DX-9100 Configuration Guide: Software Configuration, pages 81 to 90

Pages 81 to 90 of 288, from DX-9100 Configuration Guide

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Johnson Controls DX-9100

Page 81

Differential

The differential or DIF is a number that defines the change in process variable required to initiate Off transitions once the output is On. It is used to eliminate short-cycling. Via the GX Tool

Select On/Off. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Differential (DIF) field, enter the amount of change to cause an Off transition in the units of the PV. Via the SX Tool

Configure the software by entering a value for the selected differential logic variable at Alg. Item DIF (RI.28) in the On/Off module. PV OCM = 0

WSP DIF

WSP

OCM = 1

DIF

OCM = 1 PV

OCM = 0 dxcon012

Figure 11: Reverse Acting Controller/Direct Acting Controller Deviation Alarm Values

The deviation alarm values define the value which, when exceeded by the difference between the process variable and the working setpoint, will automatically generate a deviation alarm. A low low deviation alarm indicates that the process variable is lower than the working setpoint by more than the low low deviation alarm value. Via the GX Tool

Select On/Off. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev L. L. Limit (DLL) field, enter a value in units of PV. Via the SX Tool

Enter the low low deviation alarm value at Alg. Item DLL (RI.41). A low low deviation alarm indicates that the process variable is lower than the working setpoint by more than the low deviation alarm value.

Configuration Guides - DX-9100 Configuration Guide

81

Page 82

Via the GX Tool

Select On/Off. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev Low Limit (DL) field, enter a value in units of PV. Via the SX Tool

Enter the low deviation alarm value at Alg. Item DL (RI.40). A high deviation alarm indicates that the process variable exceeds the working setpoint by more than the high deviation alarm value. Via the GX Tool

Select On/Off. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev High Limit (DH) field, enter a value in units of PV. Via the SX Tool

Enter the high deviation alarm value at Alg. Item DH (RI.39). A high high deviation alarm indicates that the process variable exceeds the working setpoint by more than the high deviation alarm value. Via the GX Tool

Select On/Off. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev H. H. Limit (DHH) field, enter a value in units of PV. Via the SX Tool

Enter the high high deviation alarm value at Alg. Item DHH (RI.38). Note: Deviation alarms do not affect the control program operation unless the associated logic variables are used in other programmable modules. Deviation alarms do not light the LED on the DX front panel. Symmetrical Transfer Function

The control algorithm may be configured to operate as an On/Off controller with a symmetrical transfer function, where the comfort cooling setpoint is calculated by adding a constant symmetry band to the comfort heating setpoint and the control module action is reversed. When the control module is in Standby or Off mode, there is a shift of the setpoints, as shown in the Figure 12. When the controller is configured as direct action (ACT = +1) the output is at 1 within the symmetry band (SBC).

82

Configuration Guides - DX-9100 Configuration Guide

Page 83

Output

BOF BSB

DIF

DIF

BOF BSB

100 %

Process Variable

0%

Off

Off

SBC Standby Comfort

Standby Comfort dxcon014

Figure 12: On/Off Controller with Symmetric Operation (ACT = -1) Via the GX Tool

Select On/Off. Then select Data in the module menu. At the Ena Symm mode 0=N field, enter 1 to enable or 0 to disable this function. If enabled, select Data-2 to go to page 2. At the Symmetry Band (SBC) field, enter a value to add to the setpoint to determine the cooling setpoint. Via the SX Tool

This symmetric operation is enabled at bit X5, PM Type PMnOPT (RI.01) in the On/Off module. The symmetry band is entered at Alg. Item SBC (RI.32). Notes

1.

The WSP, output, biases, and action mode values can be read and modified from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

2.

With the SX Tool, the active values of the control algorithm can be seen at Alg. Items WSP (RI.61), PV (RI.62), RSP (RI.66), and RV (RI.67).

3.

The output of the control algorithm can be seen at PM Item PMnDO (RI.71) bit X1 (Alg. Item OCM).

Configuration Guides - DX-9100 Configuration Guide

83

Page 84

4.

The logic status of the control algorithm can be seen at PM Item PMnST (RI.72), with the following bit structure: X1 = 1

CML

Controller Output at 0

X2 = 1

CMH

Controller Output at 1

X5 = 1

LLDA

Low Low Deviation Alarm

X6 = 1

LDA

Low Deviation Alarm

X7 = 1

HDA

High Deviation Alarm

X8 = 1

HHDA High High Deviation Alarm

X9 = 1

SOF

Shutoff Mode Active

X10= 1

STA

Startup Mode Active

X11= 1

EF

External Forcing Active

X12= 1

OF

Off Mode Active

X13= 1

SB

Standby Mode Active

X14= 1

RA

Reverse Action Mode

X15 = 0

HEAT

(Cooling Controller or PV above center of SBC in Symmetric Operation)

X15 = 1

HEAT

(Heating Controller or PV below center of SBC in Symmetric Operation)

Status Items can be used as logic (digital) connections using the GX Tool or SX Tool. GX Labels

Source Points (Outputs)

PMnCMH

A 1 when a control module’s output is equal to its output high limit.

