Page 21
To set the measurement units for active sensors, select the AIn module, and then Data to call up the Data Window. Enter in the Measurement Units field: 0 = None 1 = Temperature (C or F as entered under Edit-Global Data) 2 = Percent (%) (Version 1 only) In a Version 1 controller the units are displayed on the front panel of the controller as °t, %, or none. Via the SX Tool
Under Analog Inputs, configure Item AITn (RI.00). The measurement and temperature units of each analog input can be selected with the following bits (low byte): X4 X3 X2 X1 = 0000 No Units X4 X3 X2 X1 = 0001 Celsius X4 X3 X2 X1 = 0010 Fahrenheit X4 X3 X2 X1 = 0011 Percent (Version 1 only) For RTD sensor inputs, Celsius and Fahrenheit units must be selected. Changing individual units for each AI can only be done via the SX Tool. AI: Enable Square Root
This function allows the linearization of the differential pressure signal from a 0-10 VDC or 0/4-20 mA active sensor; the function is effective over the selected range and is only available for active sensors. AI = sqrt (PR%/100) * (HR - LR) + LR Where PR% = the Analog Value in % of the physical input signal range; HR = High Range Value; and LR = Low Range Value. Via the GX Tool (option only available with active sensor)
Select AIn. Then select Data in the module menu. At the Square Root field, enter 0 to disable the square root function, or 1 to enable the square root function. Via the SX Tool
Under Analog Inputs, configure Item AITn (RI.00) (low byte): X5 = 1 Enable Square Root of Input X5 = 0 Disable Square Root of Input AI: Alarm on Unfiltered Value
An alarm from the High Limit and Low Limit Alarm values will be generated from the unfiltered input. Configuration Guides - DX-9100 Configuration Guide
21
Page 22
Via the GX Tool
Select AIn. Then select Data in the module menu. At the Alarm Unfiltered field, enter 0 to set an alarm on a filtered value, or 1 to set an alarm on an unfiltered value. Via the SX Tool
Under Analog Inputs, configure Item AITn (RI.00) (low byte): X6 = 1 Alarm on Unfiltered Value X6 = 0 Alarm on Filtered Value AI: Alarm Limits
The high limit and the low limit define at which levels the analog input reading will generate an alarm, either for remote monitoring or for internal use within the control sequences in the DX-9100. A limit differential defines when a point comes out of alarm. Note: The limits cannot be deleted. If you do not want alarms, enter limits beyond the high/low range of the sensor.
High Limit
High Alarm
Differential No Alarm AI Value No Alarm Differential Low Limit Low Alarm dxcon005
Figure 5: How Alarm Limits Function Via the GX Tool
Select AIn. Then select Data in the module menu. At the respective field, enter the required value: High Limit
=
Low Limit
=
Limit Differential =
22
Configuration Guides - DX-9100 Configuration Guide
Page 23
The low limit and high limit alarm processing can be disabled. In the menu bar, select Edit-Add Alarm Disable. The corresponding module (box) will appear on screen. Make connections as described earlier under Configuration Tools - Making Connections. Note: The Alarm Disable feature is sometimes referred to as Auto Shutdown in the BAS. Via the SX Tool
Under Analog Inputs, the alarm limits differential is adjustable with Item ADFn (RI.06). The high limit is at Item HIAn (RI.03), the low limit is at Item LOAn (RI.04). The low and high limit alarm processing can be disabled by making a logical connection to Item ALD@ - Alarm Disable Condition Source (General Module RI.31). For Both SX and GX
When the logic signal connected to ALD@ or Alarm Disable Condition Source is true (1), alarm states on analog inputs will be frozen until the logical signal returns to false (0). (Alarm states on analog inputs to XT modules are not frozen by the ALD@ connection.) AI: Filter Time Constant
The Filter Time Constant Ts (seconds) is used to filter out any cyclic instability in the analog input signals. The calculations are: FVt = FVt-1 + [1/(1 + Ts)] * (AIt - FVt-1) Where: FVt = Filtered Analog Value at current time FVt-1 = Filtered Analog Value at previous poll AIt = Actual Analog Value at current time Via the GX Tool
Select AIn. Then select Data in the module menu. At the Filter Constant (sec) field, enter a number within the recommended range 0 to 10. Via the SX Tool
Under Analog Inputs, the Filter Time Constant is selected at Item FTCn (RI.05). AI Notes
1.
You can read the AI values, and read and modify the alarm limit values using the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4. Configuration Guides - DX-9100 Configuration Guide
23
Page 24
GX Labels
2.
The alarm condition of one or more analog inputs is also indicated by an LED (AL) on the front panel. If the LED is steady, the current AI is in alarm; if flashing, another AI is in alarm.
3.
Using the SX Tool, analog input values can be read at Analog Inputs Item AIn (RI.07), and the percent of range value can be read at Item AI%n (RI.08). The value as an ADC count can be read at Item ADCn (RI.09).
4.
Using the SX Tool, analog input alarm statuses can be read at General Module Item AIS (RI.07), or at Analog Input Item AISTn (RI.10), where bits X1 and X2 indicate the high and low alarm conditions, respectively.
5.
