Page 91

Rate Actions

Each of the two rate actions defines the derivative action decay time value and is entered in minutes, between 0 and 5. Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Rate Action #1 (TD1) and Rate Action #2 (TD2) fields, enter a value. Via the SX Tool

Enter a value for the selected rate actions under Program Modules at Alg. Items TD1 (RI.29) or TD2 (RI.46). Output High Limits

Each of the two high limits is a percent of the output, which defines a high limit value for the control module output in the respective loop. The default value is 100 for each limit, and must always be higher than the low limit. Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Out H Lmt #1 (HIL1) and Out H Lmt #2 (HIL2) fields, enter a value. Via the SX Tool

Enter a value for the selected high limit under Program Modules at Alg. Items HIL1 (RI.36) and HIL2 (RI.53). Output Low Limits

Each of the two low limits is a percent of the output, which defines a low limit value for the control module output in the respective loop. The default value is 0 for each limit, and must always be lower than the high limit. The low limits are overridden when the control module is in Off mode and the output falls to 0. Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Out L Lmt #1 (LOL1) and Out L Lmt #2 (LOL2) fields, enter a value. Via the SX Tool

Enter a value for the selected low limit under Program Modules at Alg. Items LOL1 (RI.37) and LOL2 (RI.54).

Configuration Guides - DX-9100 Configuration Guide

91

Page 92

BOF2

BOF1 BSB1

Output 100 % HIL2 HIL1

PB1

PB2

BSB2

Process Variable

LOL1 LOL2 0% Off Standby Comfort

Off Standby Comfort dxcon015

Figure 13: Heating/Cooling Module Operation Deviation Alarm Values

The deviation alarm values define the value which, when exceeded by the difference between the process variable and the actual working setpoint, will automatically generate a deviation alarm. A low low deviation alarm indicates that the process variable is lower than the working setpoint of the respective loop by more than the low low deviation alarm value. Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev LL Lmt #1 (DLL1) and Dev LL Lmt #2 (DLL2) fields, enter a value in units of PV. Via the SX Tool

The low low deviation alarm value for the respective loop can be entered under Program Modules at Alg. Item DLL1 (RI.41) and DLL2 (RI.58). A low deviation alarm indicates that the process variable is lower than the working setpoint of the respective loop by more than the low deviation alarm value. Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev L Lmt #1 (DL1) and Dev L Lmt #2 (DL2) fields, enter a value in units of PV.

92

Configuration Guides - DX-9100 Configuration Guide

Page 93

Via the SX Tool

The low deviation alarm value for the respective loop can be entered under Program Modules at Alg. Item DL1 (RI.40) and DL2 (RI.57). A high deviation alarm indicates that the process variable exceeds the working setpoint of the respective loop by more than the high deviation alarm value. Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev H Lmt #1 (DH1) and Dev H Lmt #2 (DH2) fields, enter a value in units of PV. Via the SX Tool

The high deviation alarm value for the respective loop can be entered under Program Modules at Alg. Item DH1 (RI.39) and DH2 (RI.56). A high high deviation alarm indicates that the process variable exceeds the working setpoint of the respective loop by more than the high high deviation alarm value. Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev HH Lmt #1 (DHH1) and Dev HH Lmt #2 (DHH2) fields, enter a value in units of PV. Via the SX Tool

The high high deviation alarm value for the respective loop can be entered under Program Modules at Alg. Item DHH1 (RI.38) and DHH2 (RI.55). Note: Except for the PID to P changeover described below, deviation alarms do not affect the control program operation unless the associated logic variables are used in other programmable modules. Deviation alarms do not light the LED on the DX front panel. Enable PID to P

If a PID control loop has a high high or low low deviation alarm, it will operate as a proportional only loop when the PID to P feature is enabled. (Refer to Figure 9.)

Configuration Guides - DX-9100 Configuration Guide

93

Page 94

Via the GX Tool

Select DUAL PID. Then select Data in the module menu. At the Ena PID to P: 0=N field, enter 1 to enable PID to P transition, or 0 to disable this feature. Via the SX Tool

This feature is enabled when Alg. Item PIDP (RI.01) bit X7 is set to 1 under Program Modules. Error Deadband

The error deadband is expressed in percent of the active proportional band PB1 or PB2. When the process error (PV-WSP) is within this deadband, the integral term is frozen. The deadband is applied above and below setpoint and in the units of the PV is equal to: (EDB/100) * (PB/100) * Range of the PV (AIn) or (EDB/100) * (PB/100) * 100 (all other numeric values) Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Err Dd Bnd #1 (EDB1) and Err Dd Bnd #2 (EDB2) fields, enter a value in percent of PB. Via the SX Tool

The error deadbands are entered under Program Modules at Alg. Items EDB1 (RI.33) and EDB2 (RI.49). Enable Zero Output Changeover

When this option is enabled, the changeover from one loop to another will only take place when the output of the active loop is at its low limit. This feature is used when the control loops have integral or derivative action and the process variable can change very quickly. It prevents a loop becoming inactive when its output is above the low limit value due to the integral or derivative term. When this option is not enabled, the output of the loop will go to its low limit when the loop becomes inactive, and when the loop becomes active again, the output will immediately return to the value at the time of the previous changeover. This may cause unnecessary instability. When a long integral time is configured, the effect of enabling this option will be to slow down the changeover from heating to cooling or vice-versa when the process variable changes rapidly. The changeover cannot occur until the integral and derivative terms have decayed such that the output is at the low limit value. This feature is available with x.3 controllers or later.

