Page 51

Network Analog Input Configuration (Version 3 Only)

The controller has 16 network analog input modules, each contains a numerical value received from an analog output in another controller on the same LONWORKS N2 Bus. These inputs can be used in the configuration in the same way as physical analog inputs. The source of the analog data is defined in the transmitting controller.

User Tag Name and Type

For each network analog input module one must define: •

User Tag Name and Description

•

Network Analog Input Units (SX Only)

Via the GX Tool

Select PM from the toolbar, then Network Analog Input, and place the NAIn on the screen. Select NAIn and Data. Enter the User Name and Description in the Data Window. The Units number is automatically set by the GX Tool. Via the SX Tool

To configure a network analog input using the SX Tool, it is necessary to enter the units of the NAI in Item NAInDIM (RI.18 to RI.33) under NETWORK (Key 8), INPUT MODULES, and 2 (NETWORK AI MOD). There is only one unit used by the DX-912x, which is number 55. It is also necessary to change Item NAIN (RI.04) under NETWORK and GENERAL MODULE when the first NAI is defined. This Item must be set to 1 if any NAIs are used in the configuration. These Items are automatically set by the GX Tool when the NAI is created. NAI Notes

1.

On the SX Tool the numeric value of the network analog inputs can be read at Items NAIn (RI.01 to RI.16) under NETWORK and INPUT MODULES.

2.

On the SX Tool the Reliability Status of each analog input module can be seen on bits X1 to X16 at Item NAISTA (RI.17). These status indications can be used for backup control strategies in the case of a transmission failure by using the corresponding logic variables (NAIU1 to NAIU16) in the PLC. The Reliability Status will be set to 1 (Unreliable) when the DX Controller does not receive a new value over the network within a period of approximately 200 seconds.

Configuration Guides - DX-9100 Configuration Guide

51

Page 52

GX Labels

Source Points (Outputs)

NAIn

The current value of the Network Analog Input.

NAIUn

A 1 when the analog input module is unreliable.

Destination Points (Inputs)

None. Network Digital Input Configuration (Version 3 Only)

The controller has 8 network digital input modules, each contains 16 digital input status values received from a network digital output in another controller. Each of the 16 digital values in the digital input module can be used in the configuration in the same way as physical digital inputs. The source of the digital data is defined in the transmitting controller. Digital data is always transmitted in blocks of 16 values from 1 controller to another and the block cannot be split apart by the network. Not all 16 values need be used and within the controller the values can be used quite independently. For each network digital input module one must define:

User Tag Name and Type

•

User Tag Name and Description

•

Network Digital Input Type (SX Only)

Via the GX Tool

Select PM from the toolbar, then Network Digital Input, and place the NDIn on the screen. Select NDIn and Data. Enter the User Name and Description in the Data Window. The Type number is automatically set by the GX Tool. Via the SX Tool

To configure a network digital input using the SX Tool, it is necessary to enter the type of the NDI in Item NDInTYP (RI.10 to RI.17) under NETWORK (Key 8), INPUT MODULES, and 1 (NETWORK DI MOD.). There is only one type used by the DX-9100, which is number 83. It is also necessary to change Item NDIN (RI.03) under NETWORK and GENERAL MODULE when the first NDI is defined. This Item must be set to 1 if any NDIs are used in the configuration. These Items are automatically set by the GX Tool when the NDI is created.

52

Configuration Guides - DX-9100 Configuration Guide

Page 53

NDI Notes

GX Labels

1.

On the SX Tool the status values of the 16 digital inputs in each of the 8 network digital input modules can be read at bits X1 to X16 in Items NDIn (RI.01 to RI.8) under NETWORK, INPUT MODULES, and 1 (NETWORK DI MOD). The status values can be used in the configuration by connecting the corresponding logic variables NDIn-1 to NDIn-16.

2.

On the SX Tool the Reliability Status of each digital input module can be seen on bits X1 to X8 at Item NDISTA (RI.9). These status indications can be used for backup control strategies in the case of a transmission failure by using the corresponding logic variables (NDIU1 to NDIU8) in the PLC. The Reliability Status will be set to 1 (Unreliable) when the DX controller does not receive a new value over the network within a period of approximately 200 seconds.

Source Points (Outputs)

NDIn-m The current value of the Network Digital Input. NDIUn

A 1 when the digital input module is unreliable.