PMnCML

A 1 when a control module’s output is equal to its output low limit.

PMnCMP

A 1 when the control module’s WSP is being overridden by a BAS (Computer mode).

PMnEF

A 1 when this control module is being externally forced.

PMnHDA

A 1 when the difference PV - WSP is larger than the high deviation alarm value.

PMnHEAT

A 1 when, in a symmetric control module, the PV is below the center of the symmetry band, and a 0 when above center; or a 1 when, in a dual control module, Loop 1 is active.

PMnHHDA A 1 when the difference PV - WSP is larger than the high high deviation alarm value. 84

Configuration Guides - DX-9100 Configuration Guide

Page 85

PMnHLD

A 1 when the program module is in the Hold mode, being overridden by the SX Tool or a BAS.

PMnLDA

A 1 when the difference WSP - PV is larger than the low deviation alarm value.

PMnLLDA

A 1 when the difference WSP - PV is larger than the low low deviation alarm value.

PMnLSP

The value of the local setpoint. (This value is changed when adjusting the WSP from the DX front panel.)

PMnOCM

The value of the PID control module output in percent, either a 1 or 0 for an On/Off control module.

PMnSOF

A 1 when this control module is in the Shutoff mode, which occurs when enable shutoff = 1 and the BAS has commanded it On.

PMnSTA

A 1 when this control module is in the Startup mode, which occurs when enable startup = 1 and the BAS has commanded it On.

PMnWSP

The value of a control module working setpoint.

Destination Points (Inputs)

EF@

The connection to the external forcing point of control modules.

MNWS@

The connection to the minimum working setpoint of a control module. The WSP cannot be adjusted below this value.

MXWS@

The connection to the maximum working setpoint of a control module. The WSP cannot be adjusted above this value.

OF@

The connection to the off-mode source point of a control module.

PV@

The connection to the process variable of a PID or an On/Off.

RA@

The connection to the reverse action point of a control module.

RS@

The connection to a remote setpoint, which is used in the calculation for the working setpoint.

RV@

The connection to reference variable, which is a multiplier in the calculation for the working setpoint.

SB@

The connection to the standby source point of a control module. Configuration Guides - DX-9100 Configuration Guide

85

Page 86

Algorithm 03 Heating/Cooling PID Control Module (Dual PID)

The heating/cooling PID Control Module algorithm has two PID control loops, which share the same process variable and control output, and have one set of status variables, but have two different sets of tuning parameters. In Version 1.1 or later, two independent control outputs are also provided, one for each loop. Only one of the two loops will be active, depending on the control status: PV < WSP1

Loop 1 is active.

PV > WSP2

Loop 2 is active.

Abs(PV - WSP1)

<= Abs(PV - WSP2)

Loop 1 is active.

Note: WSP2 must always be greater than WSP1. Abs stands for absolute. Setting Supervisory Options

The options are a series of parameters that define how the PID Control Module operates and reacts to BAS commands. Via the GX Tool

Click on PM in the toolbar, select Control, then Dual PID, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Ena Shutoff: 0=N field, enter a 1 to enable this function. At the Shutoff Out Level field, enter a value for the output to go to if Shutoff is enabled and the BAS has set Shutoff in the controller. At the Ena Startup: 0=N field, enter a 1 to enable the function. At the Startup Out Level field, enter a value for the output to go to if Startup is enabled and the BAS has set Startup in the controller. At the Ena Off Trans: 0=N field, enter a 1 so the module will operate in Off mode if the BAS has set Shutoff and the process variable is below the Off mode WSP. This is only used in a reverse acting loop (negative proportional band) for heating applications for low temperature protection. Via the SX Tool

These parameters are defined under Program Module at PM Item PMnOPT (RI.01) in the DUAL PID module, with the following bit structure:

86

X1 = 1 SOFE

Enable Shutoff Mode from BAS

X3 = 1 STAE

Enable Startup Mode from BAS

X9 = 1 SOTO

Enable Shutoff to Off change

Configuration Guides - DX-9100 Configuration Guide

Page 87

Process Variable PV@

The Process Variable (PV) is an analog value connection to the control module. When the process variable is not equal to the setpoint, the controller responds by changing its output value in accordance with the PID parameters. Via the GX Tool

Make a connection between the source point and PV@ in the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected process variable under Program Modules at Alg. Item PV@ (RI.10) in the defined DUAL PID module. Remote Setpoint RS1@, RS2@

Each of the two remote setpoints (RSP1, RSP2) is an analog variable in the control module, in units of PV, which produces a bias in the respective local setpoint. If the input is not connected, the controller will use the default value 0. WSPn = RVn (RSPn + LSPn) + (bias)n n = 1, 2

Via the GX Tool

Make a connection between the source point and RS1@ in the destination control module. Make a connection between the source point and RS2@ in the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected remote setpoints under Program Modules at Alg. Items RS1@ (RI.11) and RS2@ (RI.18) in the defined DUAL PID module. Reference Variables RV1@, RV2@