Under Analog Inputs, the analog Item AISTn (RI.10), bits X3 and X4, indicate an input over-range (input about 2% of range above HR) condition and an input under-range (input about 2% of range below LR) condition, respectively. (This information is available on the SX Tool only.)
6.
Calibration coefficients for active and passive analog inputs are stored in the EEPROM of the DX. See the Calibration Values section further in this document.
Source Points (Outputs)
AIn
The current value of the analog input.
AI%n
The current value of the analog input in percent (%) of range.
AIHn
A 1 if the analog input is above its high limit and not below the high limit - limit differential.
AILn
A 1 if the analog input is below the low limit and not above the low limit + limit differential.
OVRn
A 1 when the value of an active analog input is more than about 2% above its high range (overrange condition), or a passive analog input is open circuited.
UNRn
A 1 when the value of an active analog input is more than about 2% below its low range (underrange condition), or a passive analog input is short circuited.
Destination Points (Inputs)
None. Note: The following destination point is applicable to all analog inputs: ALDS@ The connection to disable alarm processing on analog inputs AI1 - AI8.
24
Configuration Guides - DX-9100 Configuration Guide
Page 25
Digital Input Configuration
The DX-9100 Controller can accept up to eight digital inputs, which will be considered active when driven to a common digital ground by an external volt-free contact. The DI is defined and configured by the following parameters: •
User Name and Description (GX only)
•
Prescaler
The digital input transitions are counted as follows: Digital
Prescale
Count
Pulse
Input
Factor
Transition
Counter
DIn
PCn
DICn
CNTRn dxcon006
Figure 6: Digital Input Transitions The Pulse Counter (CNTRn) counts all state transitions of the bit-Item DICn. A state transition at DICn occurs when the number of transitions from 1 to 0 of DIn Digital Input equals the value of the Prescaler Factor (PCn). For example, if PCn is equal to 1, then every 1 to 0 state transition at the DI will add 1 to CNTRn. If equal to 3, then three changes from 1 to 0 will add 1 to CNTRn. The maximum transition rate of DIn is 10 pulses per second (minimum 50 ms On and 50 ms Off). DI: User Name, Description, Prescaler
Via the GX Tool
Select DIn. Then select Data in the module menu. At the User Name field, enter the name, which can have a maximum of eight characters. At the Description field, enter the descriptive text, which can have a maximum of 24 characters. At the Prescaler (counts) field, enter a number between 1 and 255. Via the SX Tool
Under General Module, enter the prescaler for each digital input at Items PC1 (RI.22) to PC8 (RI.29). DI Notes
1.
You can read the DI’s status and counter values using the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.
2.
On the SX Tool, the digital input status (DIn), the count transition status (DICn) and the pulse counter values can be read under General Module at the Items given in Figure 6. Configuration Guides - DX-9100 Configuration Guide
25
Page 26
GX Labels
Source Points (Outputs)
DIn
The current status of the digital input.
DICn Toggles from 0 to 1 or 1 to 0 when the number of digital input transitions (counts) equals the prescaler. Destination Points (Inputs)
None. Analog Output Configuration
The DX-9100 Controller has two analog outputs (numbered 1 and 2), controlled by two analog output modules, and six digital (triac) outputs (numbered 3 to 8) controlled by six logic output modules. Versions 2 and 3 of the DX-9100 have an additional six analog outputs (numbered 9 to 14) controlled by six analog output modules. The analog output module provides the interface between a 0-10 VDC or 0/4-20 mA hardware output and a numeric value scaled to a 0-100% range using a high and low range variable. Each analog output is defined and configured by the following parameters:
AO: Output Type
• user name and description (GX Only)
• type of output
• numeric source
• increase/decrease source (if any)
• low and high ranges
• forcing mode and level
• hold or auto on power up
• output limits, enable limits
Via the GX Tool
Select AOn. Then select Data in the module menu. At the field User Name, enter the name. At the Description field, enter the description. Then enter the output code: 0 = Disabled 1 = 0 to 10 VDC 2 = 0 to 20 mA (not available for Outputs 11-14) 3 = 4 to 20 mA (not available for Output 11-14)
26
Configuration Guides - DX-9100 Configuration Guide
Page 27
Via the SX Tool
Under Output Modules, the output type can be configured in Item AOTn (RI.00). To define the output signal set the bits as follows:
AO: Source
X2 X1 = 00
Output Disabled
X2 X1 = 01
Output 0-10 V
X2 X1 = 10
Output 0-20 mA (not available for Outputs 11-14)
X2 X1 = 11
Output 4-20 mA (not available for Outputs 11-14)
This defines the source of the numeric control signal that drives the output module. The output module can, alternatively, have two logic sources: the source of the increase signal and the source of the decrease signal. The rate of increase or decrease is fixed at 1% per second. Via the GX Tool
Expand both source and AOn modules. Place the mouse on the source point. Hold down the left mouse button and drag the cursor to the center of AO@. The connection will be made when the mouse button is released. If logic variables (Increase/Decrease) are used as a source to drive the analog output, then the source module and AOn module must be expanded as described above. Place the cursor on the logic source point. Press the mouse button and while keeping it pressed, drag the cursor to INC@ in the AOn module. Release the mouse button to make the connection. Repeat the same procedure for the DEC@ connection. Via the SX Tool
Under Output Modules, Item AO@n (RI.01) defines the source of the numeric control signal. Alternatively, the source of the increase signal is defined in Item INC@n (RI.10), and the source of the decrease signal is defined in Item DEC@n (RI.11). AO: Forcing Mode and Level
This defines the source of a logic variable that forces the Analog Output to a forcing level between 0 and 100%. When the logic source is 1, the AO will be forced to the % entered in Forcing Level. When the logic source is 0, the AO will be commanded to position via the source point. Note: If a PID is connected to the AO and the AO is forced, the PID will experience force-back, which means the PID is also in Hold mode at this time and its output is forced to the value of the analog output.
