For the Johnson Controls DX-9100
Page 101
If the input is not connected, the controller will use the default value 0 and the function is disabled such that the defined action in ACT1 or ACT2 is always used. Via the GX Tool
Make a connection between the source point and RA1@ in the destination control module. Via the SX Tool
Configure the software connection by entering the source address of the selected reverse action logic variable under Program Modules at Alg. Item RA@ (RI.16). Local Setpoint
Each of the two local setpoints is a value that represents the basic setpoint of the respective loop in the control module. It is a number that should be within the range of the process variable. The LSP1 and LSP2 are disabled when Remote mode is enabled. When a WSP1 or WSP2 is adjusted from the front panel, the respective LSP is changed according to the formula below: WSPn = RVn (RSPn + LSPn) + (bias)n n=1, 2
Via the GX Tool
Click on PM in the toolbar, select Control, then Dual On/Off and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Local SP #1 (LSP1) and Local SP #2 (LSP2) fields, enter setpoint values. Via the SX Tool
Enter a value for the selected local setpoints under Program Modules at Alg. Items LSP1 (RI.26) and LSP2 (RI.43). Action Modes
Each of the two action modes defines the action of the respective loop in the control module. A -1 will define a reverse acting control module; an increase of the process variable will cause the output to switch to Off (0). A +1 will define a direct acting control module; an increase of the process variable will cause the output to switch to On (1). ACT 1 will normally be -1 and ACT 2 will normally be +1 to define a heating/cooling controller.
Configuration Guides - DX-9100 Configuration Guide
101
Page 102
Via the GX Tool
Click on PM in the toolbar, select Control, then Dual On/Off and position the module (box) on the screen. Select the module and then Data to call up the Data Window. Go to the second page. At the Action #1 (ACT1) and Action #2 (ACT2) fields, enter a value. Via the SX Tool
Enter -1 or +1 for the selected Action mode under Program Modules at Alg. Items ACT1 (RI.27) and ACT2 (RI.44). Differential
Each of the two differential values is a number that defines the change in deviation value required to initiate Off transitions once outputs are On. Via the GX Tool
Click on PM in the toolbar, select Control, then Dual On/Off and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Diffrential #1 (DIF1) and Diffrntial #2 (DIF2) fields, enter the amount of change to cause an Off transition in units of the PV. Via the SX Tool
Enter a value for the selected differential under Program Modules at Alg. Items DIF1 (RI.2) or DIF2 (RI.45). Output
BOF1 BSB1 DIF1
BOF2 DIF2 BSB2
100%t
Process Variable
0%
Off
Off Standby Comfort
Standby Comfort dxcon016
Figure 14: Heating/Cooling On/Off Module Operation Deviation Alarm Values
102
The deviation alarm values define the value which, when exceeded by the difference between the process variable and the actual working setpoint, will automatically generate a deviation alarm.