94

Configuration Guides - DX-9100 Configuration Guide

Page 95

Via the GX Tool

Select the module and then Data to call up the Data Window. At the Ena zero c/o: 0=N field, enter a 1 to enable this function. Via the SX Tool

This parameter is defined under Program Module at PM Item PMnOPT (RI.01) in a DUAL PID module as follows: X10 = 1 EZCO Enable Zero Output Changeover Notes

1.

The WSP1, WSP2, PB1, PB2, OCM, PV, TI1, TI2, TD1, TD2, BOF1, BOF2, BSB1, and BSB2 can be read and modified from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

2.

With the SX Tool, the various outputs of the control algorithm can be seen at Alg. Items OCM (RI.60), WSP1 (RI.61), WSP2 (RI.62), PV (RI.63), RSP (RI.66), RV (RI.67), OCM1 (RI.68), and OCM2 (RI.69).

3.

OCM represents the output of the active loop. OCM1 and OCM2, which are only available for Version 1.1 and later, represent the outputs of Loops 1 and 2, respectively.

Configuration Guides - DX-9100 Configuration Guide

95

Page 96

4.

The logic status of the control algorithm can be seen at PM Item PMnST (RI.72), with following bit structure: X1 = 1

CML

Controller Output at Low Limit

X2 = 1

CMH

Controller Output at High Limit

X3 = 1

FORC

Force-back to OCM from AO is active. FORC is set when the connected AO (analog output) is in Hold mode. The value of the AO is also forced back, or set into the OCM, to provide bumpless override control for a PID module with an integral action. Force-back is not active when the AO is connected to OCM1 or OCM2.

X5 = 1

LLDA

Low Low Deviation Alarm

X6 = 1

LDA

Low Deviation Alarm

X7 = 1

HDA

High Deviation Alarm

X8 = 1

HHDA

High High Deviation Alarm

X9 = 1

SOF

Shutoff Mode Active

X10= 1

STA

Startup Mode Active

X11= 1

EF

External Forcing Active

X12= 1

OF

Off Mode Active

X13= 1

SB

Standby Mode Active

X14= 1

RA

Reverse Action Mode

X15= 0

HEAT

Cooling (Loop 2 active) (PV above WSP2)

X15= 1

HEAT

Heating (Loop 1 active) (PV below WSP1)

Status Items can be used as logic (digital) connections using the GX Tool or SX Tool. GX Labels

96

Source Points (Outputs)

PMnCMH

A 1 when a control module’s output is equal to its output high limit.

PMnCML

A 1 when a control module’s output is equal to its output low limit.

PMnCMP

A 1 when the control module’s WSP is being overridden by a BAS (Computer mode).

PMnEF

A 1 when this control module is being externally forced.

Configuration Guides - DX-9100 Configuration Guide

Page 97

PMnHEAT

A 1 when, in a symmetric control module, the PV is below the center of the symmetry band, and a 0 when above center; or a 1 when, in a dual control module, Loop 1 is active.

PMnHDA

A 1 when the difference PV - WSP is larger than the high deviation alarm value.

PMnHHDA A 1 when the difference PV - WSP is larger than the high high deviation alarm value. PMnHLD

A 1 when the program module is in the Hold mode, being overridden by the SX Tool or a BAS.

PMnLDA A 1 when the difference WSP - PV is larger than the low deviation alarm value. PMnLLDA

A 1 when the difference WSP - PV is larger than the low low deviation alarm value.

PMnLSP1

The value of the local setpoint of Loop 1 of a dual control module. (This value is directly changed when adjusting the WSP1 from the DX front panel.)

PMnLSP2

The value of the local setpoint of Loop 2 of a dual control module. (This value is changed when adjusting the WSP2 from the DX front panel.)

PMnMNWS The value of the minimum working setpoint allowed for a control module. PMnMXWS The value of the maximum working setpoint allowed for a control module. PMnOCM

The value of the dual PID control module output in percent.

PMnOCM1 The value of the Loop 1 output in a dual PID control module in percent. PMnOCM2 The value of the Loop 2 output in a dual PID control module in percent. PMnSOF

A 1 when this control module is in the Shutoff mode, which occurs when enable shutoff = 1 and the BAS has commanded it On.

PMnSTA

A 1 when this control module is in the Startup mode, which occurs when enable startup = 1 and the BAS has commanded it On.

