DX-9100 Configuration Guide: Software Configuration, pages 41 to 50

Pages 41 to 50 of 288, from DX-9100 Configuration Guide

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Johnson Controls DX-9100

Page 41

Via the GX Tool

Select PM from the toolbar, and then Analog Constants. An ACO module (box) appears. Place it where desired on screen. Select ACO. Then select Data in the module menu. Enter the values as required. Select OK to reconfirm entries, or Cancel to discard them. Via the SX Tool

Under General Module, set Items AC01 - 8 (RI. 34-41). Digital Constants

There are 32 Digital Constants in the DX-9100. The value of each constant can be set by the SX-9120 Service Module, GX-9100 Graphic Configuration Tool, or BAS, and used in a logic connection to provide a logic value for a programmable function module, output module or PLC module. In a Version 2 controller, the digital constants may also be set at the front display panel. These values are not located in EEPROM and therefore can be written to via the BAS. Via the GX Tool

Select PM from the toolbar, and then Digital Constants. A DCO module (box) appears. Place it where desired on screen. Select DCO. Then select Data in the module menu. Enter the values as required. Select OK to reconfirm entries, or Cancel to discard them. Via the SX Tool

Under General Module, set Items LCOS1 and LCOS2 (RI.10, RI.11). LCOS1 is DCO1-16. LCOS2 is DCO17-32. Logic Result Status:

There are 64 Logic Result Status variables in the DX-9100 (in Version 1.0, only 32 are available). The value of each status variable can be set by the OUT, OUTNOT, SET, or RST instruction of the PLC module, and can be used in a logic connection to provide a logic value for a programmable function module, output module, or PLC module. The variables can also be used to transmit status conditions to a BAS. These values are read only and can only be changed by PLC execution. Via GX Tool

Select PM from the toolbar, and then select LRS1-32 (or LRS33-64). A module (box) will appear. Place it as desired on screen. Connections can be made in the usual way. (See Configuration Tools - Making Connections earlier in this document.)

Configuration Guides - DX-9100 Configuration Guide

41

Page 42

Via SX Tool

Under General Module, the logic result status variables can be read at Items LRST1, LRST2, LRST3, and LRST4 (RI.08, RI.09, RI.44, RI.45). LRST1 is LRS1-16. LRST2 is LRS17-32. LRST3 is LRS33-48. LRST4 is LRS 49-64. Analog Constants, Digital Constants Note

The analog and digital constants can be read and modified (Versions 2 and 3) from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

GX Labels

Source Points (Outputs)

ACOn

The current value of an analog constant set by a supervisory system, the GX Tool, SX Tool, or on the DX front panel.

DCOn

The current value of a digital constant set by a supervisory system, the GX Tool, SX Tool, or on the DX front panel.

LRSn

The logic result status of an OUT, OUTNOT, SET, or RST statement in a PLC.

Destinations Points

None. Extension Module Configuration

Note: The XTM-905 extension module may be connected to DX controllers, Versions 1.4, 2.3, 3.3, or later, and is configured, monitored and controlled using the same Items as the XT-9100 extension module. The parameters for the configuration of inputs and outputs in extension modules reside partly in the DX-9100 Controller and partly in the XT-9100 or XTM-905 Extension Module. The parameters required by the DX-9100 Controller are described in detail in this manual. For details on the extension modules, refer to the XT-9100 Technical Bulletin (LIT-6364040) and the XT-9100 Configuration Guide (LIT-6364050), or the XTM-905 Extension Module, XPx-xxx Expansion Modules Technical Bulletin (LIT-6364210).

42

Configuration Guides - DX-9100 Configuration Guide

Page 43

Each extension module is defined by the following parameters:

XT/XTM: Type, Mode, and Map

• input and output types, and XT/XTM layout map

• extension module address

• sources (connections) for outputs

• high and low ranges for analog outputs

• high and low limits for analog inputs

Via the GX Tool

The I/O type and map details are automatically generated by the GX-9100 Graphic Configuration Software when all I/O data for extension modules has been entered, and can be downloaded to the DX-9100 and also to the extension modules when connected to the DX-9100 via the XT Bus. Select PM from the toolbar, then XT or XTM and the appropriate input/output type. A module (box) appears. Place it where desired on screen. The inputs and outputs for the XT/XTM appear on the left and right sides of the screen, respectively. Configure each input/output as appropriate (similarly to DX I/O). A module labeled XTn or XTMn will be for the points in the first XP connected to that XT or XTM. If a second XP is connected, the EXP module must be defined immediately following the first XT or XTM. An EXPn is always an expansion to the XTn-1 or XTMn-1 module.

