Page 31
GX Labels
Source Points (Outputs)
AOFn
A 1 when an analog output (AO) is being externally forced.
AOHn
A 1 when the analog output is equal to or above its high range.
AOLn
A 1 when the analog output is equal to or below its low range.
OUHn
A 1 when an analog or digital output is in Hold mode from either the DX front panel or BAS.
OUTn
The value of the analog output (including PAT or DAT).
Destination Points (Inputs)
AO@
The numeric connection to control an analog output.
AOF@
The connection to force an analog output to a specified value.
DEC@
The connection to decrement an analog type output, PAT/DAT digital type output or a sequencer module. While connection is a logic 1, the output will decrease at a rate dependent on the type of module.
ENL@
The connection to enable output limits of an analog type output (PAT and DAT included).
INC@
The connection to increment an analog type output, PAT/DAT digital type output or a sequencer module. While connection is a logic 1, the output will increase at a rate dependent on the type of module.
Configuration Guides - DX-9100 Configuration Guide
31
Page 32
Digital Output Configuration
The DX-9100 Controller has six digital output modules that are used to control six triacs. The digital output module provides the interface between a triac output and a numeric or logic variable. The modules can be programmed as one of five main output types. Some of the output types drive two consecutive outputs. In that case the second, consecutive module will be disabled, as it cannot be executed. For each digital output module one must define: • the type of output
•
User Name and Description
For digital output modules defined as PAT or DAT, you must also define: • the source
• increase/decrease source (if any)
• the source of the feedback (if any) (PAT only)
• the low and high ranges
• the Forcing Mode and Level
•
Hold or Auto on power up
• output limits, enable limits source (if any)
• the PAT full stroke time or DAT cycle
• the PAT deadband or DAT minimum on/off time
The types of configurations are described next, followed by the steps needed to configure the outputs. PAT Position Adjust Type
The PAT output type uses a pair of triacs and a numeric source. Position Adjust Type control is also known as incremental control. Using High Range and Low Range parameters, the value of the numerical source is normalized to a 0-100% value and is used as the required position for the output. The PAT output may have a physical feedback value signal (0-100%) from an analog input or other numerical variable. In this configuration the output module will drive the first triac of the pair (increase or up signal) as long as the feedback value is less than the required position. It will drive the second triac of the pair (decrease or down signal) as long as the feedback value is greater than the required position. A deadband (in percent) is specified to avoid unnecessary cycling of the triac outputs when the feedback signal is approaching the required position, and compensates for any hysteresis or mechanical tolerances in the driven device.
32
Configuration Guides - DX-9100 Configuration Guide
Page 33
When the PAT output does not have a physical feedback signal, it operates on the amount of change in the required position. To synchronize the PAT output module to the driven device, whenever the required position goes to 100%, the first triac (increase) will be switched on for the calculated time and will remain on for the specified Full Stroke Time of the driven device. Whenever the required position goes to 0%, the second triac (decrease) will be switched on for the calculated time and will remain on for the specified Full Stroke Time. If the required position remains at 100% or 0%, the appropriate triac will be switched on for the Full Stroke Time every two hours to ensure that the driven device remains at its end position over an extended period of time. For all other values of the required position, the PAT output module calculates the appropriate increase or decrease time, based on the Full Stroke Time, to bring the driven device from the last required position to the current required position, and switches the appropriate triac on for this time. The triac will not be switched if the change in the required position is less than the specified deadband. The calculation of the PAT time is performed on each processor cycle (every second), and the minimum triac on time is 100 msec. Note: The DX display panel shows the required position value (OUTn) for the digital output module associated with the first triac output. DAT Duration Adjust Type
The DAT output type provides a time-based duty cycle output that is proportional to the value of a numeric source. Using High Range and Low Range parameters, the value of the numerical source is normalized to a 0-100% value as is used as the required duty cycle. For example, with a 25% duty cycle and a DAT cycle time of 600 seconds, the triac output will be switched on for 150 seconds and off for 450 seconds. At 0% required duty cycle the triac is always off, and at 100% duty cycle the triac is always on. To avoid short on pulses when the required duty cycle is close to 0%, or short off pulses when the required duty cycle is close to 100%, a minimum on/off time may be specified (in percent of duty cycle). For applications with a short DAT duty cycle (< 10 sec) it should be noted that the absolute minimum on or off time of the output triac is 100 msec. The DAT will always complete a calculated on or off period before recalculating the next off or on time from the current value of the numeric source. The DAT recalculates after its on time and after its off time so a full on/off cycle may not equal the repetition cycle if the numeric source is changing.
