Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 9 of 31

DX-9100 Configuration Guide: Software Configuration, pages 71 to 80

Pages 71 to 80 of 288, from DX-9100 Configuration Guide

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Johnson Controls DX-9100

Page 71

Via the SX Tool

Enter the low limit value at Item LOL (RI.37) in the defined PID module. Output

BOF BSB

Output

PB

100%

100%

HIGH LIMIT (HIL)

HIGH LIMIT (HIL)

LOW LIMIT (LOL) 0%

LOW LIMIT (LOL) 0% Off Standby Comfort

Process Variable

PB

BOF BSB

Process Variable Off Standby Comfort dxcon008

Figure 8: Reverse Acting Controller (Negative PB)/ Direct Acting Controller (Positive PB) Deviation Alarm Values

The deviation alarm values define the values which, when exceeded by the difference between the process variable and the working setpoint, will automatically generate a deviation alarm. A low low deviation alarm indicates that the process variable is lower than the working setpoint by more than the low low deviation alarm value. Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev L. L. Limit (DLL) field, enter a value in units of PV. Via the SX Tool

The low low deviation alarm value can be entered at Alg. Item DLL (RI.41). A low deviation alarm indicates that the process variable is lower than the working setpoint by more than the low deviation alarm value.

Configuration Guides - DX-9100 Configuration Guide

71

Page 72

Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev Low Limit (DL) field, enter a value in units of PV. Via the SX Tool

The low deviation alarm value can be entered at Alg. Item DL (RI.40). A high deviation alarm indicates that the process variable exceeds the working setpoint by more than the high deviation alarm value. Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev High Limit (DH) field, enter a value in units of PV. Via the SX Tool

The high deviation alarm value can be entered at Alg. Item DH (RI.39). A high high deviation alarm indicates that the process variable exceeds the working setpoint by more than the high high deviation alarm value. Via the GX Tool

Select the PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Dev H. H. Limit (DHH) field, enter a value in units of PV. Via the SX Tool

The high high deviation alarm value can be entered at Alg. Item DHH (RI.38). Note: Except for the PID to P changeover described next, deviation alarms do not affect the control program operation unless the associated logic variables are used in other programmable modules. Deviation alarms do not light the LED on the DX front panel. Enable PID to P

72

If a PID control module is in a high high or low low deviation alarm condition, it will operate as a proportional-only control module when Enable PID to P is set. The Enable PID to P change on deviation alarm feature sets the integral term to zero when the process variable is far from setpoint, and the controller will convert from a PI or PID controller to a proportional only controller. This is done to prevent wind-up of the integration term when the process variable is outside of the normal control range.

Configuration Guides - DX-9100 Configuration Guide

Page 73

PV P Only

HHDA PI or PID WSP

EDB

Term Frozen

Time EDB

PI or PID P Only

LLDA dxcon010

Figure 9: Enable PID to P Via the GX Tool

Select the defined PID. Then select Data in the module menu. At the Ena PID to P: 0=N field, entering a 1 will enable this feature. Via the SX Tool

This parameter is defined through Program Modules at PM Item PMnOPT (RI.01) in the PID module, with the following bit structure: X7 = 1

Error Deadband

PIDP

Enable PID to P change automatically on the Deviation Alarm (LLDA or HHDA).

The error deadband is defined in % of the proportional band PB. When the process error (PV-WSP) is within this deadband, the integral term is frozen. The deadband is applied above and below setpoint and in the units of the PV is equal to: (EDB/100) * (PB/100) * Range of the PV (AIn) or (EDB/100) * (PB/100) * 100 (all other numeric values) Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Err Dadband (EDB) field, enter the value for the desired error deadband. Via the SX Tool

The error deadband is entered in Item EDB (RI.33) in the PID Module.

Configuration Guides - DX-9100 Configuration Guide

73

Page 74

Symmetrical Transfer Function

The control algorithm may be configured to operate as a P controller with a symmetrical transfer function, where the comfort cooling setpoint is calculated by adding a constant symmetry band to the comfort heating setpoint and the control module action is reversed. When the control module is in Standby or Off mode, there is a shift of the setpoints as shown in the figure below. For correct symmetrical operation, the controller must normally be set up as a reverse acting (heating) proportional controller, with no integral or derivative action, and the reverse action connection RA@ is not used. Use this option when you need a single setpoint for two control loops. Use a dual module for two setpoints. Via the GX Tool