Configuration Guides - DX-9100 Configuration Guide

43

Page 44

Via the SX Tool

The I/O types and map are configured in Extension Module Items, under XT Modules at XTnIOMAP (RI.00), XTnIOTYP (RI.01), and XTnIOMOD (RI.02). The I/O map (XTnIOMAP) defines which inputs/outputs (in pairs) on the extension module are used and hence monitored or controlled by the DX-9100. Eight extension modules can be defined, each with eight used points, which normally reside on the first Expansion Module XP1 (I/O Points 1-8), defined in bits X1-4. When an extension module has a second expansion module, XP2, with a further eight points, these points must be defined in bits X5-8. However, in this case, the next extension module in numerical sequence cannot be configured because the DX-9100 will use the database area reserved for the I/O points of the next extension module for the points of XP2 in this extension module. For example, if Extension Module 1 (XT1 or XTM1) has only one expansion module, XP1, all the points of XP2 will be declared as not used (bits X5-8 set to 0) and Extension Module 2 can be configured. However if Extension Module 1 has two expansion modules and some points in XP2 are declared as used (one or more bits of X5-8 set to 1), then Extension Module 2 (XT2 or XTM2) cannot be configured and all its points must be declared as not used (bits X1-8 set to 0).The I/O type (XTnIOTYP) defines which inputs/outputs (in pairs) are analog and which are digital. As the points on XP2 (if used) must be digital, only bits X1-4 can be configured. The I/O mode (XTnIOMOD) defines points as input or output (in pairs). Only those points declared as used in Item XTnIOMAP will be monitored or controlled. The combination of data in the Items XTnIOMAP, XTnIOTYP, and XTnIOMOD completely defines the configuration of an extension module. An identical set of data must be entered into the Item database in the XT-9100 or XTM-905 extension module, so that when the DX-9100 and XT/XTM are connected and started up, the DX-9100 compares databases and only send commands to the extension module if the data is identical, thus avoiding incorrect control actions. If the databases are not identical, Item XTnST, bit X6 (XTnERR) will be set. If the physical hardware of the XT/XTM module does not correspond to the database, Item XTnST, bit X4 (XTnHARD) is set.

44

Configuration Guides - DX-9100 Configuration Guide

Page 45

XT/XTM: Address, User Name, Description

The extension module address is set as an 8-bit integer (1-255). This address must also be set on the address switches of the extension module, and must be unique not only on the XT-Bus, but also on the N2 Bus (or Bus 91) to which the DX-9100 is connected. An extension module address of 0 is not permitted on the XT Bus. Via the GX Tool

Select XTn. Then select Data in the module menu. Enter the user name and description in the window that appears. In the Hardware Address field, enter the address set on the XT-9100 or XTM-905 module (a number between 1 and 255). Via the SX Tool

The extension module address is set under XT Modules, in Item XTnADX (RI.03). XT/XTM: Source

Only output points require a source connection. For analog outputs the source must define a numeric variable, and for digital outputs the source must define a logic variable. Inputs and outputs appear on the left and right sides of the screen, respectively. Via the GX Tool

Expand source and destination modules. Position the cursor on the source point. Press the mouse button, and while keeping it pressed, drag the cursor to the destination point. Release the mouse button to make the connection. Via the SX Tool

The sources for the points declared as outputs in XP1 of XTn or XTMn are entered under XT Modules at Items XTnI1@-8@ (RI.04-11). The sources for the points declared as outputs in XP2 of XTn (if used) are entered in Items XT(n+1)I1@-8@ in the next extension module Item area (n+1). All points in this next module must already have been declared unused.

Configuration Guides - DX-9100 Configuration Guide

45

Page 46

XT/XTM: High and Low Ranges for Analog Outputs

For analog outputs, the Analog High Range (AHR) defines the level of the source control signal that will correspond to the maximum output at the extension module, and the Analog Low Range (ALR) defines the level of the source control signal that corresponds to the minimum output at the extension module. The value of the output is defined as follows: If XTnALR < XTnI < XTnAHR

XTnAO =

If XTnI < XTnALR

XTnAO = 0%

If XTnI > XTnAHR

XTnAO = 100%

100 x ( XTnI − XTnALR ) ( XTnAHR − XTnALR )

Where XTnI is the value for the source control signal. Via the GX Tool

Select the XT analog output point module. Then select Data in the module menu. Enter appropriate values within the range of the source signal under both the High Range and Low Range fields: High Range

=

Low Range

=

Also enter the appropriate value in the Type of Output field. Via the SX Tool

Under XT Modules, set the following Items:

XT/XTM: High and Low Limits for Analog Inputs

46

Analog High Range =

Items XTnAHR1-8 (RI.12-26, evens)

Analog Low Range =

Items XTnALR1-8 (RI.13-27, odds)

The high limit and the low limit define at which levels the analog input reading will generate an alarm for remote monitoring purposes or for internal use within the control sequences in the DX-9100. These limits will be automatically downloaded to the extension module by the DX-9100.

Configuration Guides - DX-9100 Configuration Guide

Page 47

Via the GX Tool

Select the XT analog input point module and choose Active or Passive. Then click the right mouse button to call up the module menu and select Data. In the window that appears, enter appropriate values under both the High Limit and Low Limit fields: High Limit= Low Limit = Via the SX Tool

Under XT Modules, set the following Items: High limit = Items XTnHIA1-8 (RI.28-42, evens) Low limit = Items XTnLOA1-8 (RI.29-43, odds) XT Bus Timing

The timeout on the XT Bus for the response to a message is set according to whether XT-9100 or XTM-905 extension modules are connected. Via the GX Tool

The timing is set automatically by the GX Tool. Via the SX Tool

Under General Module, Item DXS1 (RI.32) set the following bits:

XT/XTM Notes

X6X5 = 00

XT-9100 extension modules only

X6X5 = 01

XTM-905 extension modules (or both XT-9100 and XTM-905)

1.