On/Off
This type provides a single maintained on/off triac output. It can be driven by either a logic source or numeric source where a positive value would equal an on and a zero or negative value would equal an off.
Configuration Guides - DX-9100 Configuration Guide
33
Page 34
STA/STO
This type uses a pair of triac outputs and requires a logic source. A start command (logic source changes from 0 to 1) sends a one second pulse to the first triac of the pair and a stop command (logic source changes from 1 to 0) sends a one second pulse to the second triac. Note: The DX display panel shows the status of the logic source to the digital output module associated with the first triac output. This displayed status is also the last command (on or off) to the triac pair. The display does not indicate the actual triac status.
PULSE
This type provides a single momentary triac output from a logic source. When the logic source becomes a 1, a one second pulse is sent to the triac. When the logic source changes to 0, a one second pulse is sent to the same triac.
DO: Output Type User Name and Description
Via the GX Tool
Double-click on DOn with the left mouse button. Then select one of the following: PAT, DAT, On/Off, STA/STO, or PULSE. Select DOn using the right mouse button. Then select Data in the module menu. Enter the user name and description in the respective fields. Via the SX Tool
For each digital output module the type of output can be selected with the following bits under Output Modules in Item DOTn (RI.00): X3 X2 X1 = 000
Output disabled or paired.
X3 X2 X1 = 001
On/Off - driven from a logic source.
X3 X2 X1 = 010
On/Off - driven from a numeric source (< 0 = off, > 0 = on).
X3 X2 X1 = 011
DAT (Duration Adjust Type) output, or time-based proportional duty cycle, driven from a numeric source.
X3 X2 X1 = 100
PAT without feedback: combination of two outputs, driven from a numeric source. Note: The next output is automatically taken from the next Digital Output Module in numerical sequence.
X3 X2 X1 = 101
34
PAT with Feedback: combination of two outputs, driven from a numeric source with an associated feedback connection.
Configuration Guides - DX-9100 Configuration Guide
Page 35
DO: Source
X3 X2 X1 = 110
Start/Stop: combination of two outputs driven from a logic source. This module gives the start command, and the next digital output (in numerical sequence) gives the stop command. Each triac switches on for one second.
X3 X2 X1 = 111
Pulse Type: the output generates a one second pulse for each state transition of a logic source.