PMnWSP1

The value of the working setpoint of Loop 1 of a dual control module.

PMnWSP2

The value of the working setpoint of Loop 2 of a dual control module. Configuration Guides - DX-9100 Configuration Guide

97

Page 98

Destination Points (Inputs)

Algorithm 04 Heating/ Cooling On/Off Control Module (Dual On/Off)

EF@

The connection to the external forcing point of control modules.

MNWS@

The connection to the minimum working setpoint of a control module. The WSP cannot be adjusted below this value.

MXWS@

The connection to the maximum working setpoint of a control module. The WSP cannot be adjusted above this value.

OB1@

The connection for Loop 1 of a dual PID output bias.

OB2@

The connection for Loop 2 of a dual PID output bias.

OF@

The connection to the off-mode source point of a control module.

PB@

The connection to proportional band, which replaces the value PB if there is a connection.

PV@

The connection to the process variable of a control module.

RA@

The connection to the reverse action point of a control module.

RS1@

The connection for Loop 1 of a dual control module remote setpoint.

RS2@

The connection for Loop 2 of a dual control module remote setpoint.

RV1@

The connection for Loop 1 of a dual control module reference variable.

RV2@

The connection for Loop 2 of a dual control module reference variable.

SB@

The connection to the standby source point of a control module.

The heating/cooling On/Off algorithm has two On/Off Control loops that share the same process variable and control output, and have one set of status variables, but have two different sets of tuning parameters. In Version 1.1 or later, two independent control outputs are also provided, one for each loop. Only one of the two loops will be active, depending on the control status: PV < = WSP1

Loop 1 is active.

PV > = WSP2

Loop 2 is active.

Abs (PV - WSP1) < = Abs (PV - WSP2)

Loop 1 is active.

Note: WSP2 must always be greater than WSP1. 98

Configuration Guides - DX-9100 Configuration Guide

Page 99

Setting Supervisory Control Options

The options are series of parameters that define how the On/Off Control Module operates and reacts to BAS commands. Via the GX Tool

Click on PM in the toolbar, select Control, then Dual On/Off and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Ena Shutoff: 0=N field, enter a 1 to enable this function. At the Shutoff Out Level field, enter 0 for Off and 1 for On. It will go to the specified state if Shutoff is enabled and the BAS has set Shutoff in the controller. At the Ena Startup: 0=N field, enter a 1 to enable the function. At the Startup Out Level field, enter 0 for Off and 1 for On. It will go to the specified state if Startup is enabled and the BAS has set Startup in the controller. Via the SX Tool

These parameters are defined under Item PMnOPT (RI.01) of the D On/Off module, with the following bit structure: X1 = 1 SOFE Enable Shutoff mode from Supervisory System X2 SOFL

0=0, 1=1 Shutoff out level

X3 = 1 STAE Enable Startup mode from Supervisory System X4 STAL Process Variable Connection PV@

0=0, 1=1 Startup out level

The Process Variable (PV) is an analog value connection to the control module. When the process variable is not equal to the setpoint, the controller responds by changing its output value in accordance with the On/Off parameters. Via the GX Tool

Make a connection between the source point and PV@ in the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected process variable under Program Modules at Item PV@ (RI.10) in the defined D On/Off module.

Configuration Guides - DX-9100 Configuration Guide

99

Page 100

Remote Setpoint Connections RS1@, RS2@

Each of the two remote setpoints (RSP1, RSP2) is an analog variable to the control module, in units of the PV, which produces a bias in the respective local setpoint. If the input is not connected, the controller will use the default value 0. WSPn = RVn (RSPn + LSPn) + (bias)n n = 1, 2

Via the GX Tool

Make a connection between the source point and RS1@ in the destination control module. Make a connection between the source point and RS2@ destination point. Via the SX Tool

Configure the software connection by entering the source addresses of the selected remote setpoint under Program Modules at Alg. Items RS1@ (RI.11) and RS2@ (RI.18). Reference Variable Connection RV1@, RV2@

Each of the two reference variables (RV1, RV2) is an analog input to the control module, which causes the respective loop in the control module to perform as a ratio controller. Its effect is a multiplier in the working setpoint calculation. If the input is not connected, the controller will use the default value 1. WSPn = RVn (RSPn + LSPn) + (bias)n n = 1, 2

Via the GX Tool

Make a connection between the source point and RV1@ in the destination control module. Make a connection between the source point and RV2@ destination point. Via the SX Tool

Configure the software connection by entering the source addresses of the selected reference variable under Program Modules at Alg. Items RV1@ (RI.12) and RV2@ (RI.19). Reverse Action Connection RA@

! CAUTION: The reverse action connection is a logic input to the control module which changes the action of both controllers from direct to reverse or vice versa. Extreme caution is advised with this connection when setpoint biases are also being used as the sign of the biases is not reversed. For correct controller operation, WSP2 must always be greater than WSP1.

100