XT/XTM analog input values can be read, and alarm limits read and modified from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

2.

On the SX Tool, analog input values can be read under XT Modules at Items XTnAI1-8 (RI.45-52). Only those points configured as analog inputs will be active.

3.

Analog outputs can be read and overridden (put in hold) at the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

4.

On the SX Tool, analog output values can be read in percent under XT Modules at Items XTnAO1-8 (RI.53-60). Only those points configured as analog outputs, and with the type of output defined, will be active. Configuration Guides - DX-9100 Configuration Guide

47

Page 48

5.

On the SX Tool, the total pulse count of digital inputs on XP1 can be read and reset under XT Modules at Items XTnCNT1-8 (RI.61-68). Only those points configured as digital inputs will show a correct value.

6.

Output hold control and status can be seen on the SX Tool under XT Modules at Items XTnOUH1-8 (bits X1-8 of Item XTnHDC [RI.69]). Analog and digital outputs can be modified by a BAS when in Hold mode.

7.

XT/XTM digital outputs can be read and overridden (put in hold) from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

8.

Digital output control and status can be seen on the SX Tool under XT Modules at Items XTnDO1-8 (bits X1-8 of Item XTnDO [RI.70]). Only those points configured as digital outputs will be active.

9.

XT/XTM digital inputs can be read from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

10. Digital input status can be seen on the SX Tool under XT Modules at Items XTnDI1-8 (bits X1-8 of Item XTnDI [RI.71]). Only those points configured as digital inputs will be active. 11. Extension module alarm status from analog inputs can be seen on the SX Tool under XT Modules at Items XTnAIH1-XTnAIL8 (bits X1-16 of Item XTnAIS [RI.44]). Note: The Alarm Disable connection, described under AI: Alarm Limits, does not disable XT module alarms. XT/XTM alarms are only indicated by the AL LED on the DX front panel when the XT/XTM is selected for display of analog values.

48

Configuration Guides - DX-9100 Configuration Guide

Page 49

12. Extension module local status can be seen on the SX Tool under XT Modules at Item XTnST (RI.72) in the following bits: X1

= 1 XTnCOM

XT/XTM module not answering (wrong address, bus line broken, bus line overload).

X3

= 1 XTnMIS

XT databases in DX and XT/XTM do not match.

X4

= 1 XTnHARD XT/XTM hardware failure (XT/XTM cannot find correct XPs; hardware missing or not responding).

X5

= 1 XTnSEL

XT/XTM selected on XT-Bus.

X6

= 1 XTnERR

XT/XTM configuration error XTnCOM = 1 or XTnMIS=1 or XTnHARD = 1 (Versions 1.4, 2.3, 3.3, or later)

X7

= 0 XTnFAIL

XT/XTM digital outputs set to 0 on communication failure.

X7

=1

XT/XTM digital outputs hold current state on communication failure. Read from XT module. See the XT-9100 Configuration Guide (LIT-6364050) or the XTM-905 Extension Module, XPx-xxx Expansion Modules Technical Bulletin (LIT-6364210).

X8

= 1 XTnPWR

XT/XTM detected loss of power or loss of communication.

Item X8 is automatically reset by the DX-9100 Controller after a few seconds.

Configuration Guides - DX-9100 Configuration Guide

49

Page 50

GX Labels

Source Points (Outputs)

XTnAIn

The current value of the analog input from the XT/XTM.

XTnAIHn

A 1 if the analog input is above its high limit and not below the high limit - limit differential.

XTnAILn

A 1 if the analog input is below the low limit and not above the low limit + limit differential.

XTnAOn

The value of the analog output to the XT/XTM.

XTnCOM

A 1 when the extension module is not communicating (wrong address, bus line broken, or bus line overload).

XTnDIn

The current status of the digital input from the XT/XTM.

XTnDOn

The status of the digital output to the XT/XTM.

XTnERR

A 1 when the XT database in the DX does not match the XT database in the XT/XTM module, or when XTnCOM is a 1, or when XTnHARD is a 1 (Versions 1.4, 2.3, 3.3, or later). (Combination of errors for XT/XTM module.)

XTnFAIL

The status of the Fail mode in the XT/XTM. A 0 indicates that outputs go to 0 on communication failure and a 1 indicates that the status of the outputs will be maintained.

XTnHARD

A 1 when the expansion module is not connected or not responding (hardware fault), or a module type does not match what was configured (for example, when an XP-9102 is configured and an XP-9103 is connected).

XTnOUHn

A 1 when an analog or digital output is in Hold mode from either the DX front panel or BAS.

XTnPWR

A 1 when the extension module detects a loss of power or loss of communication. The DX will reset this after a few seconds.

Destination Points (Inputs)

AO@ The numeric connection to control an analog output. DO@ The connection to control a digital output.

50

Configuration Guides - DX-9100 Configuration Guide