Configuration Guides - DX-9100 Configuration Guide
27
Page 28
Via the GX Tool
Select AOn. Then select Data in the module menu. At the Forcing Level (%) = field, enter a number between 0 and 100%. Double-click on AOn to expand the module. Double-click on the source module. Place the cursor on the logic source point. Press the mouse button and while keeping it pressed, drag the cursor to AOF@. Release the mouse button to make the connection. Via the SX Tool
Under Output Modules, Item AOF@n (RI.02) defines the source of a logic variable that forces the output to the forcing level, which is defined in Item OFLn (RI.05). AO: Hold or Auto On Power Up
Upon power restoration, the AO can optionally be forced to a Hold (Manual) or Auto (Hold reset) condition, irrespective of the Hold condition before the power failure and overriding the Initialization on Power Up setting for the controller and overrides sent from the front panel or BAS. Via the GX Tool
Select AIn. Then select Data in the module menu. Then enter 1 for the appropriate power up condition, if required: Hold on Power Up
= (1 = Yes)
Auto on Power Up
= (1= Yes)
If both Hold and Auto are enabled, Hold has higher priority. If both are disabled, the current setting under the Initialization on Power Up field determines the output. Via the SX Tool
Under Output Modules, set bits X7 and X8 of Item AOTn (RI.00) as follows: bit X8 = 0 The Hold mode is not altered after a power failure. bit X8 = 1 The Hold mode is set at power up to the status set in bit X7. bit X7 = 0 The Hold mode is set to hold at power up if bit X8 is set. bit X7 = 1 The Hold mode is reset (set to 0) at power up if bit X8 is set.
28
Configuration Guides - DX-9100 Configuration Guide
Page 29
AO: Range
The High Range Item (HRO) defines the level of the control source signal (AOn), which would correspond to an output of 100%. The Low Range Item (LRO) defines the level of the control source signal (AOn), which would correspond to an output of 0%. If LROn < AOn < HROn
OUTn = 100 * (AOn - LROn)/(HROn LROn)%
If AOn <= LROn
OUTn = 0% (0 V, 0/4 mA)
If AOn >= HROn
OUTn = 100% (10 V, 20 mA)
When the source point is equal to the high range, then the output will be at the maximum signal (10 V/20 mA). When the source point is equal to low range, then the output will be at the minimum signal (0V, 0/4 mA). Via the GX Tool
Select AIn. Then select Data in the module menu. At the High Range and Low Range fields, enter the appropriate numbers within the range of the source signal: High Range = Low Range = Via the SX Tool
Under Output Modules, set the High Range at Item HROn (RI.03) and the Low Range at Item LRO (RI.04). AO: Output Limits, Enable Limits
The output high limit defines the maximum output in percent. The output low limit defines the minimum output in percent. These limits are enabled by a logic connection and are only operative when the logic source is at 1. When the limits are enabled: If OUTn > HLOn OUTn = HLOn If OUTn < LLOn OUTn = LLOn
Configuration Guides - DX-9100 Configuration Guide
29
Page 30
Via the GX Tool
Select AOn. Then select Data in the module menu. At the High Limit % and Low Limit % fields, enter the desired number (0-100%). For Enable Limits, expand both source and AOn modules. Position the cursor on the source point. Press the mouse button, and while keeping it pressed, drag the cursor to ENL@. Release the mouse button to make the connection. Via the SX Tool
Under Output Modules, set the following: High Limit on Output = Item HLOn (RI.08) Low Limit on Output = Item LLOn (RI.09) The limits are enabled by a logic connection to Item ENL@n (RI.12). AO Notes
1.
The AO can be read and overridden (placed in hold) from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.
2.
On the SX Tool, the analog output values can be read in percent at Item OUTn (RI.06) and can be modified when the module is in Hold mode.
3.
On the SX Tool, Analog output control and status can be seen at Item AOCn (RI.07) in the following bits:
4.
30
X1 = 1
OUHn
Output in Hold mode (Manual)
X2 = 1
AOHn
Output at High Limit ... 100%
X3 = 1
AOLn
Output at Low Limit ... 0%
X4 = 1
AOFn
Output is Forced
X6 = 1
OULn
Output is Locked (Both INC@n and DEC@n are true)
The analog output module can be set in Hold on the DX front panel or by the PLC, the SX Tool, a BAS, or by configuration on power up.