Destination Points (Inputs)

None. Network Analog Output Configuration (Version 3 Only)

The controller has 16 network analog output modules, each of which can transmit a numerical value to another controller on the same LONWORKS N2 Bus. The network analog output module receives its value from a connection to a numeric Item in the same controller. Each network analog output module, if configured, sends its value to up to 16 destinations which are, in fact, network analog input modules in other controllers on the same network. A maximum of 30 Version 3 controllers can be connected to one LONWORKS N2 Bus. For each network analog output module one must define: •

User Tag Name and Description

•

Network Analog Output Units (SX Only)

• up to 16 destinations (controller address and network input module number)

• source of the output value

Configuration Guides - DX-9100 Configuration Guide

53

Page 54

User Tag Name and Units

Via the GX Tool

Select PM, then Network Analog Output, and place the NAOn on the screen. Select NAOn and Data. Enter the User Name and Description in the Data Window. The Units number is automatically set by the GX Tool. Via the SX Tool

When defining a network analog output module, it is necessary to enter the units of the NAO in Item NAOnDIM (RI.03) under NETWORK (Key 8), OUTPUT MODULES, and 2 (NETWORK AO MODn) (n = 1-16). There is only one unit used by the DX-9100, which is number 55. It is also necessary to change Item NAON (RI.02) under NETWORK and GENERAL MODULE. This Item must contain the number (0 to 16) of NAOs used in the configuration. These Items are automatically set by the GX Tool. NAO Destinations

Via the GX Tool

Select NAOn and Data. In the field Destination #1 enter a destination controller address (1-255) and a network input number (1-16) within the destination controller. Continue entering destinations as required up to the limit of 16. Only enter the address of controllers, which will be connected, to the same LONWORKS N2 Bus and use a network analog input number in a destination controller only once in the configuration. Via the SX Tool

Destinations are configured in Items NAOn>1 to NAOn>16 (RI.04 to RI.19) under NETWORK (Key 8), OUTPUT MODULES, and 2 (NETWORK AO MODn) (n = 1-16). Enter the Destination Input number (NAI) (1-16) and Destination Controller Address (1-255). An Input number of 0 cancels the destination. NAO Source

Via GX Tool

Expand NAOn to show the input NAOnAO@. Expand the source module with the desired output numeric Item and make the connection. The connection source may be seen in the NAO Data Window in the field Source Point. Via SX Tool

Connections are defined in Items NAOn@ (RI.20) under NETWORK (Key 8), OUTPUT MODULES, and 2 (NETWORK AO MODn) (n = 1-16). Enter a numeric Item address.

54

Configuration Guides - DX-9100 Configuration Guide

Page 55

NAO Note

On the SX Tool the numeric value of the network analog outputs can be read at Items NAOnOUT (RI.01) under NETWORK, OUTPUT MODULES, and 2 (NETWORK AO MODn) (n = 1-16).

GX Labels

Source Points (Outputs)

None. Destination Points (Inputs)

NAOn@ The numeric connection to control a Network Analog Output. Network Digital Output Configuration (Version 3 Only)

The controller has 8 network digital output modules, each of which can transmit 16 digital status values to another controller on the same LONWORKS N2 Bus. Each of the 16 digital values in the digital output module receives its status from a logic variable in the same controller. Each network digital output module, if configured, sends its 16 digital status values as a block to up to 16 destinations which are, network digital input modules in other controllers on the same network. A maximum of 30 Version 3 controllers can be connected to one LONWORKS N2 Bus. For each network digital output module one must define:

User Tag Name and Type

•

User Tag Name and Description

•

Network Digital Output Type (SX Only)

• up to 16 destinations (controller address and network input module number)

• sources of the 16 digital status values

Via the GX Tool

Select PM, then Network Digital Output, and place NDOn on the screen. Select NDOn and Data. Enter the User Name and Description in the Data Window. The Type number is automatically set by the GX Tool. Via the SX Tool

When defining a network digital output module it is necessary to enter the type of NDO in Item NDOnTYP (RI.03) under NETWORK (Key 8), OUTPUT MODULES, and 1 (NETWORK NDO MODn) (n = 1-8). There is only one type used by the DX-9100, which is number 83. It is also necessary to change Item NDON (RI.01) under NETWORK and GENERAL MODULE. This Item must contain the number (0-8) of NDOs used in the configuration. These Items are automatically set by the GX Tool.