Configuration Guides - DX-9100 Configuration Guide
Page 103
A low low deviation alarm indicates that the process variable is lower than the working setpoint of the respective loop by more than the low low deviation alarm value. Via the GX Tool
Click on PM in the toolbar, select Control, then Dual On/Off, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Dev LL Lmt #1 (DLL1) and Dev LL Lmt #2 (DLL2) fields, enter a value in units of PV. Via the SX Tool
The low low deviation alarm value for the respective loop can be entered under Program Modules at Alg. Item DLL1 (RI.41) and DLL2 (RI.58). A low deviation alarm indicates that the process variable is lower than the working setpoint of the respective loop by more than the low deviation alarm value. Via the GX Tool
Click on PM in the toolbar, select Control, then Dual On/Off, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Dev Low Lmt #1 (DL1) and Dev Low Lmt #2 (DL2) fields, enter a value in units of PV. Via the SX Tool
The low deviation alarm value for the respective loop can be entered under Program Modules at Alg. Item DL1 (RI.40) and DL2 (RI.57). A high deviation alarm indicates that the process variable exceeds the working setpoint of the respective loop by more than the high deviation alarm value. Via the GX Tool
Click on PM in the toolbar, select Control, then Dual On/Off and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Dev H Lmt #1 (DH1) and Dev H Lmt #2 (DH2) fields, enter a value in units of PV. Via the SX Tool
The high deviation alarm value for the respective loop can be entered under Program Modules at Alg. Item DH1 (RI.39) and DH2 (RI.56). A high high deviation alarm indicates that the process variable exceeds the working setpoint of the respective loop by more than the high high deviation alarm value. Configuration Guides - DX-9100 Configuration Guide
103
Page 104
Via the GX Tool
Click on PM in the toolbar, select Control, then Dual On/Off and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Dev HH Lmt #1 (DHH1) and Dev HH Lmt #2 (DHH2) fields, enter a value in units of PV. Via the SX Tool
The high high deviation alarm value for the respective loop can be entered under Program Modules at Alg. Item DHH1 (RI.38) and DHH2 (RI.55). Note: Deviation alarms do not affect the control program operation unless the associated logic variables are used in other programmable modules. Deviation alarms do not light the LED on the DX front panel. Notes
1.
The WSP1, WSP2, PV, OCM, ACT1, DIF1, BOF1, BSB1, ACT2, DIF2, BOF2, and BSB2 can be read and modified from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.
2.
With the SX Tool, the various outputs of the control algorithm can be seen under Program Modules at Alg. Items WSP1 (RI.61), WSP2 (RI.62), PV (RI.63), RSP (RI.66), and RV (RI.67).
3.
The output of the control algorithm can be seen under Program Modules at PM Item PMnDO (RI.71). OCM represents the output of the active loop. OCM1 and OCM2, which are only available from Version 1.1 and later, represent the outputs of Loops 1 and 2, respectively: OCM
= bit X1
OCM1 = bit X2 OCM2 = bit X3
104
Configuration Guides - DX-9100 Configuration Guide
Page 105
4.
The logic status of the control algorithm can be seen at PM Item PMnST (RI.72) with following bit structure: X1 = 1
CML
Controller Output at 0
X2 = 1
CMH
Controller Output at 1
X5 = 1
LLDA
Low Low Deviation Alarm
X6 = 1
LDA
Low Deviation Alarm
X7 = 1
HDA
High Deviation Alarm
X8 = 1
HHDA
High High Deviation Alarm
X9 = 1
SOF
Shutoff Mode Active
X10= 1
STA
Startup Mode Active
X11= 1
EF
External Forcing Active
X12= 1
OF
Off Mode Active
X13= 1
SB
Standby Mode Active
X14= 1
RA
Reverse Action Mode
X15= 0
HEAT
Cooling (Loop 2 active)
X15= 1
HEAT
Heating (Loop 1 active)
Status Items can be used as logic (digital) connections using the GX Tool or SX Tool. GX Labels
Source Points (Outputs)
PMnCMH
A 1 when a control module’s output is equal to its output high limit. PMnCML A 1 when a control module’s output is equal to its output low limit. PMnCMP A 1 when the control module’s WSP is being overridden by a BAS (Computer mode). PMnEF A 1 when this control module is being externally forced. PMnHDA A 1 when the difference PV - WSP is larger than the high deviation alarm value. PMnHHDA A 1 when the difference PV - WSP is larger than the high high deviation alarm value. PMnHLD A 1 when the program module is in the Hold mode, being overridden by the SX Tool or a BAS. PMnLDA A 1 when the difference WSP - PV is larger than the low deviation alarm value. PMnLLDA A 1 when the difference WSP - PV is larger than the low low deviation alarm value.
Configuration Guides - DX-9100 Configuration Guide
105
Page 106
PMnLSP1
The value of the local setpoint of Loop 1 of a dual control module. (This value is directly changed when adjusting the WSP1 from the DX front panel.)
