX Tool.
6.
As the numeric output cannot be read at the DX front panel, it is recommended that this algorithm is used in the higher PM numbers, reserving the lower PM numbers for algorithms that can be displayed.
7.
Only one programmable module within a DX controller may be configured as Algorithm 14 or 15.
Source Points (Outputs)
PMnHLDm A 1 when the channel of the program module has been overridden (in hold) from an SX service module or a BAS. PMnNMHm A 1 when the psychrometric numeric module output is equal to or greater than the high limit of the channel. PMnNMLm A 1 when the psychrometric numeric module output is less than or equal to the low limit of the channel. Destination Points (Inputs)
HUMIDn@ The relative humidity sensor connections for psychrometric calculations. TEMPn@
118
The temperature sensor connections for psychrometric calculations.
Configuration Guides - DX-9100 Configuration Guide
Page 119
Algorithm 16 Line Segment
The Line Segment Algorithm output is a nonlinear function of the input variable I1 defined on an X,Y plane using up to 17 break points. This is typically used to linearize input from a nonlinear sensor, or for a complex reset schedule. Output Signal
Y2 Y0,1 Y3 Input Signal
Y4
X0
X1
X2
X3
X4 dxcon017
Figure 15: Line Segment Function Function
Via the GX Tool
Click on PM in the toolbar, select Numeric, then Segment, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. On pages 1 and 2, enter the X and Y coordinates as required. Make connections between the source point and destination point In@ of the line segment module. Via the SX Tool
This algorithm is assigned to a programmable function module when the value 16 is configured in PM Item PMnTYP (RI.00). I1@ = Input Variable Connection (RI.10) Break point 0: coordinates X0,Y0 X0 = RI.26, X1 = RI.28 ... X16 = RI.58 (evens) Y0 = RI.27, X1 = RI.29 ... Y16 = RI.59 (odds) Break point 16: coordinates X16,Y16 X0 = RI.26, X1 = RI.28 ... X16 = RI.58 (evens) Y0 = RI.27, X1 = RI.29 ... Y16 = RI.59 (odds)
Configuration Guides - DX-9100 Configuration Guide
119
Page 120
Notes
1.
On the SX Tool, the output of the algorithm can be seen under Program Modules at Alg. Item NCM (RI.60).
2.
Coordinates must be defined for the complete range of the input variable (x) so that the output can always be calculated. X values must be entered in ascending order and the same number may not be entered twice.
3.
A line segment module may be chained to the next programmable function module (in numerical sequence) by: GX Tool: Select the line segment module and then Data to call up the Data Window. Go to page 2. At the Chain (0=N) field, enter 1 if you need more than 17 break points. Define the next PM as a SEGMENT module where breakpoints X0, Y0 ... X16, Y16 will act as break points X17, Y17 ... X33, Y33 for the Analog Input in the first defined module. No analog input connection is required in the second module. SX Tool: Set bit X16 in the PM Item PMnOPT (RI.01) to 1. In this case, the next programmable function module must be defined as a line segment module where Break Point 0-16 will act a Break Points 17-33 for the input connected at I1@ in the first module. No connection at I1@ is required in the second module.
GX Labels
4.
The module can be put in Hold mode by entering the value 1 at PM Item PMnHDC (RI.70) bit X1. (This can only be done via the PLC or SX Tool.) Its numeric output (NCM) can be modified in the Hold mode by a BAS or SX Tool.
5.
As the numeric output cannot be read at the DX front panel, it is recommended that this algorithm is used in the higher PM numbers, reserving the lower PM numbers for algorithms that can be displayed.
Source Points (Outputs)
PMnHLD
A 1 when the program module is in the Hold mode, being overridden by the SX Tool or a BAS.
PMnNCM
The calculation result of a numeric module.
Destination Points (Inputs)
In@
120
Analog input connections to a programmable module.
Configuration Guides - DX-9100 Configuration Guide