Page 61

Output Forcing Actions

Commands from a BAS or connections to logic variables may override the output calculated by the control algorithm, forcing it to a preprogrammed level of 0 or 1 for On/Off algorithms and 0-100% for PID algorithms. While forcing is active, the module will stop calculating until forcing is disabled. Each forcing condition is associated with an output forcing level. The possible forcing conditions, ordered in priority, are: •

Shutoff mode (BAS only)

•

Startup mode (BAS only)

•

External Forcing mode

The function of each mode may be individually enabled in each control module. The configuration of startup and shutoff are also described under Supervisory Mode Control Settings (General Module). External Forcing

With External Forcing mode, the control module output will assume a configured forcing level between 0 and 100% for PID algorithms and of 0 or 1 for On/Off algorithms, overriding the output limits of the control module. Via the GX Tool

Expand source and destination modules. Make a connection between the source point and EF@ in the destination model. When the connection is a 1, the output will go to the value specified at ExtForce Out Level (provided Shutoff and Startup are not active). Select the defined PMn. Then select Data in the module menu. For a PID module, at the ExtForce Out Level (EFL) field, enter the desired level as a number in percent of output. For On/Off modules at the ExtForce Out Level field enter 0 for Off and 1 for On.

Configuration Guides - DX-9100 Configuration Guide

61

Page 62

Via the SX Tool

External forcing is a software connection, which is configured by entering the source address of the selected logic variable under Program Modules, at the Alg. Item location EF@ (RI.17) of the defined PID module. The forcing level for PID controllers is read and modified at the Item location EFL (RI.59) of the defined PID module. The forcing level for On/Off controllers is entered at Item location OPT, bit X6: X6 = 1

= On

X6 = 0 = Off The status of the modes can be seen at Alg. Item PMnST (RI.72) follows:

Programmable Module Notes

62

X9 =

Shutoff mode (SOFF)

X10 =

Startup mode (STUP)

X11 =

External Forcing (EF)

1.

The WSP, off mode bias, and standby bias can be read and modified by the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

2.

For control module operations refer to Algorithms 1-4 in this document.

3.

For details of the Hold mode and Computer mode, refer to Supervisory Mode Control Settings (General Module) later in this document.

4.

When the PID algorithm is using integral action, forcing actions to either a PID or a connected AO will modify the integral term (I Term) such that the internally calculated output of the control module is equal to the forced value. This provides bumpless transfer when the forcing is removed. In other words when the forcing is removed, the output does not immediately change, but integrates to the new control output value. If there is another module between the PID module and the AO (a high selected, for example) and the AO is overridden, the I Term will not be modified.

Configuration Guides - DX-9100 Configuration Guide

Page 63

Control Algorithm Theory

The DX executes all modules and all of its calculations once every second. The calculations below assume that the output low/high limits are 0 to 100. HHDA LLDA HDA LDA CMH CML

OB@

OB

PB@

PB

PV@

PV

RV@

RV

RS@

RS

EF

STA

SOF HOLD f=(PB,TI,TD,EDB)

OCM Output

LSP REM

OF@

OF

SB@

SB

RA@

RA

EF@

EF

F (Modes, BSB,BOF)

WSP

Limiting And Forcing

HIL LOL

CMP

STAE SOFE

Computer

Start Up Shut Off Hold

Dxcon007

Supervisory Modes:

Figure 7: Control Module Block Diagram The PID algorithm is defined by the following equations: Proportional Control Algorithm

The standard proportional control algorithm is as follows: P. Output = (100/PB) * Deviation + output bias (OB) Where: P. Output = proportional output of control module in % PB

= Proportional Band, defined as the amount of change in the process variable, that produces a change of 0 to 100 on the output of the control module

Deviation = the difference (error) of the Process Variable (PV) and the Working Setpoint (WSP) With proportional control, the deviation (or control error) is at zero only when the output bias value matches the output value required to attain the setpoint under the actual load conditions.

Configuration Guides - DX-9100 Configuration Guide

63

Page 64

Integral Control Algorithm

When using the integral (reset action) in a PID control module, the proportional output is increased or decreased by the integral output which is determined through the following mathematical relationship: I. Output(t)

=

I. Output(t-1) + (Proportional Output * TI *[1/60])

I. Output(t)

=

Current integral output

I. Output(t-1)

=

Previous integral output

TI

=

Reset action, expressed in repeats of proportional control response per minute

Where:

Reset action is used to compensate for the deviation (or error) in proportional control and reduces the deviation towards zero over time. The integral computation is stopped as soon as the control module output calculates its high or low output limits. An integral time of zero disables the integral action. The output of a PI algorithm is: PI Output = P. Output + I. Output Although the PI Output is normally limited to 0-100, the P. Output and I. Output can individually be a negative number. Derivative Control Algorithm