Select the defined PID. Then select Data in the module menu. At the Ena Symm mode: 0=N field, enter 1 to enable this feature. Then select Data-2 to go to page 2, and at the Symmetry Band (SBC) field, enter a value to add to the setpoint to determine the cooling setpoint. Via the SX Tool

This symmetric operation is enabled under Program Modules at PM Item PMnOPT, bit X5 (RI.01) in the PID module. The symmetry band constant is entered at Item SBC (RI.32). Output

BOF BSB

PB

PB

BOF BSB

100 % HIGH LIMIT (HIL)

Process Variable

LOW LIMIT (LOL) 0% Off Standby

SBC Comfort

Off Standby Comfort dxcon011

Figure 10: Controller with Symmetric Operation (Proportional Controller Only)

74

Configuration Guides - DX-9100 Configuration Guide

Page 75

Notes

1.

The output, biases, PB, rate, and reset parameters can be read and modified from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

2.

With the SX Tool, the various outputs of the control algorithm can be seen at Items OCM (RI.60), WSP (RI.61), PV (RI.62), RSP (RI.66), and RV (RI.67).

3.

The logic status of the control algorithm can be seen at PM Item PMnST (RI.72) with the SX Tool, with the following bit structure: X1 = 1

CML

Controller Output at Low Limit

X2 = 1

CMH

Controller Output at High Limit

X3 = 1

FORC

Force-back to OCM from AO is active. FORC is set when the connected AO (analog output) is in Hold mode. The value of the AO is also forced back, or set into the OCM, to provide bumpless override control for a PID module with an integral action.

X5 = 1

LLDA

Low Low Deviation Alarm

X6 = 1

LDA

Low Deviation Alarm

X7 = 1

HDA

High Deviation Alarm

X8 = 1

HHDA High High Deviation Alarm

X9 = 1

SOF

Shutoff mode Active

X10= 1

STA

Startup mode Active

X11= 1

EF

External Forcing Active

X12= 1

OF

Off Mode Active

X13= 1

SB

Standby Mode Active

X14= 1

RA

Reverse Action Mode

X15 = 0

HEAT

(Cooling Controller or PV above center of SBC in Symmetric Operation)

X15 = 1

HEAT

(Heating Controller or PV below center of SBC in Symmetric Operation)

Status Items can be used as logic (digital) connections using the GX Tool or SX Tool.

Configuration Guides - DX-9100 Configuration Guide

75

Page 76

GX Labels

Source Points (Outputs)

PMnCMH

A 1 when a control module’s output is equal to its output high limit.

PMnCML

A 1 when a control module’s output is equal to its output low limit.

PMnCMP

A 1 when the control module’s WSP is being overridden by a BAS (Computer mode).

PMnEF

A 1 when this control module is being externally forced.

PMnHDA

A 1 when the difference PV - WSP is larger than the high deviation alarm value.

PMnHEAT

A 1 when, in a symmetric control module, the PV is below the center of the symmetry band, and a 0 when above center; or a 1 when, in a dual control module, Loop 1 is active.

PMnHHDA A 1 when the difference PV - WSP is larger than the high high deviation alarm value.

76

PMnHLD

A 1 when the program module is in the Hold mode, being overridden by the SX Tool or a BAS.

PMnLDA

A 1 when the difference WSP - PV is larger than the low deviation alarm value.

PMnLLDA

A 1 when the difference WSP - PV is larger than the low low deviation alarm value.

PMnLSP

The value of the local setpoint. (This value is changed when adjusting the WSP from the DX front panel.)

PMnOCM

The value of the PID control module output in percent; either a 1 or 0 for an On/Off control module.

PMnSOF

A 1 when this control module is in the Shutoff mode, which occurs when enable shutoff = 1 and the BAS has commanded it On.

PMnSTA

A 1 when this control module is in the Startup mode, which occurs when enable startup = 1 and the BAS has commanded it On.

PMnWSP

The value of a control module working setpoint.

Configuration Guides - DX-9100 Configuration Guide

Page 77

Destination Points (Inputs)

EF@

The connection to the external forcing point of control modules.

MNWS@

The connection to the minimum working setpoint of a control module. The WSP cannot be adjusted below this value.

MXWS@

The connection to the maximum working setpoint of a control module. The WSP cannot be adjusted above this value.

OB@

The connection of an output bias value of a PID module.

OF@

The connection to the off-mode source point of a control module.