Configuration Guides - DX-9100 Configuration Guide

55

Page 56

NDO Destinations

Via the GX Tool

Select NDOn and Data. In the Data Window, select Data-2 to go to page 2. In the field Destination #1 enter a destination controller address (1-255) and a network input number (1 to 8) within the destination controller. Continue entering destinations as required up to the limit of 16. Only enter the address of controllers that will be connected to the same LONWORKS N2 Bus and use a network digital input number in a destination controller only once in the configuration. All 16 source points will be sent as a block to each destination defined. Via the SX Tool

Destinations are configured in Items NDOn>1 to NDOn>16 (RI.04 to RI.19) under NETWORK (Key 8), OUTPUT MODULES, and 1 (NETWORK DO MODn) (n = 1-8). Enter the Destination Input number (NDI) (1-8) and Destination Controller Address (1-255). An Input number of 0 cancels the destination. NDO Sources

Via GX Tool

Expand NDOn to show the inputs NDOn-1@ to NDOn-16@. Expand the source module with the desired output logic variable and make the connection. The connection sources may be seen in the NDO Data Window in the fields Source bit #1 to Source bit #16. Via SX Tool

Connections are defined in Items NDOn-1@ to NDOn-16@ (RI.20 to RI.35) under NETWORK (Key 8), OUTPUT MODULES, and 1 (NETWORK DO MODn) (n = 1-8). Enter a logic variable index byte and bit number. NDO Note

On the SX Tool, the 16 status values of each of the 8 network digital output modules can be read at Items NDOn (RI.01) under NETWORK, OUTPUT MODULES, and 1 (NETWORK DO MODn) (n = 1-8).

GX Labels

Source Points (Outputs)

None. Destination Points (Inputs)

NDOn-m@

56

The logic connection to control a Network Digital Output.

Configuration Guides - DX-9100 Configuration Guide

Page 57

Programmable Function Module Configuration

The DX-9100 provides twelve programmable function modules that are sequentially executed each second. The module’s function, inputs, and outputs depend on the algorithm assigned to it. The assignment is made by programming the module to correspond to the algorithm. Once the PM is defined to perform a specific function, the remaining entries of the module can be defined to achieve the desired output.

Parameter Tags

Each of the twelve programmable function modules has a set of generic parameters, each with a PM Tag. Each of the available algorithms has a specific set of parameters, each with an algorithm tag (Alg. Tag). When an algorithm is assigned to a programmable function module, a parameter has two tags: • one PM Tag, which represents the generic function in the programmable function module

• one Alg. Tag, which represents the specific function of the parameter in the assigned algorithm

For example, the process variable connection in a PID control algorithm assigned to Programmable Function Module 1 has a generic tag, PM1I1@. In Algorithm 1 (PID controller) this same parameter has the tag PV@. Both tags are listed in the Item list for the algorithms; one as PM Tag and the other as Alg. Tag. Note: In the GX Tool, algorithm tags are used exclusively. When mapping Items to a BAS, such as Metasys PM tags are used. Control Algorithm Configurations

The DX-9100 provides four control algorithms: • PID Controller • On/Off Controller • Heating/Cooling PID Controller (Dual PID) • Heating/Cooling On/Off Controller (Dual On/Off) Each of these algorithms can be used in any one of the twelve programmable function modules. The algorithms have a number of different operating modes, which are a function of operating parameters and digital connections. Each control module operates from its Working Setpoint (WSP), which is a resultant value calculated by the controller from the Reference Variable (RV), the Local Setpoint (LSP), the Remote Setpoint (RSP), the Standby Mode Bias (BSB), and the Off Mode Bias (BOF). The algorithm then compares the Working Setpoint (WSP) with the Process Variable (PV) to generate an output (OCM). Configuration Guides - DX-9100 Configuration Guide

57

Page 58

•

Comfort mode (or Occupied mode) is the working mode of the algorithm to obtain the desired control typical during occupancy. The output is calculated by the control algorithm using as working setpoint the value: WSP = RV * (LSP + RSP) This mode is active when both Standby and Off modes are disabled.