PMnLSP2
The value of the local setpoint of Loop 2 of a dual control module. (This value is changed when adjusting the WSP2 from the DX front panel.)
PMnOCM
The value of the dual On/Off control module output; either a 1 or 0
PMnOCM1 The value of the Loop 1 output in a dual On/Off control module; either a 1 or 0 PMnOCM2 The value of the Loop 2 output in a dual On/Off control module; either a 1 or 0 PMnSOF
A 1 when this control module is in the Shutoff mode, which occurs when enable shutoff = 1 and the BAS has commanded it On.
PMnSTA
A 1 when this control module is in the Startup mode, which occurs when enable startup = 1 and the BAS has commanded it On.
PMnWSP1
The value of the working setpoint of Loop 1 of a dual control module.
PMnWSP2
The value of the working setpoint of Loop 2 of a dual control module.
Destination Points (Inputs)
106
EF@
The connection to the external forcing point of control modules.
MNWS@
The connection to the minimum working setpoint of a control module. The WSP cannot be adjusted below this value.
MXWS@
The connection to the maximum working setpoint of a control module. The WSP cannot be adjusted above this value.
OF@
The connection to the off-mode source point of a control module.
PV@
The connection to the process variable of a control module.
RA@
The connection to the reverse action point of a control module.
RS1@
The connection for Loop 1 of a dual control module remote setpoint.
Configuration Guides - DX-9100 Configuration Guide
Page 107
RS2@
The connection for Loop 2 of a dual control module remote setpoint.
RV1@
The connection for Loop 1 of a dual control module reference variable.
RV2@
The connection for Loop 2 of a dual control module reference variable.
SB@
The connection to the standby source point of a control module.
Numerical Calculation and Other Function Module Configurations
Each of the twelve programmable function modules can be defined as a numerical calculation module or other type of control module, capable of executing a mathematical or control algorithm.
Algorithm 11 Average
The average algorithm calculates the arithmetic average of up to eight connected inputs. If one of the inputs is not connected, the calculation module will assume a value of 1 for the corresponding variable.
Each module can accept numeric and logic variable inputs and each module provides a numeric and/or logic output that can be connected to either a programmable function module or output module.
Each input may be weighted with a constant K. (I1*K1 + I2*K2 + .... + I8*K8) K0 In@
= Input Variable Connection n = 1-8
Kn
= Constant n = 0-8
Note: If K0 = 0, the average module will not update its output. Function
Via the GX Tool
Click on PM in the toolbar, select Numeric, then Average and position the module (box) on the screen. Make connections between source points and destination points In@, as applicable. Select the module (box) on screen and then Data to call up the Data Window. Under numbers 0 through 8, enter appropriate values to complete the calculation.
Configuration Guides - DX-9100 Configuration Guide
107
Page 108
Via the SX Tool
An Average Calculation Algorithm of a DX-9100 Controller is assigned to a programmable function module when the value 11 is configured, under Program Modules, in PM Item PMnTYP (RI.00). To connect to the Input Variable Connection, enter the source addresses at Alg. Item In@, (RI.10 - RI.17). Enter the values for the constants at Alg. Item Kn, (RI.26 - RI.34). High/Low Limits
The output of the module is limited by the high and low limits. Use these limits to keep the output within a reasonable range in case of the failure of an input. Via the GX Tool
Select the average module on screen and then Data to call up the Data Window. Enter a value at the High Limit and Low Limit fields. If the calculation > high limit, then NCM = high limit If the calculation < low limit, then NCM = low limit Via the SX Tool
The low limit value is entered under Program Modules at Alg. Item LOL (RI.37) and the high limit at Alg. Item HIL (RI.36). Notes
1. On the SX Tool, the output of the algorithm can be seen under Program Modules at Alg. Item NCM (RI.60). 2. The logical status of the algorithm can be seen on the SX Tool under Program Modules at PM Item PMnST (RI.72), with the following bit structure: X1 = 1
NML
Calculated Output is at Low Limit
X2 = 1
NMH
Calculated Output is at High Limit
3.