PB@

The connection to proportional band, which replaces the value PB if there is a connection.

PV@

The connection to the process variable of a PID or an On/Off.

RA@

The connection to the reverse action point of a control module.

RS@

The connection to a remote setpoint, which is used in the calculation for the working setpoint.

RV@

The connection to reference variable which is a multiplier in the calculation for the working setpoint.

SB@

The connection to the standby source point of a control module.

Configuration Guides - DX-9100 Configuration Guide

77

Page 78

Algorithm 02 On/Off Control Module Setting Supervisory Control Options

These options are a series of parameters that define how the On/Off Control Module operates and reacts to BAS commands. Via the GX Tool

Select the defined On/Off module. Then select Data in the module menu. At the Ena Shutoff: 0=N field, enter a 1 to enable this function. At the Shutoff Out Level field, enter 0 for Off and 1 for On. It will go to the specified state if Shutoff is enabled and the BAS has set Shutoff in the controller. At the Ena Startup: 0=N field, enter a 1 to enable the function. At the Startup Out Level field, enter 0 for Off and 1 for On. It will go to the specified state if Startup is enabled, and the BAS has set Startup in the controller. Via the SX Tool

These parameters are defined under Program Modules at PM Item PMnOPT (RI.01) of the On/Off module, with the following bit structure:

Process Variable Connection PV

X1 = 1

SOFE

Enable Shutoff mode from BAS

X2

SOFL

0=0, 1=1 Shutoff out level

X3 = 1

STAE

Enable Startup mode from BAS

X4

STAL

0=0, 1=1 Startup out level

The Process Variable (PV) is an analog value connection to the control module. When the process variable is not equal to the setpoint, the controller responds by changing its output value in accordance with the On/Off parameters. Via the GX Tool

Make a connection between the source point and PV@ in the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected process variable at Alg. Item PV@ (RI.10) in the defined On/Off module.

78

Configuration Guides - DX-9100 Configuration Guide

Page 79

Remote Setpoint Connection RS@

The Remote Setpoint (RSP) is an analog variable in the control module, in units of PV, which produces a bias in the local setpoint. If the input is not connected, the controller will use the default value 0. WSP = RV (RSP + LSP) + bias Via the GX Tool

Make a connection between the source point and RS@ in the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected remote setpoint at Alg. Item RS@ (RI.11) in the defined On/Off module. Reference Variable Connection RV@

The Reference Variable (RV) is an analog variable to the control module, which causes the control module to perform as a ratio controller. Its effect is a multiplier in the working setpoint calculation. If the input is not connected, the controller will use the default value 1. WSP = RV (RSP + LSP) + bias Via the GX Tool

Make a connection between the source point and RV@ in the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected reference variable at Alg. Item RV@ (RI.12) in the defined On/Off module. Reverse Action Connection RA@

The Reverse Action connection or RA@ is a logic input to the control module which changes its action from direct to reverse or vice versa. If the input is not connected, the controller will use the default value 0 and the function is disabled such that the defined action in ACT is always used. Note: When reverse action is a logic 1, the DX front panel PB will not show that it has been reversed.

Configuration Guides - DX-9100 Configuration Guide

79

Page 80

Via the GX Tool

Make a connection between the source point and RA@ in the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected reverse action logic variable at Alg. Item RA@ (RI.16). Local Setpoint

The Local Setpoint or LSP is a value that represents the basic setpoint of the control module. It is a number that should be within the range of the process variable. The LSP is disabled when Remote mode is enabled. When a WSP adjustment is made from the front panel, it is the LSP that is actually changed according to the formula below: WSP = RV (RSP + LSP) + bias Via the GX Tool

Select On/Off. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Local Set Pt (LSP) field, enter the setpoint of the module. Via the SX Tool

Under Program Modules, select the On/Off module and enter a value for the local setpoint at Alg. Item LSP (RI.26). Action Mode

The Action mode or ACT is a value that defines the action of the control module. A -1 will define a reverse acting control module; a decrease of the process variable below WSP will cause the output to switch to On (1). A +1 will define a direct acting control module; an increase of the process variable above WSP will cause the output to switch to On (1). Via the GX Tool

Select On/Off. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Action (ACT) field, enter 1 or -1. Via the SX Tool

Under Program Modules, select the On/Off module and enter 1 or -1 as the Action mode at Alg. Item ACT (RI.27).

80

Configuration Guides - DX-9100 Configuration Guide