This defines the source of the signal that will drive the output module. PAT and DAT output modules, alternatively to one numeric source, can have two logic sources: the source of the increase signal and the source of the decrease signal. The rate of increase or decrease for PAT type outputs is derived from the full stroke time. For DAT type outputs the rate is 1% per second. Via the GX Tool
Expand both source and DOn modules. Position the cursor on the source point. Press the mouse button, and while keeping it pressed, drag the cursor to DOn@. Release the mouse button to make the connection. Alternatively, for PAT and DAT modules, you can select sources for increase and decrease. Connections are made in the usual way between the increase source point and INC@, and between the decrease source point and DEC@ in the DOn module. Via the SX Tool
Under Output Modules, the signal source is defined by Item DO@n (RI.01). PAT and DAT output modules can, alternatively, have two logic sources. The source of the increase signal is defined in Item INC@n (RI.13), and the source of the decrease signal is defined in Item DEC@n (RI.14). DO: Feedback for PAT
This defines the source of the analog feedback (0-100%) that is needed for the PAT with feedback type module. Via the GX Tool
Expand the source and destination modules. Position the cursor on the source point. Press the mouse button, and while keeping it pressed, drag the cursor to FB@. Release the mouse button to make the connection. Via the SX Tool
Under Output Modules, Item FB@n (RI.02) defines the source of the analog feedback. Configuration Guides - DX-9100 Configuration Guide
35
Page 36
DO: Range (PAT or DAT)
The High Range (HRO) defines the level of the control numeric source signal, which will correspond to the maximum output of 100%. The Low Range (LRO) defines the level of the numeric control source signal, which will correspond to the minimum output of 0%. The requested output is scaled to obtain: OUTn = 100 * (DOn - LROn) / (HROn - LROn) % Where DOn is the value of the control signal to the module (source value). Via the GX Tool
Select DOn. Then select Data in the module menu. At the High Range and Low Range fields, enter the desired numbers within the range of the source control signal. Via the SX Tool
Under Output Modules, set the following: High Range at Item HROn (RI.04) Low Range at Item LROn (RI.05) DO: Forcing Mode and Level (PAT or DAT
This defines the source of a logic signal that forces the logic module output to a forcing level. When the logic connection is a 1, the output will go to a forced level; when 0, the output will go to normal control. Via the GX Tool
Select DOn. Then select Data in the module menu. At the Forcing Level field, enter a number from 0 to 100%. Expand the source and destination modules. Position the cursor on the logic source point. Press the mouse button, and while keeping it pressed, drag the cursor to DOF@. Release the mouse button to make the connection. Via the SX Tool
Under Output Modules, Item DOF@n (RI.03) defines the source; Item OFLn (RI.10) defines the forcing level. DO: Hold or Auto On Power Up (PAT or DAT
36
Upon power restoration, the DO can optionally be forced to a Hold or Auto (Hold reset) condition, irrespective of the Hold condition before the power failure and overriding the Initialization on Power Up setting for the controller.
Configuration Guides - DX-9100 Configuration Guide
Page 37
Via the GX Tool
Select DOn. Then select Data in the module menu. Then enter 1 for the appropriate power up condition, if required: Hold on Power up = (1 = Yes) Auto on Power up = (1= Yes) If both Hold and Auto are enabled, Hold takes priority. If both are disabled, the current setting under the Initialization on Power Up field determines the output. Via the SX Tool
Under Output Modules, set bits X7 and X8 of Item DOTn (RI.00) as follows: bit X8 = 0 The Hold mode is not altered after a power failure. bit X8 = 1 The Hold mode is set at power up to the status set in bit X7. bit X7 = 0 The Hold mode is set to hold at power up if bit X8 is set. bit X7 = 1 The Hold mode is reset (set to 0) at power up if bit X8 is set. DO: Output Limits (PAT with Feedback or DAT
The output high limit defines the maximum output in percent. The output low limit defines the minimum output in percent. These limits are enabled by a logic connection and are only operative when the logic source is as 1. When the limits are enabled: If OUTn > HLOn OUTn = HLOn If OUTn < LLOn OUTn = LLOn Via the GX Tool
Select DOn. Then select Data in the module menu. At the High Range Limit % and Low Limit % fields, enter the desired numbers (0-100%). Expand source and destinations modules. Position the cursor on the source point. Press the mouse button, and while keeping it pressed, drag the cursor to ENLn@ in the destination module. Release the mouse button to make the connection.
Configuration Guides - DX-9100 Configuration Guide
37
Page 38
Via the SX Tool
Under Output Modules, set the following: High Limit on Output = Item HLOn (RI.08) Low Limit on Output = Item LLOn (RI.09) The limits are enabled by a logic connection to Item ENL@n (RI.15). DO: PAT Full Stroke Time or DAT Cycle
The full stroke time (in seconds) needs to be defined for PAT type modules. This is the time it takes the electromechanical actuator to drive the controlled device from fully open to fully closed or vice versa. The DAT cycle (in seconds) also needs to be defined. This is the duration adjust time proportion base for a DAT type output. Via the GX Tool
For PAT, select DOn. Then select Data in the module menu. At the Stroke Time (sec) field, enter the electro-mechanical actuator stroke time. For DAT, select DOn. Then select Data in the module menu. At the Repetition Cycle (sec) field, enter the cycle. Via the SX Tool
Under Output Modules, Item FSTn (RI.06) defines the full stroke time (in seconds) for PAT type modules. The same Item defines the DAT cycle (in seconds). DO: PAT Deadband
The PAT deadband is the change in output value required to initiate triac switching in a PAT type output.