•

When operating in Standby mode the controller setpoint may be reduced or increased when compared with the Comfort mode setpoint. The output is calculated by the control algorithm using as working setpoint the value: WSP = RV * (LSP + RSP) + BSB This mode is active when the standby module control connection is a Logic 1 and the Off mode is disabled. The standby bias is a signed number, expressed in the same units as the PV.

•

Off mode (Unoccupied mode) is similar to the Standby mode, but the setpoint may be further reduced or increased. The output is calculated by the control algorithm using the following function: WSP = RV * (LSP + RSP) + BOF This mode is active when the Off mode control connection is a Logic 1. The off bias is a signed number, expressed in the same units as the PV. In the Off mode, the output low limit of the controller is not used and the output can fall to 0. If both Standby and Off modes are active, the control module uses the Off mode working setpoint.

58

Configuration Guides - DX-9100 Configuration Guide

Page 59

Via the GX Tool

Before establishing the mode, you must first set the PM type to Control and then to the appropriate type. Click on PM in the toolbar, select Control, then PID, On/Off, Dual PID, or Dual On/Off, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. Enter control parameters and modes. To go to page 2, click on Data 2. At Standby Bias (BSB) or Off mode Bias (BOF), enter a value to bias the WSP. For Dual PID or Dual On/Off modules, enter values for each loop at Stdby Bias #1 (BSB1), Off Bias #1 (BOF1), Stdby Bias #2 (BSB2), and Off Bias #2 (BOF2). To define the mode connections, expand source and destination modules. Position the cursor on the source point. Press the mouse button, and while keeping it pressed, drag the cursor to SB@. Release the mouse button to make the connection. For Off mode, make a similar connection between the respective source point and OF@. When the connected logic variable is in a 1 state, the value entered will be used to calculate the WSP of the module. The WSP is always the active setpoint of the module. Via the SX Tool

Define the PM type under Program Modules PMnTYP (RI.00): 1

= PID Controller

2

= On/Off

3

= Dual PID

4

= Dual On/Off

Then set the modes of operation under Program Modules: PMnOF@ (RI.14) defines the Off mode control logic connection. PMnSB@ (RI.15) defines the Standby mode control logic connection. BSB1 (RI.30) defines the bias value during Standby mode in Loop 1. BOF1 (RI.31) defines the bias value during Off mode in Loop 1. For Dual PID and Dual On/Off only: BSB2 (RI.47) defines the bias value during Standby mode in Loop 2. BSF2 (RI.48) defines the bias value during Off mode in Loop 2. The mode status of the controller can be read at Item PMnST (RI.72) as follows: X13 = Standby Mode (SB) X12 = Off Mode (OF) Configuration Guides - DX-9100 Configuration Guide

59

Page 60

Remote Mode

In Remote mode, the local setpoint is excluded from the calculation of the working setpoint, and the WSP cannot be modified from the front panel of the controller. Via the GX Tool

Select the defined PMn, then Data in the module menu. At the Remote mode: (0 = N) = field, enter 0 or 1: If 0, the module will calculate from: WSP = RV * (LSP + RSP) + bias If 1, the module will calculate from: WSP = RV * (RSP) + bias Via the SX Tool

Under Program Modules, select the PID Module and set bit X8 in Item PMnOPT (RI.01):

Minimum/ Maximum Working Setpoint

X8 = 0

No Remote mode.

X8 = 1

Remote mode enabled.

For the DX-9100, Version 1.1 or later, the calculated WSP value cannot lie outside of limits set either by numeric connections or entered parameters. If there are no connections, the values entered at Minimum Working Setpoint and Maximum Working Setpoint will be used. When modifying the WSP from the front panel of the controller, it is not possible to set a value for WSP, which lies outside of the set limits. Via the GX Tool

Select the defined PMn. Then select Data in the module menu. In the Data Window, select Data-2 to go to page 2. At the Minimum WSP (MNWS) and Maximum WSP (MXWS) fields, enter values to not exceed the working setpoint. To use source points for MNWS and MXWS, connect the respective source points to MNWS@ and MXWS@. The values of source points will take priority over entered values. Via the SX Tool

Under Program Modules, select the PID modules and set the following: MNWS@ (RI.22) defines numeric connection for Min. WSP. MNWS (RI.35) defines the numeric value of Min. WSP. MXWS@ (RI.23) defines the numeric connection for Max. WSP. MXWS (RI.42) defines the numeric value for Max. WSP.

60