When using the derivative action (rate action) in a PID control module, the 0-100 output is modified through the following mathematical calculation: D. Output(t)

=

[(PV(t) - PV(t-1)) * CD] + (D. Output(t-1) * BD)

=

Current Derivative Output

D. Output(t-1) =

Previous Derivative Output

PV(t) PV(t-1)

=

Current Process Variable in % of input range

=

Previous Process Variable in % of range

BD

=

(60 * TD) / [4 + (60 * TD)]

CD

=

120 * TD * (1 - BD) * 100/PB

TD

=

Rate action: a time constant determining the rate of decay of the derivative output to ensure stable control.

Where: D. Output(t)

Rate action is the braking response in case approach to the setpoint is too rapid and may pass, or the accelerating response in case the deviation from the setpoint is too rapid and may not be corrected quickly enough by PI control.

64

Configuration Guides - DX-9100 Configuration Guide

Page 65

Most commercial HVAC applications will not require derivative action. A rate action equal to zero disables the derivative term. The output of a PID algorithm is: PID Output = P.Output + I.Output + D.Output Algorithm 01 PID Control Module Setting Supervisory Control Options

These options are a series of parameters that define how the PID Control Module operates and reacts to BAS commands. For more information, refer to Supervisory Mode Control Settings (General Module) later in this document. Via the GX Tool

Select the defined PID module. Then select Data in the module menu. At the Ena Shutoff: 0=N field, enter a 1 to enable this function. At the Shutoff Out Level field, enter a value for the output to go to if Ena Shutoff = 1 and the BAS has set Shut off in the controller. At the Ena Startup: 0=N field, enter a 1 to enable this function. At the Startup Out Level= field, enter a value for the output to go to if Ena Startup = 1 and the BAS has set Startup in the controller. At the Ena Off Trans: 0=N field, enter a 1 if the module is required to operate in Off mode when the BAS has set Shutoff and the process variable is below the Off mode working setpoint (WSP). This is only used in reverse acting modules (negative proportional band) for heating applications for low temperature protection. Via the SX Tool

These parameters are defined under Program Modules at PM Item PMnOPT (RI.01) of the PID module, with the following bit structure: X1 = 1 SOFE Enable Shutoff mode from BAS X3 = 1 STAE Enable Startup mode from BAS X9 = 1 SOTO Enable Shutoff to Off Change

Configuration Guides - DX-9100 Configuration Guide

65

Page 66

Process Variable Connection PV@

The Process Variable (PV) is an analog value connection to the control module. When the process variable is not equal to the setpoint, the controller responds by changing its output value in accordance with the PID parameters. Via the GX Tool

Make a connection between the source point and PV@ in the destination control module. Via the SX Tool

Under Program Modules, configure the software connection by entering the source address of the selected process variable at the PV@ Item (RI.10) location in the defined PID module. Remote Setpoint Connection RS@

The Remote Setpoint (RSP) is an analog variable in the control module, in units of PV, which produces a bias in the local setpoint. If the input is not connected, the controller will use the default value 0. WSP = RV (RSP + LSP) + (bias)n Via the GX Tool

Make a connection between the source point and RS@ in the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected remote setpoint at the RS@ Item (RI.11) location in the defined PID module. Reference Variable Connection RV@

The Reference Variable (RV) is an analog variable to the control module, which causes the control module to perform as a ratio controller. Its effect is a multiplier in the working setpoint calculation. If the input is not connected, the controller will use the default value 1. WSP = RV (RSP + LSP) + (bias)n Via the GX Tool

Make a connection between the source point and RV@ in the destination control module.

66

Configuration Guides - DX-9100 Configuration Guide

Page 67

Via the SX Tool

The software connection is configured by entering the source address of the selected reference variable at the RV@ Item (RI.12) location in the defined PID module. Proportional Band

The proportional band is a number that defines the action and sensitivity of the control module. A negative number defines a reverse acting control module; an increase of the process variable produces a decrease in the output signal. A positive number defines a direct acting control module; an increase of the process variable produces an increase in the output signal. The number itself is an analog input connection (PB@) or value (PB) that is expressed as a percentage of the process variable range. When the process variable is one of the eight analog inputs to the DX-9100 Controller, the PV range is the range of the active analog input or the control range of the passive analog input. Otherwise, the range defaults to 0-100 (including all XP analog inputs). The connection is used for an application requiring a dynamic proportional band, and if this input is not connected, the controller will use the proportional band value of PB. The number itself defines the percentage of the process variable range change that will produce a full output signal change. For example, if the process variable has a control range of 0 to 100, a proportional band of 2% indicates that a change of 2 in the process variable will cause the control module output signal to change by 100%. If the process variable range is 0-40, a proportional band of 10% indicates that a change of 4 in the process variable will cause the control module output signal to change by 100%. Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Proport. Band (PB) field, enter the required value. Alternatively, make a connection between the source point and PB@ of the control module. Via the SX Tool

Under Program Modules, select the PID module. The software connection is configured by entering the source address of the selected proportional band at the PB@ Item (RI.13) location in the defined PID module; or, enter a value for the proportional band at the PB Item (RI.27) location.