Each of the two reference variables (RV1, RV2) is an analog input to the control module, which causes the respective loop in the control module to perform as a ratio controller. Its effect is a multiplier in the working setpoint calculation. If the input is not connected, the controller will use the default value 1. WSPn = RVn (RSPn + LSPn) + (bias)n n = 1, 2

Via the GX Tool

Make a connection between the source point and RV1@ in the destination control module. Make a connection between the source point and RV2@ in the destination control module. Configuration Guides - DX-9100 Configuration Guide

87

Page 88

Via the SX Tool

Configure the software connection by entering the source address of the selected reference variables under Program Modules at Alg. Item RV1@ (RI.12) and RV2@ (RI.19) in the defined DUAL PID module. Proportional Band

The proportional band is a number that defines the action and sensitivity of the control module. A negative number defines a reverse acting control module; an increase of the process variable produces a decrease in the output signal. A positive number defines a direct acting control module; an increase of the process variable produces an increase in the output signal. The number itself is an analog input connection (PB@) or value (PB1 or PB2) that is expressed in percent of the process variable range. When the process variable is one of the eight analog inputs to the DX-9100 Controller, the PV range is the range of the analog input. Otherwise, the range defaults to 0-100 (including all XP analog inputs). The connection is used for an application requiring a dynamic proportional band and if this input is not connected, the controller will use the proportional band value of PB1 or PB2. The number itself defines the percentage of the process variable range change that will produce a full output signal change. For example, if the process variable has a control range of 0 to 100, a proportional band of 2% indicates that a change of 2 in the process variable will cause the control module output signal to change by 100%. If the process variable range is 0-40, a proportional band of 10% indicates that a change of 4 in the process variable will cause the control module output signal to change by 100%. Via the GX Tool

Make a connection between the source point and PB1@ in the destination control module. Make a connection between the source point and PB2@ in the destination control module. Alternately, select the defined Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Proport. Band (PB1) and Proport. Band (PB2) fields, enter the required values. Via the SX Tool

Under Program Modules, select the DUAL PID module. The software connection is configured by entering the source addresses of the selected proportional band at Alg. Items PB1 (RI.27) and PB2 (RI.44); or, enter a value for the proportional bands at the PB Items (RI.27, RI.44) location.

88

Configuration Guides - DX-9100 Configuration Guide

Page 89

Reverse Action Connection RA@

The reverse action connection is a logic input to the control module, which changes the action of both controllers from direct to reverse or vice versa. Extreme caution is advised when using this connection when setpoint biases are also being used as the sign of the biases is not reversed. For correct controller operation, WSP2 must always be greater than WSP1. If the input is not connected, the controller will use the default value 0 and the function is disabled such that the defined action in PB@, PB1 or PB2 is always used. Via the GX Tool

Make a connection between the source point and the RA@ point of the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected reverse action logic variable under Program Modules at Alg. Item RA@ (RI.16) in the defined DUAL PID module. Output Bias

Each of the two output bias connections (OB1@, OB2@) is an analog input to the respective loop of the control module which biases the value of the output. If the input is not connected, the controller will use the output bias value OB1 or OB2. This option is normally used in a proportional only control module where the value of OBn determines the output of the respective control module when the PV is equal to the WSP. Via the GX Tool

Make a connection between the source point and the OB1@ point of the destination control module. Make a connection between the source point and the OB2@ destination point. Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. Enter a value at: •

Output Bias #1 (OB1)

•

Output Bias #2 (OB2)

Via the SX Tool

Configure the software connection by entering the source address of the selected output bias at Items OB1@ (RI.20) and OB2@ (RI.21). Alternatively, the internal output bias values are set under Program Modules at Alg. Items OB1 (RI.34) or OB2 (RI.50).

Configuration Guides - DX-9100 Configuration Guide

89

Page 90

Local Setpoint

Each of the two local setpoints is a value that represents the basic setpoint of the respective loop in the control module. It is a number that should be within the range of the process variable. LSP1 and LSP2 are disabled when Remote mode is enabled. When a WSP1 or WSP2 is adjusted from the front panel, the respective LSP is changed according to the formula below: WSPn = RVn (RSPn + LSPn) + (bias)n n=1,2

Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Local SP #1 (LSP1) and Local SP #2 (LSP2) fields, enter a value in units of PV. Via the SX Tool

Under Program Modules, select the DUAL PID module and enter values for the local setpoints at Alg. Items LSP1 (RI.26) and LSP2 (RI.43). Reset Actions

Each of the two reset actions is a number which defines the integration time for proportional-integral type control modules and is expressed in repeats per period of 1 minute, between 0 and 60. The integral time (Tn) may be computed from this number using the formula: Tn = 1/TI. Note: The integral term of each control loop is frozen when the loop becomes inactive and therefore determines the initial output of the loop when it again becomes active. Via the GX Tool

Select Dual PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Reset Action #1 (TI1) and Reset Action #2 (TI2) fields, enter a value. Via the SX Tool

Enter a value for the selected reset actions under Program Modules at Alg. Items TI1 (RI.28) or TI2 (RI.45).

90