The module can be put in Hold mode by entering the value 1 in Alg. Item HLD (RI.70) bit X1. (This can only be done via the PLC or SX Tool.) Its numeric output (NCM) can be modified in the Hold mode by a BAS or SX Tool.
4.
As the numeric output cannot be read at the DX front panel, it is recommended that this algorithm is used in the higher PM numbers, reserving the lower PM numbers for algorithms that can be displayed.
Status Items can be used as logic (digital) connections using the GX Tool or SX Tool.
108
Configuration Guides - DX-9100 Configuration Guide
Page 109
GX Labels
Source Points (Outputs)
PMnHLD
A 1 when the program module is in the Hold mode, being overridden by the SX Tool or a BAS.
PMnNCM
The calculation result of a numeric module.
PMnNMH
A 1 when the calculated output is equal to or greater than the numeric module high limit.
PMnNML
A 1 when the calculated output is less than or equal to the numeric module low limit.
Destination Points (Inputs)
In@ Algorithm 12 Minimum Select
Analog input connections to a programmable module.
The Minimum Select algorithm selects the minimum value of up to eight input variables. Each input may be weighted with a constant K. If an input is not connected, the corresponding variable is automatically excluded from the calculation. If one of the inputs is required to be a constant, connect an analog constant (ACO). K0 + MIN. (I1*K1, I2*K2, ... , I8*K8)
Function
In@= Input Variable Connection n = 1-8
Kn = Constant n = 0-8
Via the GX Tool
Click on PM in the toolbar, select Numeric, then Minimum and position the module (box) on the screen. Make connections between source points and destination points In@ as applicable. Select the module (box) on screen and then Data to call up the Data Window. Under numbers 0 through 8, enter appropriate values to complete the calculation. Via the SX Tool
This algorithm is assigned to a programmable function module when the value 12 is configured in PM Item PMnTYP (RI.00). To connect to the Input Variable Connection, enter the source addresses at Alg. Item In@, (RI.10 - RI.17). Enter the values for constants at Alg. Item Kn, (RI.26-RI.34). High/Low Limits
The output of the module is limited by the high and low limits. Use these limits to keep the output within a reasonable range in case of the failure of an input. Configuration Guides - DX-9100 Configuration Guide
109
Page 110
Via the GX Tool
Select the minimum module on screen and then Data to call up the Data Window. Then enter the appropriate values in the High Limit and Low Limit fields. If the calculation > high limit, then NCM = high limit If the calculation < low limit, then NCM = low limit Via the SX Tool
The low limit value is entered under Program Modules at Alg. Item LOL (RI.37) and the high limit at Alg. Item HIL (RI.36). Notes
GX Labels
1.
On the SX Tool, the output of the algorithm can be seen under Program Modules at Alg. Item NCM (RI.60).
2.
The logical status of the algorithm can be seen under Program Modules on the SX Tool at PM Item PMnST (RI.72) with following bit structure: X1 = 1
NML Calculated Output is at Low Limit
X2 = 1
NMH Calculated Output is at High Limit
3.
The module can be put in Hold mode by entering the value 1 in PM Item PMnHDC (RI.70) at bit X1. (This can only be done via the PLC or SX Tool.) Its numeric output (NCM) can be modified in the Hold mode by a BAS or SX Tool.
4.
As the minimum select output cannot be read at the DX front panel, it is recommended that this algorithm is used in the higher PM numbers, reserving the lower PM numbers for algorithms that can be displayed.
Source Points (Outputs)
PMnHLD
A 1 when the program module is in the Hold mode, being overridden by the SX Tool or a BAS.
PMnNCM
The calculation result of a numeric module.
PMnNMH
A 1 when the calculated output is equal to or greater than the numeric module high limit.
PMnNML
A 1 when the calculated output is less than or equal to the numeric module low limit.
Destination Points (Inputs)
In@
110
Analog input connections to a programmable module.