DAT Minimum On/Off Time
The DAT minimum On/Off time defines in percent of cycle the shortest on period when the required output approaches 0%, and the shortest off period when the required output approaches 100%. Via the GX Tool
For PAT, select DOn. Then select Data in the module menu. At the Deadband field, enter the desired number (normally a whole number between 0 and 5%). For DAT, select DOn. Then select Data in the module menu. At the Minimum On/Off (%) field, enter the desired number in percentage of repetition cycle (normally between 0 and 5%).
38
Configuration Guides - DX-9100 Configuration Guide
Page 39
Via the SX Tool
Under Output Modules, Item DBn (RI.07) defines the PAT deadband. The same Item defines the DAT Minimum On/Off in % of output. DO Notes
1.
The DOs can be read and overridden (put in hold) from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.
2.
On the SX Tool, the output values can be read in percent at Output Modules, Item OUTn (RI.11). For PAT and DAT type modules the range is 0-100%. The other types have an output of 0 (off) or 100 (on) percent.
3.
Digital Output Control and Status can be seen at Item DOCn (RI.12) on the SX Tool in the following bits: X1 = 1
OUHn
Output in Hold mode (manual)
X2 = 1
DOHn
Output at High Limit ... 100%
X3 = 1
DOLn
Output at Low Limit ... 0%
X4 = 1
DOFn
Output is Forced
X5 = 1
AFBn
Incorrect Feedback
(The incorrect feedback bit is set whenever one of the PAT output triacs is switched on and the feedback signal does not change within five seconds.) X6 = 1
OULn
Output is Locked (both INC@n and DEC@n are true)
4.
The triac output status can be read on the SX Tool under General Module, at Item TOS (RI.05).
5.
The digital output module can be set in Hold (Manual) on the DX front panel or by the PLC, the SX Tool, a BAS, or by configuration on power up.
Configuration Guides - DX-9100 Configuration Guide
39
Page 40
GX Labels
Source Points (Outputs)
AFB
A 1 when the DO PAT associated feedback value is not responding to changes in the DO PAT command value.
DOn
The status of the digital output.
DOFn
A 1 when the digital output PAT or DAT is being externally forced.
DOHn
A 1 when the digital output PAT or DAT is at its defined high limit.
DOLn
A 1 when the digital output PAT or DAT is at its defined low limit.
OUHn
A 1 when an analog or digital output is in Hold mode from either the DX front panel or BAS.
OUTn
The value of the analog output (including PAT or DAT).
Destination Points (Inputs)
DEC@
The connection to decrement an analog type output, PAT/DAT digital type output or a sequencer module. While connection is a logic 1, the output will decrease at a rate dependent on the type of module.
DO@
The connection to control a digital output.
DOF@
The connection for forcing a digital output to a specified value.
ENL@
The connection to enable output limits of an analog type output (PAT and DAT included).
FB@
The connection to the feedback of a PAT. Usually a signal from a potentiometer on the controlled device.
INC@
The connection to increment an analog type output, PAT/DAT digital type output or a sequencer module. While connection is a logic 1, the output will increase at a rate dependent on the type of module.
Constants and Result Status Analog Constants
40
There are eight Analog Constants in the DX-9100. The value of each constant can be set by the SX-9120 Service Module, GX-9100 Configuration software, or BAS, used in an analog connection to provide a constant analog value for a programmable function module or output module. In a Version 2 or 3 controller, the analog constants may also be set at the DX front display panel. These values are not located in EEPROM and therefore can be written to via the BAS.