Configuration Guides - DX-9100 Configuration Guide

67

Page 68

Reverse Action Connection RA@

The Reverse Action Connection is a logic input to the control module, which changes its action from direct to reverse or vice versa. If the input is not connected, the controller uses the default value 0 and the function is disabled such that the defined action in PB is always used. The reverse action connection should not normally be used when the controller is configured as symmetric. The DX front panel will not show that the PB has been reversed by this connection. Via the GX Tool

Make a connection between the source point and the RA@ point of the destination control module. Via the SX Tool

Configure the software connection by entering the source address of the selected reverse action logic variable at the RA@ Item (RI.16) location in the defined PID modules. Output Bias

The Output Bias Connection or OB@ is an analog input to the control module which biases the value of the output. If the input is not connected, the controller uses the output bias value OB. This option is normally used in a proportional-only control module where the value of OB determines the output of the control module when the PV is equal to the WSP. Via the GX Tool

Make a connection between the source point and the OB@ destination point. Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Output Bias (OB) field, enter a value from 0 to 100. In a P-only controller, this will be the output value when PV = WSP. Via the SX Tool

Configure the software connection by entering the source address of the selected output bias at the OB@ Item (RI.20) location. Alternatively, enter the output bias value at the OB Item (RI.34) location.

68

Configuration Guides - DX-9100 Configuration Guide

Page 69

Local Setpoint

The local setpoint or LSP is a value that represents the basic setpoint of the control module. It is a number that should be within the range of the process variable. The LSP is disabled (ignored) in Remote mode. When a WSP adjustment is made from the front panel, it is the LSP that is actually changed according to the formula below: WSP = RV (RSP + LSP) + bias Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Local Setpoint (LSP) field, enter the setpoint of the module. To enable the Remote mode, enter a 1 at the Remote mode: 0 = N field. If 1, the setpoint will be calculated as follows: WSP = RV (RSP) + bias Via the SX Tool

Under Program Modules, select the PID module and enter a value for the local setpoint at the LSP Item (RI.26) location. To enable the Remote mode, set Alg. Item REM (RI.01), bit X8 to 1. Reset Action

Reset action or TI is a number that defines the integration time for proportional-integral type control modules and is expressed in repeats per period of 1 minute, between 0 and 60, with one decimal place. The integral time Tn may be computed from this number using the formula: Tn = 1/TI. Reset action should normally be set to 0 for symmetrical action controllers. Note: To clear the reset action from the DX front panel, set the value to any negative number. Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Reset Action (TI) field, enter a value between 0 and 60. Via the SX Tool

Under Program Modules, select the PID module and enter a value for the reset action at the TI Item (RI.28) location. A zero number and all negative numbers will disable the integral action of the controller.

Configuration Guides - DX-9100 Configuration Guide

69

Page 70

Rate Action

Rate action or TD defines the derivative action decay time parameter and is entered in minutes, between 0 and 5, with one decimal place. Rate action should normally be set to 0 for symmetrical action controllers. Note: To clear the rate action from the DX front panel, set the value to any negative number. Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Rate Action (TD) field, enter a value between 0 and 5. Via the SX Tool

Under Program Modules, select the PID module and enter a value for the rate action at the TD Item (RI.29) location. A zero number and all negative numbers will disable the rate action of the controller. Output High Limit

The High Limit or HIL is a number in percent of the output, which defines a high limit value for the control module output. The default value is 100, and must always be higher than the low limit. Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Out High Lmt (HIL) field, enter the high limit in terms of percentage. Via the SX Tool

Enter the high limit value at Item HIL (RI.36) in the defined PID module. Output Low Limit

The Low Limit or LOL is a number in percent of the output, which defines a low limit value for the control module output. The default value is 0, and must always be lower than the high limit. The lower limit is overridden when the control module is in Off mode and the output falls to 0. Via the GX Tool

Select the defined PID. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Out Low Lmt (LOL) field, enter the lower limit in terms of percentage.

70

Configuration Guides - DX-9100 Configuration Guide